• Title/Summary/Keyword: Distribution arresters

Search Result 58, Processing Time 0.038 seconds

Longterm Aging Characteristics of Distribution Polymer Housed Surge Arresters by Multistress Accelerated Aging (복합 가속열화를 통한 배전용 고분자 피뢰기의 장기 열화특성 예측)

  • Kim, Ju-Yong;Kwon, Tae-Ho;Park, Chul-Bae;Kim, Joon-Eel
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.20 no.8
    • /
    • pp.691-696
    • /
    • 2007
  • In this study accelerated aging test equipment was developed to simulate domestic weather condition for accelerated aging test of polymer housed distribution surge arresters. Polymer arresters were aged for 3,000 hours by this test equipment and chemical and electrical characteristics analysis of surge arresters were conducted after aging test. In addition, performance assessment of outdoor installed arresters for 3 years was conducted to compare aging effect between accelerated aging test and natural aging. Through this experiment it is verified that the capability of the proposed aging test for simulating natural aging and the housing material and disconnector of domestic polymer arresters can be deteriorated by the long time field operation.

A Study on Lightning Surges in Underground Distribution Systems

  • Jung Chae-Kyun;Kim Sang-Kuk;Lee Jong-Beom
    • KIEE International Transactions on Power Engineering
    • /
    • v.5A no.2
    • /
    • pp.171-176
    • /
    • 2005
  • The effects of surge arresters for the protection of transmission systems against direct lightning strokes have already been reviewed by many researchers. However, their studies have not encompassed underground cable systems. Therefore, in this paper we investigate the 22.9kV combined distribution systems that have arresters and ground wires. In addition, we analyze the overvoltages on underground distribution cable sections when direct lightning strokes contact the overhead ground wire using EMTP. Finally, we discuss the effect of lightning strokes according to the change of cable length and installation of arresters. This study provides insulation coordination methods for reasonable system design in 22.9kV underground distribution cable systems.

A Study on the Dielectric Properties of Lightening Arrester used for Distribution Line (배전용 피뢰기의 유전특성에 관한 연구)

  • Kim, Chan-Young;Kim, Ju-Yong;Song, Il-Keun;Lee, Byoung-Sun;Han, Yong-Heui
    • Proceedings of the KIEE Conference
    • /
    • 1999.07d
    • /
    • pp.1642-1644
    • /
    • 1999
  • This paper provides the results of dielectric properties for aged or controlled lightening arresters. The aged lightening arresters were used for five years in distribution line. The leakage current of lightening arresters and elements was measured to confirm whether the lightening arrester was deteriorated or not. The microstructure was also investigated to determine the size of grain and grain boundary. The dielectric properties of aged lightening arresters were compared to those of controlled lightening arresters. The dielectric constant and the tan${\delta}$ of aged lightening arrester were larger than those of controlled one, resulting from accelerated aging due to the thin grain boundary.

  • PDF

Harmonics Analysis of Leakage Current due to Artificial Contamination of Distribution Arresters (배전용 피뢰기의 인공오손에 의한 누설전류의 고조파 분석)

  • Park, Jae-Jun
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.61 no.9
    • /
    • pp.1306-1313
    • /
    • 2012
  • This paper reports the contamination performance of two distribution arresters (new and used ones) tested under three different contaminant conditions - clean fog, ESDD (equivalent salt deposit density) level (A, B, C, and D), and kaolin contamination conditions, and their leakage current, total leakage current, and component of the resistive leakage current were measured in order to diagnose arrester deterioration. The 3rd harmonics was larger than 5th and 7th ones for the arrester under the clean fog, and as the ESDD contamination level was applied, 5th one became relatively larger than 3rd one. Therefore, these results indicated that the resistive leakage current could be used for the diagnosis of the arresters.

Temperature Characteristics with Structure of 18kV Lightning Arresters for Distribution System (18kV 배전용 피뢰기의 구조에 따른 온도특성)

  • Cho, Han-Goo;Yoon, Han-Soo;Lee, Un-Yong;Kim, Suk-Sou;Choi, In-Hyuk
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2004.07b
    • /
    • pp.1125-1128
    • /
    • 2004
  • This paper presents the temperature characteristics with structure of 18 kV lightning arresters for distribution. Three types of polymer arresters were fabricated and ceramic type arrester was also ready to investigate. Below $100^{\circ}C$, three types of polymer arresters exhibited almost the same leakage current value, but above $100^{\circ}C$, polymer arrester that arrester module was injected into polymer housing with grease exhibited the highest leakage current and the arrester with the lowest leakage current was the arrester that silicon rubber was directly injected to arrester module. The rising of leakage current of polymer arrester with grease was because of existing grease between FRP winding and silicon housing, and reducing the insulation characteristics of the grease. All polymer arresters exhibited the same temperature characteristics but ceramic typr arrester was slower than polymer arrester in heat emission despite lowest leakage current. It was thought that the air layer between ZnO varistor blocks and ceramic housing prevented the heat emission. However, in spite of the difference of the structure, the variation of the surface temperature of all arresters exhibited the same result.

