• Title/Summary/Keyword: Degree of stratification

Search Result 46, Processing Time 0.022 seconds

A Study on Thermal Stratification Characteristics and Useful Rate of Hot Water in Thermal Storage Tank during Hot Water Extraction Process (온수 추출과정 동안 축열조 내의 열성층 특성 및 온수 이용률에 관한 연구)

  • 장영근;박정원
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.14 no.6
    • /
    • pp.503-511
    • /
    • 2002
  • Heat flow characteristics during hot water extraction process was studied experimentally. Data were taken at various outlet port type for the fixed inlet port type, inlet-outlet temperature differences and mass flow rates. In this study, the temperature distribution in a storage tank and an outlet temperature were measured to predict a degree of stratification in the storage tank, and a useful rate of hot water was analysed with respect to the variables dominating a extraction process. Experimental results show that the degree of stratification and useful rate of hot water are all high in a low flow rate in case of using modified distributor I (MDI) as the outlet port type.

Effect on Stratification due to Diffuser Shape in a Thermal Storage Tank (온도 성층축열조 가시화 및 실증분석에 관한 고찰)

  • Lee Young-Soo;Lee Sang-Nam;Kim Jong-Ryul
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.17 no.11
    • /
    • pp.990-997
    • /
    • 2005
  • The stratified effect was investigated with three different types of diffuser shape in a thermal storage tank with variation of diffuser diameter, velocity, Froude number etc. Its effect was estimated by the degree of stratification. No matter of diffuser diameter and shape, the degree of stratification was the best as the Froude number gets closer to 1. In the case of a curved diffuser, when its diameter is a quarter of tank diameter and ejection velocity in a diffuser is approximately 0.2 m/s, the Froude number was almost 1. In the case of a flatted diffuser, when ejection velocity was 0.05 m/s, the Froude number was 1.5. Both cases which Froude number were nearer 1, showed the good degree of stratification.

Effect of an aspect ratio on thermal stratification in a solar seasonal thermal storage tank (태양열 계간 축열조 내부 열성층화에 대한 탱크 종횡비 영향 연구)

  • Kim, Seong Keun;Jung, Sung Yong
    • Journal of the Korean Society of Visualization
    • /
    • v.18 no.2
    • /
    • pp.28-34
    • /
    • 2020
  • In this study, we numerically investigated the thermal stratification in solar seasonal thermal storage tanks. The vertical in/out flows were unsuitable for the thermal stratification in a large scale. The effect of an aspect ratio (AR) on the thermal stratification was investigated. When AR was less than 2, water adheres and flows along the upper wall due to buoyance and the surface effect. Thereafter, hot water flows down and a large scale vortex occurs in entire tank. For high AR, jet flows ejected from the inlet pipe impinges to the opposite wall and splits. The divided flows create two vortex flows in the upper and lower regions. These different flows strongly influence temperature and thermal stratification. The thermal stratification was evaluated in terms of the thermocline thickness and degree of stratification. Compared to ARs, the maximum degree of stratification was obtained with AR of 5 having the minimum thermocline thickness.

Effects of the aspect ratio and inlet velocity on the thermal stratification in a diffuser type seasonal thermal storage tank (디퓨저 타입 계간 축열조 내부 열성층화에 대한 입구 유속 및 탱크 종횡비 영향 연구)

  • Kim, Seong Keun;Jung, Sung Yong
    • Journal of the Korean Society of Visualization
    • /
    • v.19 no.3
    • /
    • pp.99-105
    • /
    • 2021
  • In this study, the thermal stratification in solar seasonal thermal storage tanks was numerically simulated. The effects of the aspect ratio (AR) and inlet velocity on the thermal stratification in the diffuser type heat storage tank were investigated. The temperature distributions inside the tank were similar with velocity fields. Jet flows from opposite diffusers encountered each other at the tank center region. Thereafter, the downward flows occurred, and this flows strongly affected the thermal stratification. When AR was smaller than 2, these downward flows influenced a further distance and enhanced mixing inside the tank. Thermal stratification was evaluated by thermocline thickness and degree of stratification, and AR of 3 had the highest degree of stratification. The inlet velocity effect was expressed with the ratio (Re/Ri) of Reynolds and Richardson numbers. The second-order approximation was found for the relationship between the thermocline thickness and log Re/Ri.

Thermal Stratification and Heat Loss in Underground Thermal Storage Caverns with Different Aspect Ratios and Storage Volumes (지하 열저장 공동의 종횡비와 저장용량에 따른 열성층화 및 열손실)

  • Park, Dohyun;Ryu, Dong-Woo;Choi, Byung-Hee;Sunwoo, Choon;Han, Kong-Chang
    • Tunnel and Underground Space
    • /
    • v.23 no.4
    • /
    • pp.308-318
    • /
    • 2013
  • Thermal stratification in heat stores is essential to improve the efficiency of energy storage systems and deliver more useful energy on demand. It is generally well known that the degree of thermal stratification in heat stores varies depending on the aspect ratio (the height-to-width ratio) and size of the stores. The present study aims to investigate the effect of the aspect ratio and storage volume of rock caverns for storing hot water on thermal stratification in the caverns and heat loss to the surroundings. Heat transfer simulations using a computational fluid dynamics code, FLUENT were performed at different aspect ratios and storage volumes of rock caverns. The variation of thermal stratification with respect to time was examined using an index to quantify the degree of stratification, and the heat loss to the surroundings was evaluated. The results of the numerical simulations demonstrated that the thermal stratification in rock caverns was improved by increasing the aspect ratio, but this effect was not remarkable beyond an aspect ratio of 3-4. When the storage volume of rock caverns was large, a higher thermal stratification was maintained for a relatively longer time compared to caverns with a small storage volume, but the difference in thermal stratification between the two cases tended to decrease as the aspect ratio became larger. In addition, the numerical results showed that the heat loss to the surrounding rock tended to increase with an increase in aspect ratio because the surface area of rock caverns increased as the aspect ratio became larger. The total heat loss from multiple small caverns with a reduced storage volume per cavern was larger compared to a single cavern with the same total storage volume as that of the multiple caverns.

