DOI QR코드

DOI QR Code

Vestibule Smoke Control Considering the Stack Effect and the Opening of the Outside Door

굴뚝효과와 외부출입문 개방을 고려한 부속실 제연

  • Yongkwang Kim (Korea Safety Tecnology Co. Ltd) ;
  • Zudal Son (Korea Hazardous Safety Association) ;
  • Seoyoung Kim (Candidate Fire and Safety Engineering, Woosuk University) ;
  • Hasung Kong (Department of Fire and Disaster Prevention, Woosuk University)
  • 김용광 ((주)한국안전기술) ;
  • 손주달 ((사)한국위험물안전협회) ;
  • 김서영 (우석대학교 소방.안전공학과) ;
  • 공하성 (우석대학교 소방방재학과)
  • Received : 2024.01.26
  • Accepted : 2024.03.18
  • Published : 2024.03.30

Abstract

The purpose of this study is to improve the stack effect of the staircase and the failure to take into account the opening of the outside door of the staircase, which are the disadvantages of the existing smoke control only vestibule. As a result of the study, the new vestibule and the staircase simultaneous smoke control are equipped with an exhaust flap damper with an effective opening area of about 0.25 m2 in the upper part of the staircase, and a ventilator-type air supply fan of about 5 m3/s in the lower part, and take measures to prevent overpressure in the staircase. If you use the new simultaneous smoke control method of the vestibule and staircase, you can achieve the following effects. First, it is possible to open the external entrance door. Second, it can reduce the stack effect. Third, the staircase door closes automatically without fail. And a new method of preventing overpressure was proposed for the vestibule.

Keywords

References

  1. J. S. An, S. W. Kim, S. R. Kim, S. W. Hong(2011), "A Study on Air-supply Flow Rate Setup for Pressurization System of Stair Vestibule of High-Rise Building under Consideration of Stack Effect." J. The Society of Air-coonditioning and Refrigerating Engineers of Korea, 2011(7):741-743.
  2. J. He, X. Huang, X. Ning, T. Zhou, J. Wang, R. Yuen(2020), "Stairwell smoke transport in a full-scale high-rise building: Influence of opening location." Fire Safety Journal, 117:1-13.
  3. Y. K. Kim(2020), "Proposal of Air Supply Smoke Control System about Stair-case Considering Stack Effect & Opening of the Outside Door." Fire Sci. Eng, 34(5):130-137.
  4. D. M. Lee(2017), Smelting Engineering, Donghwa technology, pp.303-316.
  5. D. M. Lee(2017), Smelting Engineering, Donghwa technology, pp.306-307.
  6. Ministry of Land, Infrastructure and Transport, "Performance standards for fire doors" (KS F 2846)
  7. National Fire Agency(2022), National Safety Performance Code of Staircase and Annex smoke control facilities for Special Evacuation Staircase 501A (NFPC 501A)
  8. S. H. Ryu, S. K. Lee, D. H. Hong, M. O. Yoon, K. R. Choi, J. H. Park(2010), "Expermential Study on Features of Air Egress Velocity in Vestibule Pressurization System." J. of Korean Institute of Fire Sci. & Eng, 24(5):79-86.
  9. P. S. Shin, H. S. Kim(2015), "The Experimental Study on the Leakage of Automatic Pressure Differential.Overpressure Control Dampers." Fire Sci. Eng., 29(6):71-75.
  10. W. Lei, Z. Zheng, C. Rong, C. Tai, S. Zhao, A. Li(2022), "Study on fire smoke control in evacuation passageways on the top floor of an atrium involving breathing zones combines with underfloor makeup air supplementation." Safety Science, 153:1-15.