DOI QR코드

DOI QR Code

Detection and localization of partial discharge in high-voltage direct current cables using a high-frequency current transformer

HFCT를 활용한 고전압직류송전 케이블 부분방전 위치추정

  • Hong, Seonmin (Department of Electrical Engineering, Kyungpook National University) ;
  • Son, Wooyoung (Department of Electrical Engineering, Kyungpook National University) ;
  • Cheon, Hyewon (Department of Electrical Engineering, Kyungpook National University) ;
  • Kang, Daekyoung (Department of Biomedical convergence Science and Technology, Kyungpook National Unversity) ;
  • Park, Jonghoo (Department of Electrical Engineering, Kyungpook National University)
  • 홍선민 (경북대학교전기공학과) ;
  • 손우영 (경북대학교전기공학과) ;
  • 천혜원 (경북대학교전기공학과) ;
  • 강대경 (경북대학교 의생명융합공학과) ;
  • 박종후 (경북대학교전기공학과)
  • Received : 2021.03.20
  • Accepted : 2021.03.26
  • Published : 2021.03.31

Abstract

Detection and localization of partial discharge are considered critical techniques for estimating the lifetimes of power cables. High-frequency current transformers (HFCTs) are commonly used for the detection of partial discharge in high-voltage alternating current (HVAC) power cables; however, their applicability is compromised by the limitations of the installation locations. HFCTs are typically installed in cable terminals or insulation joint boxes because HVACs induce strong time-varying magnetic fields around the cables, saturating the ferromagnetic materials in the HFCTs. Therefore, partial discharges near the installation locations can be detected. In this study, the feasibility of partial discharge detection using a HFCT was investigated for high-voltage direct current (HVDC) cables. We demonstrated that the HFCT could be installed at any location in the HVDC power cable to monitor partial discharge along the entire cable length. Furthermore, we showed that the HFCT could detect the location of partial discharge with high accuracy.

Keywords

References

  1. I.E.C. Standard, High Voltage Test Techniques: Partial discharge Measurement, IEC-60270, pp. 13-31, 2000.
  2. P. A. A. F. Wouters, P. C. T. Laan van der, E. Hetzel, and E. F. Steennis, "New on-line PD measurement technique for polymer insulated cables and accessories", Proc of 8th Int. Symp. on High Voltage Engineering. pp. 105-108, Yokohama, Japan, 1993.
  3. N. H. Ahmed and N. N. Srinivas, "On-line partial discharge detection in cables", IEEE-DEI Trans., Vol. 5, No. 2, pp. 181-188, 1998. https://doi.org/10.1109/94.671927
  4. B. T. Phung, Z. Liu, T. R. Blackburn, and R. E. James, "Online partial discharge measurement on high voltage power cables", Proc. of 11th Int. Symp. on High Voltage Engineering. pp. 328-332, London, UK, 1999.
  5. Z. Liu, B.T. Phung, T. R. Blackburn, and R. E. James, "The propagation of partial discharge pulses in a HV cable", Proc. of AUPEC/EECON eds, pp. 287-292 Darwin NT, Australia, 1999.
  6. E. F. Steennis, F. van den Boogaard, C. G. N. de Jong, M. J. M. van Riet, and G. P. T. Van der Wijk "Learning from high-voltage XLPE cable system testing and monitoring", CIGRE, pp. 21-203, 2000.
  7. W. Wei, Z. Sen, C. Bin, and L.En-heng, "The study of online PD detector in power cable", Proc. of 6th Int. Conf. on Properties and Applications of Dielectric Materials, pp. 177-180, Xian, China, 2000.
  8. A. Rodrigo, P. Llovera, V. Fuster, and A. Quijano, "Influence of High Frequency Current Transformers Bandwidth on Charge Evaluation in Partial Discharge Measurements", IEEE Trans. Dielectr. Electr. Insul., Vol. 18, No. 5, pp. 1798-1802, 2011. https://doi.org/10.1109/TDEI.2011.6032852
  9. A. Rodrigo, P. Llovera, V. Fuster, and A. Quijano, "Study of Partial Discharge Charge Evaluation and the Associated Uncertainty by Means of High Frequency Current Transformers", IEEE Trans. Dielectr. Electr. Insul., Vol. 19, No. 2, pp. 434-442, 2012. https://doi.org/10.1109/TDEI.2012.6180236
  10. D. Jovcic, High voltage direct current transmission: Converters, Systems and DC Grids, 2nd ed., John Wiley & Sons, NJ, pp. 1-12, 2019.