• 제목/요약/키워드: Ground Rod

검색결과 161건 처리시간 0.023초

봉상접지전극의 접지임피던스의 주파수의존성의 분석 (Analysis of the Frequency Dependent Characteristics of Ground Impedance of a Ground Rod)

  • 이복희;엄주홍
    • 대한전기학회논문지:전기물성ㆍ응용부문C
    • /
    • 제53권8호
    • /
    • pp.426-432
    • /
    • 2004
  • This paper presents a systematic approach of measurement, modeling and analysis of grounding system impedance in the field of lightning protection system and intelligent power equipments. The measurement and analysis system of ground impedance is based on a computer aided technique. The magnitude and phase of ground impedance were determined by the novel measurement and analysis using the revised fall-of-potential method. The ground impedances of the ground rod of 50 m long are considerably dependent on the frequency. The ground impedance is mainly resistive in the frequency range of 3-20 kHz. At higher frequencies, the reactive components of the ground impedances are no longer negligible and the inductance of the ground rod was found to be the core factor deciding the ground impedance. Although the steady-state ground resistance of the ground rod of 50 m was less than that of the ground rod of 10 m, the ground impedances of the ground rod of 50 m over the frequency range of more than 60 kHz were much greater than those of the ground rod of 10 m. Furthermore, the equivalent circuit model based on the measured data was proposed. and the calculated results were in approximately agreement with the measured data.

토중방전을 수반하는 접지봉의 임펄스응답에 대한 기초적 연구 (A Fundamental Study on the Impulse Responses of Ground Rod Attendant upon Soil Discharges)

  • 유양우;조성철;이복희
    • 조명전기설비학회논문지
    • /
    • 제28권4호
    • /
    • pp.62-69
    • /
    • 2014
  • This paper deals with the fundamental characteristics of transient and conventional ground impedances associated with soil discharges when the lightning impulse voltage was applied to a small-sized ground rod. The potential rise responses of the test ground rod to impulse currents were observed. The current-voltage (I-V)curves, transient and conventional ground impedance curves were examined.. To analyze the transient behaviors of ground rod attendant upon soil discharges, the impulse responses of ground rod were compared with those of non-inductive resistor. As a consequence, the potential rise and impedance of ground rod were reduced and the currents dispersed into the earth were increased due to soil discharges near the ground rod. Soil discharges are classified into two regimes; ionization and breakdown phenomena. The potential rise and impulse impedance of ground rod are significantly decreased by breakdown processes in soil.

봉형 접지전극의 시설깊이에 따른 대지전위분포 (Ground Potential Distribution Associated with the Buried Depth of Ground Rod)

  • 이복희;엄주홍;안창환
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2000년도 하계학술대회 논문집 C
    • /
    • pp.2068-2070
    • /
    • 2000
  • Ground potential rise is a vital part of personal safety, this paper presents the ground potential rise distribution induced by a ground rod. The experiments were conducted with the AC square wave currents according to the buried depth of ground rod. The ground potential is significantly varied in the vicinity of ground rod and the ground potential distribution is flat and few with increasing the buried depth of ground rod.

  • PDF

대지구조에 따른 접지봉 주번의 대지표면전위분포 (Ground Surface Potential Distribution near Ground Rod Associated with Soil Structures)

  • 이복희;정현욱;백영환
    • 조명전기설비학회논문지
    • /
    • 제21권1호
    • /
    • pp.142-147
    • /
    • 2007
  • 본 논문은 대지구조와 접지봉의 매설깊이에 따른 대지표면의 전위상승에 대해서 기술하였다. 대지표면의 전위상승에 따른 인체의 감전사고의 저감에 관한 기초적 자료를 제안하기 위해서 접지봉 부근에서의 대지표면전위를 계산하고 측정하였다. 접지봉 부근의 대지표면전위상승은 대지구조에 크게 의존하며, 매설깊이가 깊어질수록 낮아졌다. 대지표면전위상승은 접지봉의 직상부에서 최대이었으며, 측정결과는 접지해석프로그램으로 계산한 결과와 잘 일치하였다.

수중에 잠긴 접지전극 주변에서의 이온화에 의한 전위저감 및 에너지방출 (Potential Reduction and Energy Dispersion Due to Ionization Around the Submerged Ground Rod)

  • 최종혁;안상덕;양순만;이복희
    • 조명전기설비학회논문지
    • /
    • 제23권1호
    • /
    • pp.92-99
    • /
    • 2009
  • 심매설 접지봉의 경우 장마철에 빗물이나 지하수와 접촉하는 경우가 발생한다. 수중에 잠겨있는 접지극에 서지 전압이 인가되면 접지극 주변에서 이온화 현상이 발생하게 된다. 지중이나 수중에서의 이온화 현상은 접지 시스템의 에너지적인 특성에 의해 영향을 받는다. 이 논문의 목적은 축소된 전해 수조를 이용하여 임펄스 전압에 의한 접지시스템의 과도특성을 파악하는데 있다. 매틀랩 프로그램을 활용하여 이온화에 의한 전위저감과 방출된 에너지를 측정하여 정량적인 분석을 수행하였다. 접지극 끝단의 최대 전압은 물의 저항률과 Marx형 전압발생장치의 충전전압에 따라 다양하게 나타났다. 접지극 끝단의 전위는 절연파괴전압에 이르기 전 인가전압에서 대략 절반까지 감소하였다. 또한 절연파괴가 발생하기 전 인가된 에너지의 절반 이상의 에너지가 이온화에 의해 접지극을 통하여 방출되었다.

