DOI QR코드

DOI QR Code

Evaluation of Structural Integrity and Cooling Performance of 4250 kVA Power Transformer with ONAN Mode

ONAN 모드 4250kVA 변압기의 구조 건전성과 냉각 성능의 평가

  • Yang, Chaofan (Dept. of Mechanical Engineering, Korea Maritime & Ocean University) ;
  • Kim, Seongik (Dept. of Mechanical Engineering, Korea Maritime & Ocean University) ;
  • Cho, Jong-Rae (Dept. of Mechanical Engineering, Korea Maritime & Ocean University)
  • ;
  • 김성익 (한국해양대학교 대학원 기계공학과) ;
  • 조종래 (한국해양대학교 대학원 기계공학과)
  • Received : 2021.04.29
  • Accepted : 2021.06.04
  • Published : 2021.07.31

Abstract

The main research content of this paper is to evaluate the structural integrity and the cooling performance of 4250 kVA power transformer with ONAN(Oil Natural and Air Natural) mode. The dynamic analysis is used to verify the structural safety of the transformer by seismic loading. The transformer structure is simplified and NX software is used to build a three-dimensional model, and ANSYS commercial software is used to calculate the stress and deformation by applying corresponding load. The analysis result was evaluated whether it satisfies the design requirements according to the IEEE Std 693 standard. In terms of thermal analysis to evaluate the cooling performance, the thermal physical model is used to calculate the heat exchange between the radiator and the tank in the steady state, and the result is input into the Fluent software to calculate the internal temperature field of the transformer tank, which reduces the calculation cost of thermal fluid. Comparing the simulated hot spot temperature and top oil temperature of the transformer with the calculation results of the IEC60076 classic model, it is found that the error is only 1.9%.

Keywords

Acknowledgement

This work was supported by IEN Hanchang Co., LTD using the financial resource granted by the Ministry of SMEs and Startups (S2869647).

References

  1. Goodno, B. J., Gould, N. C., Caldwell, P., Gould, P. L., Effects of the January 2010 Haitian earthquake on selected electrical equipment, Earthquake Spectra, Vol. 27, pp. 251-276, 2011. https://doi.org/10.1193/1.3636415
  2. IEEE, IEEE recommended practice for seismic design of substations, IEEE Power Engineer Society, IEEE Standard 693-2018, 2018.
  3. Xie Q., Zhu, R.Y., "Damage to electric power grid infrastructure caused by natural disasters in China earthquake, wind, and ice", IEEE Power and Energy Magazine, Vol. 9, No. 2, pp.28-36, 2011. https://doi.org/10.1109/MPE.2010.939947
  4. Amoiralis, E. I., Tsili, M. A., & Kladas, A. G., "Transformer design and optimization: A literature survey", IEEE Trans. Power Deliv., Vol. 24, pp. 1999-2024, 2009. https://doi.org/10.1109/TPWRD.2009.2028763
  5. Susa, D. and Lehtonen, M., "Dynamic thermal modeling of power trans-formers: Further development-Part I", IEEE transactions on power delivery, Vol. 21, No. 4, pp.1961-1970, 2006. https://doi.org/10.1109/TPWRD.2005.864069
  6. International Electrotechnical Commission (IEC), Power Transformers-Part 7: Loading Guide for Oil-Immersed Power Transformers, IEC 60076-7, 2005.
  7. Susa, D. and Nordman H., IEC 60076-7 loading guide thermal model constants estimation, Int. Trans. Elect. Energy Syst., Vol. 23, pp. 946-960, 2013. https://doi.org/10.1002/etep.1631
  8. IEEE, IEEE Guide for Loading Mineral-Oil-Immersed Transformers and Step Voltage Regulators, IEEE Standard C57.91, 2011.
  9. Wang, L., Zhou, L, Yuan, S., Wang, J., Tang, H., Wang, D. and Guo, L., "Improved Dynamic Thermal Model with Pre-Physical Modeling for Transformers in ONAN Cooling Mode", IEEE Transaction on power delivery, Vol. 34, No.4, pp. 1442-1450, 2019. https://doi.org/10.1109/tpwrd.2019.2903939
  10. Kim, M.-G., Cho, S. M. and Kim, J.-K., "Prediction and evaluation of the cooling performance of radiators used in oil-filled owner transformer applications with non-direct and direct-oil-forced flow", Experimental Thermal and Fluid Science, Vol. 44 pp. 392-397, 2013. https://doi.org/10.1016/j.expthermflusci.2012.07.011
  11. Gong, R., Ruan, J., Chen, J., Quan, Y., Wang, J. and Duan, C., Analysis and experiment of hot-spot temperature rise of 110 kV three-phase three-limb transformer, Energies, Vol. 10, No. 8, pp. 1079-1092, 2017. https://doi.org/10.3390/en10081079
  12. Wang, L., Zhou, L., Tang, H., Wang, D. and Cui, Y., Numerical and experimental validation of variation of power transformers thermal time constants with load factor, Applied Thermal Engineering, Vol. 126 pp. 939-948, 2017. https://doi.org/10.1016/j.applthermaleng.2017.07.167
  13. Rodriguez, G. R., Garelli, L., Storti, M., Granata, D., Amadei, M., and Rossetti, M., Numerical and experimental thermo-fluid dynamic analysis of a power transformer working in ONAN mode, Appl. Therm. Eng., Vol.112, pp.1271-1280, 2017. https://doi.org/10.1016/j.applthermaleng.2016.08.171
  14. Menter, F. R., "Zonal Two Equation k-ω Turbulence Models for Aerodynamic Flows", In 23rd fluid dynamics, plasmadynamics, and lasers conference, pp. 2906, 1993.
  15. Menter, F. R., Two-equation eddy-viscosity turbulence models for engineering applications, AIAA Journal, Vol. 32, No 8. pp. 1598-1605, 1994. https://doi.org/10.2514/3.12149