• Title/Summary/Keyword: Arc-fault

Search Result 228, Processing Time 0.038 seconds

Control Algorithm Development for an Arc Current Interruption (아크 전류 차단을 위한 제어알고리즘 개발)

  • 반기종;김낙교
    • The Transactions of the Korean Institute of Electrical Engineers D
    • /
    • v.53 no.3
    • /
    • pp.166-172
    • /
    • 2004
  • Arc Fault Current is an electric discharge which is occurred in two opposite electrode. In this Paper, arc current control algorithm is designed for the interruption of arc fault current which is occurred in the low voltage network. This arc Is one of the main causes of electric fire. Arc fault in electrical network has the characteristics of low current, high impedance and high frequency. Conventional control algorithm does not have the arc current interrupt function. Hence, Control algorithm of arc current is designed for the interruption of arc fault current which has the modified arc characteristics.

Arc Fault Circuit Interrupter Design for Electrical Fire Protection (전기화재 방지를 위한 아크고장전류 차단기 설계)

  • Ban, Gi-Jong;Kim, Lark-Kyo
    • The Transactions of the Korean Institute of Electrical Engineers D
    • /
    • v.55 no.5
    • /
    • pp.220-225
    • /
    • 2006
  • Arc Fault Current is an electric discharge which is occurred in two opposite electrode. In this paper, AFCI(arc fault circuit interrupter) is designed for the interruption of arc fault current which is occurred in the local electric network. This arc is one of the main causes of electric fire. Arc fault in electrical network has the characteristics of low current, high impedance and high frequency. Conventional arc fault circuit interrupter does not have the arc current interrupt function. Hence, Arc current controller is designed for the interruption of arc fault current which has the modified arc characteristics.

Arc Fault Circuit Interruption Design

  • Kang, C.S.
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2006.05a
    • /
    • pp.384-386
    • /
    • 2006
  • In this paper, arc current controller is designed for the interruption of arc fault current which is occurred in the low voltage network. Arc in electrical network have the characteristics of low current, high impedance and high frequency. Conventional controller does not have the arc current interrupt function. Hence, arc current controller is designed for the interruption of arc fault current.

  • PDF

Design of an Arc Current Controller for Arc Interruption

  • Kang, Chang-Soo
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.21 no.9
    • /
    • pp.109-113
    • /
    • 2007
  • In this paper, an arc current controller was designed for the interruption of arc fault currents occurred in a low voltage network. Arc in an electrical network represents the characteristics of low current, high impedance, and high frequency. Conventional controllers do not have arc current interrupt functions. Thus, an arc current controller was designed for the interruption of arc fault currents.

Analysis of Serial Arc with DC Current (DC 전류에 의한 직렬 아크 특성 분석)

  • Ban, Gi-Jong;Nam, Moon-Hyun;Kim, Lark-Kyo
    • Proceedings of the KIEE Conference
    • /
    • 2007.07a
    • /
    • pp.1700-1701
    • /
    • 2007
  • DC Arc Fault Current is an electric discharge which is occurred in two opposite electrode. In this paper, DC arc detection device is designed for the display of DC arc fault current which is occurred in the local electric network with DC Power. This DC arc is one of the main causes of electric fire. Arc fault in electrical network has the characteristics of low current, high impedance and low frequency. DC Arc current detection device is designed for the display of arc fault current which has the modified arc characteristics.

  • PDF

A Series Arc Fault Detection Strategy for Single-Phase Boost PFC Rectifiers

  • Cho, Younghoon;Lim, Jongung;Seo, Hyunuk;Bang, Sun-Bae;Choe, Gyu-Ha
    • Journal of Power Electronics
    • /
    • v.15 no.6
    • /
    • pp.1664-1672
    • /
    • 2015
  • This paper proposes a series arc fault detection algorithm which incorporates peak voltage and harmonic current detectors for single-phase boost power factor correction (PFC) rectifiers. The series arc fault model is also proposed to analyze the phenomenon of the arc fault and detection algorithm. For arc detection, the virtual dq transformation is utilized to detect the peak input voltage. In addition, multiple combinations of low- and high-pass filters are applied to extract the specific harmonic components which show the characteristics of the series arc fault conditions. The proposed model and the arc detection method are experimentally verified through a boost PFC rectifier prototype operating under the grid-tied condition with an artificial arc generator manufactured under the guidelines for the Underwriters Laboratories (UL) 1699 standard.