  • PDF

The Causes and Countermeasures for failures of Distribution Polymer Surge Arresters (배전용 폴리머 피뢰기의 고장원인 및 대책)

  • Kim, Ju-Yong;Lee, Jae-Bong;Kim, Dong-Myung;Jang, Sang-Ok;Hwang, Gwang-Soo
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2003.07b
    • /
    • pp.1159-1162
    • /
    • 2003
  • Recently we suffered lot of failures of polymer surge arresters made by same manufacture after one year field operation. In order to set up countermeasures we investigated the causes of failures. We extracted faulted arresters and sound ones which were installed in same pole with faulted ones for the electrical test and dissection. 44 arresters were removed from 8 branch offices. Almost all of faulted arresters hadtracking damage on the interface between inner module and housing and the surface of inner module was very rough and irregular. It was possible to occur moisture ingress into the interface between inner module and housing due to the void of the interface and non tight sealing caps. Lots of sound arresters were failed during the moisture ingress test. This result must relate with tracking damage of faulted arresters. Therefore we can say that arresters had poor interface and sealing system. But we could not found aging and defects of ZnO elements because the electrical performance except moisture ingress test of arresters showed good.

  • PDF

Analysis of Shielding Effect with Installation Methods of Arresters in Double Circuits Distribution Systems (2회선 배전계통에서 피뢰기 설치방법에 따른 차폐 효과 분석)

  • 정채균;김상국;이종범;정영호
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.53 no.2
    • /
    • pp.104-110
    • /
    • 2004
  • This paper describes the lightning overvoltage occurred differently according to installation methods of arresters and overhead grounding wire in case of double circuits distribution systems. First, the analysis models are established considering the severe case between upper and lower distribution line, when the direct lightning surge strikes to the overhead grounding wire. The lightning overvoltage is variously analyzed with the change of grounding interval and resistance, arrester installation interval as well as the magnitude of surge using EMTP. After simulation results are compared with the BIL which is now used at field, the authors propose the methods for suitable shielding in domestic distribution systems.

Accelerated aging test method and characteristics analysis of polymer housed surge arresters (폴리머 피뢰기 가속열화 방법과 열화특성 분석)

  • Kim, Ju-Yong;Park, Chul-Bae;Kwon, Tae-Ho;Jung, Yeon-Ha
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2007.05a
    • /
    • pp.210-213
    • /
    • 2007
  • In this study accelerated aging test cycle and equipment was developed for aging test of polymer housed surge arresters under domestic weather condition In order to investigate aging characteristics of polymer surge arresters electrical and chemical analysis of the arresters which are used for accelerated aging test and outdoor exposure test were conducted. Through the analysis the capability of the proposed method was verified and characteristics data were presented for maintenance of domestic arresters. Based on these results long term reliability assessment method was proposed for polymer housed distribution surge arresters.

  • PDF

Temperature and Leakage Current Characteristics with Structure of Polymeric Surge Arresters (폴리머 피뢰기의 구조에 따른 온도와 누설전류 특성)

  • Cho, Han-Goo;Lee, Un-Yong;Kim, Ha-Na
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2006.06a
    • /
    • pp.513-514
    • /
    • 2006
  • This paper presents the temperature characteristics with the structure of 18 kV surge arresters for distribution system. Three types of polymer arrester were fabricated and a ceramic arrester was also prepared to investigate. Below $100^{\circ}C$, three types of polymeric arresters exhibited almost the same leakage current value, but above $100^{\circ}C$, the polymeric arresters whose module was injected into polymeric housing with the grease exhibited the highest leakage current. In contrary, the arresters being manufactured by directly injecting silicone rubber onto arrester module exhibited the lowest leakage current. The rapid rising of leakage current of the polymeric arresters with the grease at $120^{\circ}C$ was because of the deterioration of the insulation characteristics of the grease between the FRP module and the silicone housing. All polymeric arresters exhibited the same surface temperature characteristics but the ceramic arresters was slower than the polymer arrester in heat emission despite the lowest leakage current. It was thought that the air layer between ZnO varistor blocks and the ceramic housing prevented the heat emission.

  • PDF

Insulation Design of Distribution Systems in Case of the Stroke of Direct Lightning Surge (직격뢰 침입시 배전계통 절연설계)

  • 정채균;김상국;이종범;서재호
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.53 no.4
    • /
    • pp.238-247
    • /
    • 2004
  • This paper describes the insulation coordination scheme of line in distribution system when the direct lightning surge strikes. The BIL that is applied to distribution system is not properly considered the performance and operation of arresters. Because of that, the high BIL is being used at partial system. This paper variously analyses the lightning overvoltage of line and equipment with earth of overhead grounding wire and installation types of arrester. From these result. authors examine the rationality of BIL.