• Title/Summary/Keyword: Cup-burner Halon

Search Result 5, Processing Time 0.017 seconds

A Study on the Flame Extinguishing Characteristics of Inerting Gaseous Agents (불활성가스계 소화약제의 불꽃소화 특성에 관한 연구)

  • Kim, Sung-Min;Shin, Chang-Sub;Park, Jae-Man
    • Proceedings of the Korea Institute of Fire Science and Engineering Conference
    • /
    • 2008.04a
    • /
    • pp.148-150
    • /
    • 2008
  • Halon gas agent has been widely used as the extinguishing agent for B class and C class fires because of its excellent extinguishing power. But Halon was found to contribute to the ozone layer destruction, eventually Halon designated as one of ozone-layer-destroying materials in the Montreal Protocol in 1987, In this study, in the context of such researches, we measured the characteristics of flame concentrations of inert gaseous agents by Cup-burner method.

  • PDF

Flame Extinguishing Concentrations of Mixed Gaseous Agents (가스계 혼합소화약제의 불꽃소화농도)

  • 김재덕;임종성;이윤우;이윤용
    • Fire Science and Engineering
    • /
    • v.15 no.1
    • /
    • pp.34-40
    • /
    • 2001
  • Fire extinguishing efficiency of mixed gaseous agents were investigated by the cup-burner test and predicting by the model of flame extinguishing concentration. The binary mixed agents that tested were carbon dioxide/HFC-23, carbon dioxide/HCFC-22, carbon dioxide/HFC-227ea, carbon dioxide/HFC-125, carbon dioxide/FIC-13I1, Hexafluoropropylene/HFC-23 and ternary mixed agents were carbon dioxide/HFC-23/HFC-l34a, carbon dioxide/HFC-23/HFC-227ea, carbon dioxide/HFC-23/HFC-125. A model which contains the flame extinguishing concentration and composition of pure components predicted the flame extinguishing concentration of mixture well. This model was superior when each component of the mixture exhibit physical fire extinguishing performance.

  • PDF

A Study on the Measurement of Flame Extinguishing Concentration of Halon Alternatives by New Test Equipment (할론대체물질의 새로운 불꽃소화농도 측정장치에 관한 연구)

  • 김재덕;임종성;이윤우;이윤용
    • Fire Science and Engineering
    • /
    • v.8 no.1
    • /
    • pp.3-8
    • /
    • 1994
  • A new test system was established to measure the flame extinguishing concentration of Halon alternatives. The main characteristic of this system is to use the solid paraffin with a wick instead of liquid fuel, such as n-Heptane. Our results showed that the extinguishing concentration of compounds was lower than that of other existing data, but the trend was consistent with others. The flame extinguishing concentration of all tested compounds were not almost effected by gas flow velocity. The system produces good reliable data with a minimum error for measuring the flame extinguishing concentration. Therefore our new system can be utilized as a standard equipment to evaluate Halon alternatives.

  • PDF

Flame Extinguishing Characteristics of Clean Gaseous Agents and Effects of Additives (가스계 청정소화약제의 소화특성과 첨가제에 따른 영향)

  • Shin, Chang-Sub;Kim, Sung-Min
    • Journal of the Korean Society of Safety
    • /
    • v.23 no.6
    • /
    • pp.95-99
    • /
    • 2008
  • Halon was known as a cause of the ozone layer destruction. In 1987, it was designated as one of the ozone-layer-destroying materials in the Montreal Protocol. Therefore substitutes of Halon agent has been developed including inert gas extinguish system, which is one of the most widely used fire extinguishing system. This study intended to increase the efficiency of inert gas extinguishing agent by using inert gas additives. As IG-541 shows high extinguishing power, the experiment was performed to measure the effects of gaseous additives to it. Cup-burner fire extinguishing apparatus was used with n-Heptane fuel. Among many of pure inert gaseous agents, Helium showed the most excellent extinguishing power. When Helium was added to IG-541, fire extinguishing power was increased and the concentration of oxygen in chimney also risen. By adding Helium to IG-541, the effectiveness of inert gas fire extinguishing system is able to be increased.

Fire Extinguishing Ability of Binary Gaseous Extinguishing Agents Evaluated by Cup Burner and Numerical Studies (이성분계 가스계소화약제 소화성능의 컵버너실험 및 이론적 고찰)

  • Kwon, Kyung-Ok;Won, Dong-Bin;Choi, Keun-Joo;Kim, Jong-Won;Shin, Dong-Il
    • Journal of the Korean Institute of Gas
    • /
    • v.11 no.3
    • /
    • pp.7-12
    • /
    • 2007
  • The search for a new fire-extinguishing agent with all the desirable properties of halon 1301 has not been successful. To study binary gaseous extinguishing agents instead, one has to determine the extinguishing concentrations for several compositions of a given chemical in an inert gas. This process is expensive and time consuming. The fire suppression efficiencies of gas mixtures of HFC 125 and HFC 227ea with nitrogen as total flooding agents were studied by cup burner method. It was shown that addition of small amounts of those extinguishants to nitrogen can enhance the suppression effectiveness of the inert gas. As expected, the degree of synergism was highest at low concentrations of the chemical. For each binary system, extinguishing concentrations of the pure compounds and one binary data were used to predict the extinguishing concentrations for the entire range of binary composition. The predicted values were very close to experimental data.

  • PDF