Abstract

Appropriate explosion proof electrical equipment should be installed in hazardous areas. In areas where hydrogen is handled, explosion proof electrical equipment adjacent to the hydrogen handing facility must be reviewed for selection of gas group IIC (or IIB+H2) equipment. When selecting explosion proof electrical equipment for the flammable substance handling facility in areas where hydrogen and flammable substance are handled, the method to avoid gas group IIC (or IIB+H2) equipment has been suggested by using the operating pressure of the hydrogen handling facility. When the operating pressure of the outdoor hydrogen handling facility is 1.065 MPa or less, it has been confirmed that there is no need to install gas group IIC (or IIB+H2) equipment for the flammable substance handling facility adjacent to the hydrogen handling facility. And the method of selecting explosion proof electrical equipment for the flammable substance handling facility has been suggested as a flowchart, so it will be able to be utilized when selecting appropriate explosion proof electrical equipment.

Keywords

References

  1. KS C IEC 60079-10-1, "Explosive atmospheres - Part 10-1: Classification of areas-explosive gas atmospheres", Korean Agency for Technology and Standards, Korea, 2017. Retrieved from https://standard.go.kr/KSCI/standardIntro/getStandardSearchList.do;jsessionid=EjqbmQums39ZhZdXxXGW9dHq.node01?menuId=919&topMenuId=502&upperMenuId=503.
  2. KS C IEC 60079-0, "Explosive atmospheres - part 0: equipment- general requirements", Korean Agency for Technology and Standards, Korea, 2019. Retrieved from https://standard.go.kr/KSCI/standardIntro/getStandardSearchList.do;jsessionid=EjqbmQums39ZhZdXxXGW9dHq.node01?menuId=919&topMenuId=502&upperMenuId=503.
  3. KGS GC101, "Classification code for explosive hazardous area on gas facility", Korea Gas Safety Corporation, Korea, 2018. Retrieved from https://cyber.kgs.or.kr/kgscode.codeSearch.searchByMain.ex.do.
  4. J. H. Kim, M. K. Lee, S. H. Kil, Y. G. Kim, and Y. K. Ko, "Area classification of hazardous gas facility according to KGS GC101 code", Journal of the Korean Institute of Gas, Vol. 23, No. 4, 2019, pp. 46-64, doi: https://doi.org/10.7842/kigas.2019.23.4.46.
  5. D. Y. Pyo and O. T. Lim, "A study on explosive hazardous areas in hydrogen handling facility", Trans Korean Hydrogen New Energy Soc, Vol. 30, No. 1, 2019, pp. 29-34, doi: https://doi.org/10.7316/KHNES.2019.30.1.29.
  6. P. R. Cho, H. J. Lee, and J. B. Baek, "Study on the negligible extent(NE) and release characteristic of KS C IEC 60079-10-1(2015) standard", Journal of the Korean Society of Safety, Vol. 35, No. 2, 2020, pp. 111-117, doi: https://doi.org/10.14346/JKOSOS.2020.35.2.111.
  7. D. Y. Kim, Y. W. Chon, I. M. Lee, and Y. W. Hwang, "A study on the improvement of classification of explosion hazardous area using hypothetic volume through release characteristic", J. Korea Saf. Manag. Sci., Vol. 19, No. 2, 2017, pp. 31-39, doi: https://doi.org/10.12812/ksms.2017.19.2.31.
  8. D. C. Jun, "A study on safety policies for a transition to a hydrogen economy", Trans Korean Hydrogen New Energy Soc, Vol. 25, No. 2, 2014, pp. 161-172, doi: https://doi.org/10.7316/KHNES.2014.25.2.161.
  9. N. S. Kim, J. G. Lim, and I. S. Woo, "A study on the examination of explosion hazardous area applying ventilation and dilution", Journal of the Korean Institute of Gas, Vol. 22, No. 4, 2018, pp. 27-31, doi: https://doi.org/10.7842/kigas.2018.22.4.27.