The Arc Fault Determination Method for the Electric Fire Prevention (전기화재 방지를 위한 아크고장 판단기법에 대한 연구)

  • Ko, Yun-Seok
    • The Journal of the Korea institute of electronic communication sciences
    • /
    • v.3 no.4
    • /
    • pp.260-265
    • /
    • 2008
  • The arc-fault occurring in the customer system becomes the direct cause of electric fire. However, it is very difficult to identify the arc-fault using the existing fault detection mechanism because the magnitude of the fault current is very small. Accordingly, this paper analyzes the causes of arc fault and designs the basic detection mechanism of arc fault. And then, it proposes an signal processing-based arc-fault determination methodology which can enhance the of accuracy of the arc-fault determination by applying DFT/DWT to the voltage and current waveform. Finally, this paper showed the application methodology of the proposed signal processing based fault determination method by applying and analyzing DFT/DWT to an high voltage in-rush current waveform.

  • PDF

Analysis of Detection Method for Series Arc Fault Signal by using DWT (이산 웨이블렛 변환을 이용한 직렬 아크고장 신호 검출 방법 분석)

  • Bang, Sun-Bae;Kim, Chong-Min;Park, Chong-Yeun;Chung, Young-Sik
    • The Transactions of the Korean Institute of Electrical Engineers P
    • /
    • v.58 no.3
    • /
    • pp.362-368
    • /
    • 2009
  • Electrical fires have been occurred continuously in spite of installing ELB. Therefore the concern with the electrical arc-fault that cause the fire has growing. This paper measured series arc fault currents by the method of arc generator test in UL standard 1699. The used analysis methods in this paper are three different ways using DWT(discrete wavelet transform) those are frequently used for the arc fault current signal analysis. The arc fault detection probability is 100 % by method using noise-energy/shoulder-duration ratio of approximation coefficient. As these results, the variation of noise-energy and shoulder-duration ratio of approximation coefficient are founded important factors for the analysis of arc fault.

Analysis of Series Arc-Fault Signals Using Wavelet Transform From Non-linear Loads (웨이블렛 변환을 이용한 비선형 부하 전원선에서의 직렬 아크고장 신호 분석)

  • Bang, Sun-Bae;Park, Chong-Yeun;Jang, Mog-Soon;Choi, Won-HO
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.57 no.8
    • /
    • pp.1470-1477
    • /
    • 2008
  • In this paper, a new detection method of series arc-fault signals occurring at the wiring of home appliances is proposed. The discrete wavelet transform was used for the numerical analysis of the variation rate in peak, RMS, noise energy, shoulder of the arc-fault current wave. As a results, the arc distinction threshold value of these variation rates was about 0.1 in most cases. The arc-fault current of the loads with the active PFC circuit showed a high rate of variation in noise energy and shoulder, but arc-fault current of the loads without the active PFC circuit showed a high rate of variation in peak and RMS. The arc fault current in resistive loads showed a high rate of variation in shoulder.

AFCI algorithm design for electrical fire protection (전기화재 방지를 위한 AFCI 알고리즘 설계)

  • Ban, Gi-Jong;Choi, Sung-Dai;Nam, Moon-Hyun;Kim, Lark-Kyo
    • Proceedings of the KIEE Conference
    • /
    • 2006.07d
    • /
    • pp.1769-1770
    • /
    • 2006
  • Arc Fault is an electric discharge which is occurred in two opposite electrode. In this paper, AFCI(arc fault circuit interrupter) is designed for the interruption of arc fault current which is occurred in the local electric network. This arc is one of the main causes of electric fire. Arc fault in electrical network has the characteristics of low current, high impedance and high frequency. Conventional interrupter does not have the arc current interrupt function. Hence, Arc fault circuit interrupter controller is designed for the interruption of arc fault current which has the modified arc characteristics.

  • PDF