Numerical Study on the Thermal Stratification Behavior in Underground Rock Cavern for Thermal Energy Storage (TES) (열에너지 저장을 위한 지하 암반공동 내 열성층화 거동에 대한 수치해석적 연구)

  • Park, Do-Hyun;Kim, Hyung-Mok;Ryu, Dong-Woo;Choi, Byung-Hee;SunWoo, Choon;Han, Kong-Chang
    • Tunnel and Underground Space
    • /
    • v.22 no.3
    • /
    • pp.188-195
    • /
    • 2012
  • Using a computational fluid dynamics (CFD) code, FLUENT, the present study investigated the thermal stratification behavior of Lyckebo storage in Sweden, which is the very first large-scale rock cavern for underground thermal energy storage. Heat transfer analysis was carried out for numerical cases with different temperatures of the surrounding rock mass in order to examine the effect of rock mass heating due to periodic storage and production of thermal energy on thermal stratification and heat loss. The change of thermal stratification with respect to time was quantitatively examined based on an index of the degree of stratification. The results of numerical simulation showed that in the early operational stage where the surrounding rock mass was less heated, the stratification of stored thermal energy was rapidly degraded over time, but the degradation and heat loss tended to reduce as the surrounding rock mass was heated during a long period of operation.

A Study on Flow and Mixing Caracteristics according to Hot Water Extraction (온수 추출에 따른 유동 및 혼합 특성에 관한 연구)

  • 장영근;박이동;김철주;황영규
    • Proceedings of the Korea Society for Energy Engineering kosee Conference
    • /
    • 1995.05a
    • /
    • pp.53-59
    • /
    • 1995
  • In a hot water extraction process, the flow pattern of upper region in a storage tank is a major reason of mixing between hot water and cold water. In this study, the temperature distribution in a storage tank was measured to predict the flow pattern of upper region, and the degree of stratification was analysed to the variables dominating a extraction process. And also, it was found that the degree of stratification improved expecially in a low flow rate in case of using modified distributor I(DMI) as a outlet port type.

  • PDF

Ratio and Product Type Exponential Estimators of Population Mean in Double Sampling for Stratification

  • Tailor, Rajesh;Chouhan, Sunil;Kim, Jong-Min
    • Communications for Statistical Applications and Methods
    • /
    • v.21 no.1
    • /
    • pp.1-9
    • /
    • 2014
  • This paper discusses the problem of estimation of finite population mean in double sampling for stratification. In fact, ratio and product type exponential estimators of population mean are proposed in double sampling for stratification. The biases and mean squared errors of proposed estimators are obtained upto the first degree of approximation. The proposed estimators have been compared with usual unbiased estimator, ratio and product estimators in double sampling for stratification. To judge the performance of the proposed estimators an empirical study has been carried out.

A study on Characteristics of Heat Flow of Low Temperature Latent Thermal Storage System (저온 잠열 축열조내의 열유동 특성에 관한 연구)

  • Lee, W.S.;Park, J.W.
    • Solar Energy
    • /
    • v.19 no.4
    • /
    • pp.33-43
    • /
    • 1999
  • The study on ice thermal storage system is to improve total system performance and increase the economical efficiency in actual all-conditioning facilities. To obtain the high charging and discharging efficiencies in ice thermal storage system, the improvement of thermal stratification is essential, therefore the process flow must be piston flow in the cylindrical type. With the relation of the aspect ratio(H/D) in the storage tank, the stratification is formed better as inlet flow rate is smaller. If the inlet and the outlet port are settled at the upside and downside of the storage tank, higher storage rate could be obtainable. In case that the flow directions inside the thermal storage tank are the upward flow in charging and the downward in discharging, thermal stratification is improved because the thermocline thickness is maitained thin and the degree of stratification increases respectively. In the charging process, in case of inlet flow rate the thermal stratification has a tendency to be improved with the lower flow rate and smaller temperature gradient in case of inlet temperature, the large temperature difference between inflowing water and storage water are influenced from the thermal conduction. The effect of the reference temperature difference is seen differently in comparison with the former study for chilled and hot water. In the discharging process, the thermal stratification is improved by the effect of the thermal stratification of the charging process.

  • PDF

A Study on Thermally Stratied Hot Water Storage Tank in A Solar Heating System (태양열 난방 시스템에 적용되는 축열조의 성층화에 관한 연구)

  • Hong, Hi-Ki;Kim, Hyo-Kyung
    • The Magazine of the Society of Air-Conditioning and Refrigerating Engineers of Korea
    • /
    • v.15 no.1
    • /
    • pp.87-96
    • /
    • 1986
  • An experiment on the devices that enchance the stratification of storage tanks in a solar heat ins system has been carried out. The benefits of thermal stratification in sensible heat storage are to increase the system performance such as the collector efficiency or the fraction of the total load supplied by solar energy. Using the diffuser and the distributor as the stratification enchancement device, the expeliments were perfomed in the different condition of diameter and material of the distributor. As a result of experiments, there exists the diameter of distributor in which the stratification is made maximum under certain design and operation condition. Also it was identified that the kind of distributor material influenced the degree of stratification. Comparing the experimental result to the computational results calculated under the same conditions, the node number N(stratification index) was determined. The results of computer simulation that was performed about the actual solar heating system in Seoul for 24 hours show the relative advantage of stratified over well-mixed storage and the significant improvements in system performance.

  • PDF