접지전류의 주파수에 따른 수직 접지전극 주변에서 전위간섭 영향 분석 (An Analysis of Potential Interference Effects in the Vicinity of Ground Rod Depending on Frequency of Ground Currents)

  • 이복희;조용승;최종혁;양순만
    • 조명전기설비학회논문지
    • /
    • 제25권12호
    • /
    • pp.88-93
    • /
    • 2011
  • When the ground current is injected into the adjacent ground electrode, the potential interference is caused between ground electrodes, the ground potential interferences have been largely studied with power frequency fault currents. Many attempts to find the frequency-dependent grounding impedance report that the high frequency grounding impedance is very different with the ground resistance. This paper presents experimental data on the frequency-dependent potential interference effects in the vicinity of ground rod. The ground potential rises around the test ground rod of 4 or 6[m] were measured and discussed. As a result, the ground potential rises and potential interference factor are decreased with decreasing the grounding impedance. It was found that the lowering of grounding impedance is critical to reduce the ground potential interference effects.

대지구조에 따른 대지표면전위의 분석 (Analyses of Earth Surface Potentials Depending on Soil Structures)

  • 이복희;백영환;정현욱
    • 전기학회논문지
    • /
    • 제56권10호
    • /
    • pp.1796-1801
    • /
    • 2007
  • This paper presents electric potential rise on the surface of the earth due to ground currents. It is the aim of this paper to propose fundamental data relevant to the earth surface potentials depending on the soil structures. The earth potential rise, touch and step voltages in the immediate vicinity of the ground rod of a distribution pole were measured and analyzed. The results described in this paper are based on laboratory measurements which were intended to simulate conditions existing in actual installations. As a result, the earth surface potential rise, touch and step voltages strongly depend on the soil structure. The highest earth surface potential occurred in the vicinity of the top of ground rod. When the ground rod was installed in the distance range of $1{\sim}1.5\;m$ from distribution pole, the highest touch voltages appeared near the place of 1 m on the straight line connecting the distribution pole to ground rod.

침상 접지봉의 임펄스접지임피던스에 미치는 지중방전의 영향 (Effects of Soil Discharges on the Impulsive Ground Impedance of Ground Rod with Needles)

  • 유양우;조성철;이복희
    • 조명전기설비학회논문지
    • /
    • 제28권5호
    • /
    • pp.98-105
    • /
    • 2014
  • Soil discharges near the ground rod play an important role to reduce the ground potential rise and the ground impedance and to help the fault current to spread into the earth. This paper presents the effects of soil discharges on the transient and conventional ground impedances when the lightning impulse voltage was applied to a ground rod with radial needles. The current-voltage (I-V)curves and transient ground impedance curves were calculated based on the measured current and potential traces. Soil discharge behaviors related to I-V curves and transient ground impedance curves were analyzed as a function of the magnitude of lightning impulse voltages. As a result, the soil discharges occurred near the ground electrode contribute to the reduction of conventional ground impedance and limits the ground potential rise effectively under lightning impulse voltages.

봉상 접지전극에시 전류유입위치에 따른 임펄스 접지임피던스의 특성 (Behaviors of Impulse Ground Impedances Associated with the Current Injection Point in a Ground Rod)

  • 이복희;정동철;이수봉
    • 조명전기설비학회논문지
    • /
    • 제19권1호
    • /
    • pp.94-100
    • /
    • 2005
  • 본 논문은 전류유입위치에 따른 봉상접지전극의 과도 및 실효임펄스임피던스의 특성에 관한 것으로 뇌격전류를 인가하여 실규모 접지봉에 대한 시간영역에서의 성능을 평가하였다. 임펄스전류가 가해진 봉상접지전극의 과도 접지임피던스는 접지저항보다 높게 나타났으며, 접지전극의 길이가 길어짐에 따라 접지저항과 실효임펄스접지임피던스는 감소되었다. 또한 실효임펄스접지임피던스는 짧은 시간범위에서는 급격하게 증가하였다. 접지저항의 저감은 접지시스템의 임펄스임피던스 특성의 개선에 결정적인 역할을 한다. 임펄스전류를 접지봉의 하단에 인가하였을 때 접지봉 전위의 파두부에 고주파의 진동 파형이 포함되고 실효임펄스임피던스는 다른 경우보다 높게 나타났다.

배전용 전주와 접지전극의 이격거리에 따른 접촉전압 (Touch Voltage According to the Distance between Distribution Concrete Pole and Ground Rod)

  • 이복희;정현욱;이태형;백영환;이동문;정동철;이규선;안창환
    • 한국조명전기설비학회:학술대회논문집
    • /
    • 한국조명전기설비학회 2005년도 학술대회 논문집
    • /
    • pp.391-394
    • /
    • 2005
  • This paper describes the touch voltages and potential distributions according to the distance between distribution concrete pole and ground rod when the current is injected to a ground rod through overhead ground wire. Touch voltage is measured in four directions. The touch voltage and ground potential distribution per 1 A are analyzed. The touch voltage was the highest at the around surface just above the ground rod.

  • PDF