• 제목/요약/키워드: Ground-loop heat exchanger

검색결과 74건 처리시간 0.026초

저심도 대구경 지중열교환기의 설치조건에 따른 성능 연구 (Performance Evaluation of Large Borehole Ground-Loop Heat Exchanger)

  • 유규상;박일문;최재호;신현준
    • 대한설비공학회:학술대회논문집
    • /
    • 대한설비공학회 2009년도 하계학술발표대회 논문집
    • /
    • pp.58-63
    • /
    • 2009
  • A ground-loop heat exchanger for the ground source heat pump system is the core equipment determining the thermal performance and initial cost of the system. The size and performance of the heat exchanger is highly dependent on the ground thermal properties - the ground effective thermal conductivity, the borehole thermal resistance and the undisturbed ground temperature. Nowadays, precast concrete piles using steel reinforced precast concrete piles - energy piles - are used to reduce the installing cost of the ground-loop heat exchanger. We were carried out some tests to investigate the effects of some parameters such as borehole length, grouting materials and U-tube configuration of the energy piles. 4 concrete piles, each measuring $250mm{\sim}400mm$ in diameter and approx. 10m in length, and rigged with single spiral and 3 U-tube loop of $16mm{\times}2.3mm$ PB piping. The thermal response tests were conducted using a testing device for 4-different ground-loop heat exchangers. During the heating period, the energy piles absorb the heat of 0.89kW to 1.37kW.

  • PDF

개방형 지중열교환기 용량 설계 방법에 관한 연구 (Study on the Capacity Design Tool Development for Open-loop Ground Heat Exchanger)

  • 류형규;최승혁;윤희원;김유승
    • 한국지열·수열에너지학회논문집
    • /
    • 제13권2호
    • /
    • pp.9-15
    • /
    • 2017
  • When applying geothermal systems in cities such as seoul where high density development prevails, the selection of geothermal system capable of obtaining a large capacity in the limited grounds is necessary. In this study, an easy-to-use design tool is developed in the form of spreadsheet by applying the calculation theory of existing closed-loop vertical ground heat exchanger that can be used in the early design stage of the open-loop ground heat exchanger. By only using the maximum cooling and heating load, it is possible to calculate optimal design open-loop ground heat exchanger. Further research is needed, we are plan to improve the program considering the heat loss of groundwater flowing in the inner casing, G-Function for Open-Loop, and verification by applying actual projects.

지중열교환기 설치 조건이 지중 유효 열전도도에 미치는 영향 (Effect of Some Parameters on Ground Effective Thermal Conductivity)

  • 최재호;임효재;공형진;손병후
    • 대한설비공학회:학술대회논문집
    • /
    • 대한설비공학회 2008년도 동계학술발표대회 논문집
    • /
    • pp.33-38
    • /
    • 2008
  • A ground-loop heat exchanger in a ground source heat pump system is an important unit that determines the thermal performance of a system and its initial cost. The Size and performance of this heat exchanger is highly dependent on ground thermal properties. A proper design requires certain site-specific parameters, most importantly the ground effective thermal conductivity, the borehole thermal resistance and the undisturbed ground temperature. This study was performed to investigate the effect of some parameters such as borehole lengths, various grouting materials and U-tube configurations on ground effective thermal conductivity. In this study, thermal response tests were conducted using a testing device with 9-different ground-loop heat exchangers. From the experimental results, the length of ground-loop heat exchanger affects to the effective thermal conductivity. Among the various grouting materials, the bentonite-based grout with silica sand shows the largest thermal conductivity value.

  • PDF

설계조건 변화에 따른 지중열교환기 길이 변화 연구 (Study on Capacity Alteration of Geothermal Heat Exchanger by Changing Design Condition)

  • 박종일;박경순
    • 한국지열·수열에너지학회논문집
    • /
    • 제9권4호
    • /
    • pp.9-14
    • /
    • 2013
  • A ground loop heat exchanger for the ground source heat pump system is the important equipment determining the thermal performance and initial cost of the system. The length and performance of the underground heat exchanger is dependent on ground thermal conductivity, operation hours, ground loop diameter, grout, ground loop arrangement, pipe placement and design temperature. In this study we find out heat exchanger length with various design factor.

파이프 순환수의 수치해석 모사를 통한 수직 밀폐형 지중열교환기 단면의 열전달 효율 평가 (Numerical Evaluation of Heat Transfer un Ground Heat Exchanger Considering Flow through U-loop)

  • 길후정;이강자;이철호;최항석
    • 한국신재생에너지학회:학술대회논문집
    • /
    • 한국신재생에너지학회 2009년도 춘계학술대회 논문집
    • /
    • pp.583-587
    • /
    • 2009
  • This paper presents a series of numerical simulations on the thermal performance and sectional efficiency of a closed-loop vertical ground heat exchanger (U-loop) equipped in a geothermal heat pump system (GHP). A 3-D finite volume analysis (Fluent) was used to simulate the operating process of the closed-loop vertical ground heat exchanger by considering the effect of the thickness of HDPE pipe and grout thermal properties, distance between the inflow and outflow pipes, and the effectiveness of the latticed HDPE pipe system. It was observed that the thermal interference between the two strands of U-loop is of importance in determining the efficiency of the ground heat exchanger, and thus it is highly recommendable to modify the cross section configuration of the conventional U-loop system by including a thermally insulating latice between the two strands.

