Evaluation of Carbon Dioxide Concentrations and Ventilation Rates in Elementary, Middle, and High Schools

초·중·고등학교의 이산화탄소 농도 및 환기량 평가

  • Choe, Youngtae (Department of Occupational Health, Daegu Catholic University) ;
  • Heo, Jung (Department of Occupational Health, Daegu Catholic University) ;
  • Park, Jinhyeon (Department of Occupational Health, Daegu Catholic University) ;
  • Kim, Eunchae (Department of Occupational Health, Daegu Catholic University) ;
  • Ryu, Hyoensu (Department of Occupational Health, Daegu Catholic University) ;
  • Kim, Dong Jun (Department of Occupational Health, Daegu Catholic University) ;
  • Cho, Mansu (Department of Occupational Health, Daegu Catholic University) ;
  • Lee, Chaekwan (Department of Occupational and Environmental Medicine, Busan Paik Hospital & Institute of Environmental and Occupational Medicine, Inje University) ;
  • Lee, Jongdae (Department of Environmental Health Science, SoonChunHyang University) ;
  • Yang, Wonho (Department of Occupational Health, Daegu Catholic University)
  • 최영태 (대구가톨릭대학교 산업보건학과) ;
  • 허정 (대구가톨릭대학교 산업보건학과) ;
  • 박진현 (대구가톨릭대학교 산업보건학과) ;
  • 김은채 (대구가톨릭대학교 산업보건학과) ;
  • 류현수 (대구가톨릭대학교 산업보건학과) ;
  • 김동준 (대구가톨릭대학교 산업보건학과) ;
  • 조만수 (대구가톨릭대학교 산업보건학과) ;
  • 이채관 (인제대학교 부산백병원 직업환경의학과, 환경산업의학연구소) ;
  • 이종대 (순천향대학교 환경보건학과) ;
  • 양원호 (대구가톨릭대학교 산업보건학과)
  • Received : 2020.05.27
  • Accepted : 2020.06.18
  • Published : 2020.06.30

Abstract

Objectives: Much attention has been paid to indoor air quality. Ventilation within schools is important because of indoor air quality and its effect on health and learning performance. In this study, we evaluated the carbon dioxide (CO2) concentrations and ventilation rates in schools. Methods: This study measured the concentration of CO2 in elementary, middle, and high school classrooms over six months. The seasons during the study were summer, fall, and winter. Sensor-based monitoring was used and the basic characteristics of the classroom were investigated. The body surface area of the students was used to calculate the CO2 generation rate, and the air change per hour (ACH) was evaluated using mass balance modeling. Results: The average CO2 concentration measured in most schools exceeded 1000 ppm. The ventilation rates varied from season to season. Compared to the recommended ventilation rate of 4.9 ACH, the roughly 3 ACH calculated in this study indicates that most schools possessed insufficient ventilation. Conclusions: The concentration of CO2 in school classrooms could be an indicator of indoor air quality and can affect students' learning ability. In this study, CO2 concentrations exceeding the standard indicate a lack of ventilation along with problems with indoor air quality. Therefore, appropriate improvements are needed to overcome these problems.

Keywords

References

  1. Ministry of Environment. A study on indoor air pollution characterization and management. 2002.
  2. Yang W, Lee K, Chung M. Characterization of indoor air quality using multiple measurements of nitrogen dioxide. Indoor Air. 2004; 14: 105-111. https://doi.org/10.1046/j.1600-0668.2003.00216.x
  3. Landrigan P. Environmental hazards for children in USA. International Journal of Occupational Medicine and Environmental Health. 1998; 11(2): 189-194.
  4. Lee S, Chang M. Indoor and outdoor air quality investigation at schools in Hong Kong. Chemosphere. 2000; 41(1-2): 109-113. https://doi.org/10.1016/S0045-6535(99)00396-3
  5. Yang W. Time-activity pattern of students and indoor air quality of school. Korean Institute of Educational Facilities. 2014; 21(6): 17-22.
  6. Korea Ministry of Government Legislation. Enforcement decree of the school health act. 2018.
  7. Jeon E. Jang G. Kook C. Evaluation of indoor air quality in urban school. Korean Journal of Environmental Education. 1999; 12(2): 73-80.
  8. Camilla V. Kati J. Sander T. Kaiser A. Maria A. Raimo M, et al. Ventilation positive pressure intervention effect on indoor air quality in a school building with moisture problems. Environmental Research and Public Health. 2018; 15(2): 230. https://doi.org/10.3390/ijerph15020230
  9. Lim W. Literature review of the effect of the carbon dioxide concentration in classroom air on the students learning performance. Korean Journal of Environmental Education. 2015; 28(2): 134-145. https://doi.org/10.17965/kjee.2015.28.2.134
  10. Shendell D. Prill R. Fisk W. Apte M. Blake D. Faulkner D. Associations between classroom $CO_2$ concentrations and student attendance in Washington and Idaho. Indoor Air. 2004; 14: 333-341. https://doi.org/10.1111/j.1600-0668.2004.00251.x
  11. National Institute of Meteorological Sciences. Report of Global Atmosphere Watch. 2018.
  12. Lee J. Choi J. Kim H. Determination of body surface area and formulas to estimate body surface area using the alginate method. Journal of Physiological Anthropology. 2008; 27(2): 71-82. https://doi.org/10.2114/jpa2.27.71
  13. National Institute of Environmental Research. Study on the Improvement of exposure factors of korean adults on risk assessment. 2018.
  14. David A. Alexander B. Carbon Dioxide Levels and Ventilation Rates in Schools. International Journal of Ventilation. 2002; 1:1 45-52.
  15. Tichenor B, Sparks L., White J., Jackson M. Evaluating sources of indoor air pollution. Air & Waste Management Association. 1990; 40: 487-492. https://doi.org/10.1080/10473289.1990.10466703
  16. Kraenzmer M. Modeling and continuous monitoring of indoor air pollutants for identification of sources and sinks. Environmental International. 1999; 25(5): 541-551. https://doi.org/10.1016/S0160-4120(99)00029-X
  17. Yang W. Characterization of indoor air quality using multiple measurements of nitrogen dioxide. [Seoul]:Seoul National University; 2001.
  18. Korea Meteorological Adminstration. Annual climatological report. 2017.
  19. Park Y, Kim Y. A study on the indoor air quality of a high school dance practice room focusing on $PM_{10}$ and $CO_2$. The Korean Journal of Physical Education. 2019; 58(3): 317-326.
  20. Kim S. Investment of Air Change per Hour (ACH) in a Elementary School. Korean Society for Atmospheric Environment. 2010; 406.
  21. Park J, Ryu H, Heo J, Cho M, Yang W. Estimation of ventilation rates in korean homes using Timeactivity patterns and carbon dioxide concentration. Korean Society of Environmental Health. 2019;45(1): 1-8.
  22. Kim S, Kim J, Kim J. A study on the $CO_2$ concentration control in lecture room. Korea Institute of Architectural Sustainable Environment and Building Systems. 2012; 97-100.