DOI QR코드

DOI QR Code

Application of the Proper Air Supply Amount Based on the Influent Water Quality for the Development of Efficient Blower Control Logic in Sewage Treatment Plants

하수처리장의 효율적인 Blower Control Logic 개발을 위한 유입수질 기반 공기공급량 적용 연구

  • 여우석 (신한대학교 스마트토목환경도시공학전공) ;
  • 김종규 (신한대학교 도시기반부동산학과)
  • Received : 2021.11.24
  • Accepted : 2022.04.26
  • Published : 2022.08.01

Abstract

The standards pertaining to the quality of discharged water in sewage treatment plants are strengthening, and accordingly, facilities in sewage treatment plants are being upgraded. In addition, the discharge water quality of sewage treatment plants must be maintained at a high level, and efficient sewage treatment plant operations have thus emerged as a very important issue. For the efficient operation of sewage treatment plants, this study applied a basic blowing amount calculation method based on sewage facilities to evaluate the required oxygen amount and blowing amount according to inflow water quality by logicizing various influencing factors. As a result of calculating the amount of air blown by applying actual April water quality data from sewage treatment plant A to the blower demand calculation developed through this study, it was found that the average amount of air blown was reduced by about 12%. When the blower demand calculation developed here is applied to an actual sewage treatment plant, the amount of air blown can be controlled based on the inflow water quality. This can facilitate the realization of an autonomous control of sewage treatment plants, in contrast to the existing sewage treatment operation method that relies on operational experience of operator. In addition, it is expected that efficient sewage treatment plants can be operated by reducing blowing amounts and power costs, which will contribute to both energy and carbon savings.

하수처리장의 방류수 수질기준이 강화되고 있으며, 이에 따라 하수처리장 시설도 고도화되고 있다. 또한 하수처리장의 방류수질은 높은 수준으로 유지되어야 하며, 이에 따라 효율적인 하수처리장 운영이 매우 중요한 이슈로 대두되고 있다. 본 연구에서는 하수처리장의 Blower Control Loigc 개발을 위해, 하수도 시설기준의 기본 송풍량 산정 방식을 기반으로 유입수질에 따른 필요 산소량 및 송풍량을 산정하였다. 본 연구를 통해 A 하수처리장의 실제 4월 수질 데이터를 적용하여 송풍량을 산정한 결과, 평균적으로 약 12 %의 송풍량이 절감이 될 수 있다는 것을 확인하였다. 본 연구에서 산정한 결과에 따라 Blower Control Logic을 개발하여 실제 하수처리장에 적용하게 된다면, 유입수질을 기반으로 송풍량 제어가 가능함에 따라 운전자의 경험에 의존하고 있는 기존의 하수처리 운영방식에서 벗어나 하수처리장 자율제어가 가능할 것으로 판단된다. 또한, 송풍량 및 전력비 절감이 이루어진 효율적인 하수처리장 운영을 기대 할 수 있으며, 이를 통해 불필요한 에너지 및 탄소 절감에 기여할 수 있을 것이라고 판단된다.

Keywords

Acknowledgement

본 결과물은 환경부의 재원으로 환경산업산업기술의 상하수도 혁신 기술개발사업의 지원을 받아 연구되었습니다(과제번호: 2020002700010).

References

  1. Chang, S. Y., Shin, P. S., Jeong, Y. K. and Choi, Y. J. (2020). "Development of air supply control technology in sidestream MLE process by measuring conductivity." Journal of Korean Society of Environmental Engineers, Vol. 42, No. 3, pp. 97-109 (in Korean). https://doi.org/10.4491/ksee.2020.42.3.97
  2. Kim, B. S., Choi, M. Y., Kwon, H., Kim, J. M., Cha, W. O. and Chun, W. M. (2013). "The evaluation of effect indicators on estimation of aeration volume for wastewater treatment plants." Journal of Korean Society of Environmental Engineers, Vol. 35, No. 1, pp. 38-44 (in Korean). https://doi.org/10.4491/KSEE.2013.35.1.038
  3. Kim, J. T. (2018). "A Study on Strengthening option of T-N effluent water quality standards of sewage treatment plants." Journal of Korean Society on Water Environment, Vol. 34, No. 2, pp. 216-225 (in Korean). https://doi.org/10.15681/KSWE.2018.34.2.216
  4. Kim, M. H., Ji, S. H. and Jang, J. H. (2014). "A study on energy saving effect from automatic control of air flow rate and estimation of optimal do concentration in oxic reactor of wastewater treatment plant." Journal of Energy Engineering, Vol. 23, No. 2, pp. 49-56 (in Korean). https://doi.org/10.5855/ENERGY.2014.23.2.049
  5. Korea Environment Corporation (2006). Telemonitoring system construction process (in Korean).
  6. Korea Water and Wastewater Works Association (KWWA) (2011). Sewage facility standards (in Korean).
  7. K-water (2009). Development of self-diagnosis sewage treatment plant operation management system (commercialized version) and field application of actual sewage treatment plant (in Korean).
  8. Lee, S. M., Kim, H. L. and Ki, K. S. (2019). "Study on the low energy sewage management based on pre-sensing technology and automatic blower control." Journal of Environmental Impact Assessment, Vol. 28, No. 6, pp. 592-603 (in Korean). https://doi.org/10.14249/EIA.2019.28.6.592
  9. Nam, E. S. (2020). "Optimization of activated sludge process in wastewater treatment system using explainable neural network." The Transactions of the Korean Institute of Electrical Engineers, Vol. 69, No. 12, pp. 1950-1956 (in Korean). https://doi.org/10.5370/kiee.2020.69.12.1950
  10. Park, H. D. and Noguera, D. R. (2004). "Evaluating the effect of dissolved oxygen on ammonia-oxidzing bacterial communities in activated sludge." Water Research, Vol. 38, No. 14-15, pp. 3275-3286. https://doi.org/10.1016/j.watres.2004.04.047
  11. Sun, Y., Xin, L., Wu, G. and Guan, Y. (2019). "Nitrogen removal, nitrous oxide emission and microbial community in sequencing batch and continuous-flow intermittent aeration process." Environmental Engineering Research, Vol. 24, No. 1, pp. 107-116. https://doi.org/10.4491/eer.2018.141
  12. Vase, J. L. and Praet, E. (2002). "On the use of fluorescence measurements to characterize wastewater." Water Science & Technology, Vol. 45, No. 4-5, pp. 109-116. https://doi.org/10.2166/wst.2002.0564