DOI QR코드

DOI QR Code

Measurement and Analysis of Indoor Environment in Emergency Switching Type Temporary Negative Pressure Isolation Ward that Use Portable Negative Pressure Units

이동형 음압기를 적용한 긴급 전환형 임시음압격리병실의 실내 환경 측정 분석

  • 이원석 (건축학과, 서울대학교) ;
  • 이세진 (건축학과, 서울대학교) ;
  • 김희강 (건설환경종합연구소, 서울대학교) ;
  • 여명석 (건축학과, 서울대학교)
  • Received : 2022.11.16
  • Accepted : 2022.11.24
  • Published : 2022.12.15

Abstract

Purpose: Because of the recent COVID-19 pandemic, there have been many cases of using portable negative pressure unit to convert general wards into temporary negative pressure isolation wards. The purpose of this study is to analyze the indoor environment of the switching type wards. Methods: Field measurements and experiments were conducted in a medical facility. Air volume, wind speed and pressure difference were measured in non-occupant state. Dispersion tests were performed with gas and particle matter. Results: The pressure difference between the wards and the corridor was higher than -2.5 Pa in normal situation. However, in the gas and particle dispersion tests, it was found that there were concerns about the spread through leakages in low-airtight walls or ceilings. In addition, it was confirmed that the pressure imbalance in ducts through the non-sealed diffusers could cause back flow during portable unit operation. Furthermore, when there was a pressure difference between adjacent wards planned to be at same pressure level, the possibility of the spread through the leakages was found. Implications: When using portable units for making switching type wards, it is necessary to create airtight space and seal the non-operation diffusers. In case of operating the air handling unit, T.A.B must be performed to adjust the duct balancing.

Keywords

Acknowledgement

본 연구는 보건복지부의 재원으로 감염병의료안전강화 기술개발사업 지원에 의하여 이루어진 것임(과제고유번호 : HG22C0017)

References

  1. B. C. Singer ; W. W. Delp, 2018, "Response of consumer and research grade indoor air qualitymonitors to residential sources of fine particles", Indoor Air 28.4, p.624-639 https://doi.org/10.1111/ina.12463
  2. David L. Johnson, 2005, "Oklahoma State Department of Health Design and Implementation Guidelines for Airborne Infectious Isolation under Epidemic Emergency Response Conditions", Oklahoma State Department of Health, Oklahoma
  3. Kenneth R. Mead; Amy Feng, M.S.; Duane Hammond; Stan Shulman, 2012, "Expedient Methods for Surge Airborne Isolation within Healthcare Settings during Response to a Natural or Manmade Epidemic", NIOSH
  4. Miller, S. L.; Clements, N.; Elliott, S. A.; Subhash, S. S.; Eagan, A.; Radonovich, L. J., 2017, "Implementing a negative-pressure isolation ward for a surge in airborne infectious patients.", American journal of infection control, 45(6), p.652-659 https://doi.org/10.1016/j.ajic.2017.01.029
  5. Minnesota Department of Health, 2010, "Airborne Infectious Disease Management: Methods for temporary Negative Pressure Isolation", Minnesota
  6. Minnesota Department of Health, 2020, "Guidelines for Temporary Negative Pressure Isolation Rooms", USA
  7. Mousavi, E. S.; Pollitt, K. J. G.; Sherman, J.; Martinello, R. A., 2020, "Performance analysis of portable HEPA filters and temporary plastic anterooms on the spread of surrogate coronavirus", Building and environment, 183, p.107186
  8. Park, J. Y.; Sung, M., 2015, "A study on the contaminant dispersion from isolation ward under abnormal operation of facilities", Energy procedia, 78, p.1239-1244 https://doi.org/10.1016/j.egypro.2015.11.264
  9. Robert D. Booth; LT.Samantha J. Ponce; Gregory J. Corso; CAPT. Shelley K. Perkins, 2021, "Current/Updated Health Care Facilities Ventilation Controls and Guidelines for Management of Patients with Suspected or Confirmed SARS-CoV-2 (COVID-19)", ASHE, USA
  10. Shruti Hegde; Kyeong T. Min; James Moore; Philip Lundrigan; Neal Patwari; Scott Collingwood; Alfred Balch; Kerry E. Kelly, 2020, "Indoor household particulate matter measurements using a network of low-cost sensors.", Aerosol and Air Quality Research 20.2, p.381-394 https://doi.org/10.4209/aaqr.2019.01.0046
  11. Weili Liu; Junfeng Zhang; Jamal H. Hashim; Juliana Jalaludin; Zailina Hashim; Bernard D. Goldstein, 2003, "Mosquito coil emissions and health implications", Environmental Health Perspectives, September, p.1459