  • PDF

지중열교환기 설치 조건이 지중 유효 열전도도에 미치는 영향에 관한 실험적 연구 (An Experimental Study on the Effect of Ground Heat Exchanger to the Overall Thermal Conductivity)

  • 공형진;임효재;최재호;손병후
    • 대한설비공학회:학술대회논문집
    • /
    • 대한설비공학회 2009년도 하계학술발표대회 논문집
    • /
    • pp.45-51
    • /
    • 2009
  • A ground-loop heat exchanger in a ground source heat pump system is an important unit that determines the thermal performance of a system and its initial cost. The size and performance of this heat exchanger is highly dependent on ground thermal properties. A proper design requires certain site-specific parameters, most importantly the ground effective thermal conductivity, the borehole thermal resistance and the undisturbed ground temperature. This study was performed to investigate the effect of some parameters such as borehole lengths, various grouting materials and U-tube configurations on ground effective thermal conductivity. In this study, thermal response tests were conducted using a testing device with 9-different ground-loop heat exchangers. From the experimental results, the length of ground-loop heat exchanger affects to the effective thermal conductivity. Among the various grouting materials, the bentonite-based grout with silica sand shows the largest thermal conductivity value.

  • PDF

설계변수가 수직밀폐형 지중열교환기 설계길이에 미치는 영향 (Effect of the Design Parameters of Geothermal Heat Exchanger Design Length)

  • 민경천;최재호
    • 한국지열·수열에너지학회논문집
    • /
    • 제7권2호
    • /
    • pp.10-15
    • /
    • 2011
  • A ground loop heat exchanger for the ground source heat pump system is the core equipment determining the thermal performance and initial cost of the system The length and performance of the heat exchanger is dependent on the ground thermal conductivity, the operation hours, the ground loop diameter, the grout, the ground loop arrangement, the pipe placement and the design temperature. The result of this simulation shows that higher thermal conductivity of grouting materials leads to the decrease length of geothermal heat exchanger from 100.0 to 84.4%.

반밀폐형 지중열교환기 성능에 관한 실험적 연구 (An Experimental Study on the Performance of Semi-Closed Loop Ground Heat Exchanger)

  • 김욱중;염한길;이춘우
    • 한국신재생에너지학회:학술대회논문집
    • /
    • 한국신재생에너지학회 2007년도 추계학술대회 논문집
    • /
    • pp.542-545
    • /
    • 2007
  • A semi-closed loop ground heat exchanger is proposed and its performance is compared through the measuring the effective thermal conductivity of the ground. In-situ tests based on the line source model are carried out to evaluate the thermal characteristics of each ground heat exchanger which has different penetration water flow rate. The test results show the increasing effective thermal conductivity of ground as the penetration water flow rate(PWFR) is increased. Therefore, the higher thermal performance of the proposed semi-closed ground heat exchanger can be expected.

  • PDF

지중열교환기 설치 조건이 지중 유효 열전도도와 보어홀 열저항에 미치는 영향 (The Effects of the Installation Conditions of Ground Loop Heat Exchanger to the Thermal Conductivity and Borehole Resistance)

  • 임효재;공형진;강성재;최재호
    • 설비공학논문집
    • /
    • 제23권2호
    • /
    • pp.95-102
    • /
    • 2011
  • A ground loop heat exchanger in a ground source heat pump system is an important unit that determines the thermal performance of a system and its initial cost. A proper design requires certain site specific parameters, most importantly the ground effective thermal conductivity, the borehole thermal resistance and the undisturbed ground temperature. This study was performed to investigate the effect of some parameters such as borehole lengths, various grouting materials and U tube configurations on ground effective thermal conductivity and borehole thermal resistance. In this study, thermal response tests were conducted using a testing device to 9 different ground loop heat exchangers. From the experimental results, the length of ground loop heat exchanger affects to the effective thermal conductivity. The results of this experiment shows that higher thermal conductivity of grouting materials leads to the increase effective thermal conductivity from 22 to 32%. Also, mounting spacers have increased by 14%.

개방형 지열히트펌프 시스템의 성능평가 (Performance Evaluation of Open-Loop Ground Water Heat Pump system)

  • 김태원
    • 한국신재생에너지학회:학술대회논문집
    • /
    • 한국신재생에너지학회 2006년도 추계학술대회
    • /
    • pp.9-14
    • /
    • 2006
  • Open loop or ground water heat pump systems are the oldest of ground-source systems. Standing column wells can be used as highly efficient ground heat exchanger in geo-thermal heat pump systems, where hydrological and geological conditions are suitable. These systems require some careful considerations for well design, ground water flow, heat exchanger selection etc This paper describes 9round water temperature variations, performances in heat ins and cool ing mode and the results of ground water analysis.

  • PDF