• Title/Summary/Keyword: Hydrant system

Search Result 21, Processing Time 0.029 seconds

A Comparative study of the performance for hose reel hydrant system and indoor hydrant system (호스릴옥내소화전설비와 옥내소화전설비의 성능 비교 연구)

  • Nam, Jun-Seok;Baek, Chang-Sun;Kim, Joon-Bae;Kang, Tae-Young;Park, Sung-Ock;Han, Jae-Ho
    • Proceedings of the Korea Institute of Fire Science and Engineering Conference
    • /
    • 2008.04a
    • /
    • pp.104-107
    • /
    • 2008
  • The performance of hose reel hydrant system and indoor hydrant system was tested comparatively. At that result, a hose reel hydrant system are excellent and have the same performance as indoor hydrant system. If hose reel hydrant system has the performance that pressure is more than 0.17 MPa and flow-rate is over 130 LPM at the nozzle, it can be substituted for indoor hydrant system.

  • PDF

An Analysis on the Effect of Pressure System Installation on the Pipeline to Identify Pressurized Water and Self-inspection Ease in Apartment Building (아파트에 설치하는 옥내소화전 압력계 설치가 배관의 가압수 식별 및 자체점검 용이성 간의 영향 분석)

  • Son, Joo-Dal;Kong, Ha-Sung
    • Journal of the Korea Safety Management & Science
    • /
    • v.22 no.1
    • /
    • pp.33-44
    • /
    • 2020
  • This study analyzed how the installation of a pressure gauge in the indoor fire hydrant of an apartment building affected identifying pressurized water in the pipe, making it easier to conduct internal inspection on the fire suppression system, and ensuring reliability of fire suppression. The following are the study's results: First, identifying pressurized water in the indoor firefighting pipe had a positive effect on the installation of a pressure gauge in the indoor fire hydrant. This implies that a higher level of identification of pressurized water in the indoor firefighting pipe had a positive impact on improving the installation and use of a pressure gauge in the indoor fire hydrant. Second, making it easier for the fire safety officer to inspect the fire suppression system had a positive effect on the installation of a pressure gauge in the indoor fire hydrant. This suggests that if it becomes easier for the apartment building's stakeholder to conduct internal inspection or the firefighting facility manager to carry out inspection on the fire suppression system, it would have a positive effect on the installation of a pressure gauge in the indoor fire hydrant. Finally, ensuring reliability in fire suppression had a positive effect on the installation of a pressure gauge in the indoor fire hydrant. This implies that if it becomes easier to identify pressurized water in the indoor firefighting pipe, for the fire safety officer to conduct internal inspection, or for the firefighting facility manager to carry out inspection in accordance with the fire suppression system's internal inspection requirements, it would increase reliability in fire suppression, making it more necessary to install a pressure gauge in the indoor fire hydrant.

A Study on Improvement of Discharge Pressure Measurement of Indoor Fire Hydrant System (옥내소화전설비의 방수압 측정 개선에 관한 연구)

  • Min, Se-Hong;Jeong, Sang-Ho
    • Fire Science and Engineering
    • /
    • v.26 no.3
    • /
    • pp.67-72
    • /
    • 2012
  • Indoor fire hydrant facilities and sprinkler system applied to the initial fire suppression for buildings' interior fire are pivotal roles in extinguishing the fire in the early stage. The roof shapes of recent buildings combined with distinctive local culture and design are being constructed. Distinctive roof forms, i.e. gable roof buildings are planned and built, View point planning with the roof gardens also restricts measurement of the discharge pressure on the indoor fire hydrant, It is too narrow to gauge the water discharge pressure with deploying up to 5 water hoses. To resolve these problems improvement for the efficient management of indoor fire hydrant system and the effective early stage flame extinguishment is suggested.

A study on the removal of particulate matters using unidirectional flushing (단방향 플러싱에 의한 입자성 물질의 제거에 관한 연구)

  • Kim, Dooil;Cheon, Subin;Hyun, Inhwan
    • Journal of Korean Society of Water and Wastewater
    • /
    • v.29 no.3
    • /
    • pp.371-380
    • /
    • 2015
  • Particulate matters in a water distribution system are main causes of turbidity and discoloration of tap water. They could be removed by conventional or uni-directional flushing in a water distribution system. The behaviors and required flow velocity of particles are not well known for their flushing. A model water main and hydrant were made from transparent acrylic pipe of 30mm and 16mm in diameter, respectively. We analyzed the effect of flushing velocity, particle density, and particle diameter. We found that the existence of break-though velocities at which particles begin to be removed, and which are affected by their physical properties. The removal efficiencies seemed to be influenced by resuspension capabilities related to their upward movement from the bottom. Heavy particles like scale were hard to remove through upflow hydrant because the falling velocity, calculated using Stokes' law, was higher. Particle removal efficiencies of upward hydrant and downward drain showed minor differences. Additionally, the length between hydrant and control valve affected flushing efficiency because the particulate matters were trapped in this space by inertia and recirculating flow.

Comparison of Waterproofing Preparation Time with the Unfolded of Donut-type Staking Method Fire Hose in Indoor Hydrant System (옥내소화전설비에서 도너츠형 적재방식의 소방호스 전개형태에 따른 방수준비시간 비교)

  • Hong, Suk-Hwan;Kong, Ha-Sung
    • Journal of the Korea Safety Management & Science
    • /
    • v.23 no.3
    • /
    • pp.115-122
    • /
    • 2021
  • In this study, the purpose of this study was to examine the effect of twisting in the preparation of waterproofing in the process of unfolded donut-type staking method fire hoses in indoor hydrant system. The central pull-out method caused more twisting than the rolling method, and there was no significant difference in the number of twists according to the pull-out method in the case of male and female students. It was found that the time it took to untwist and prepare waterproofing was much shorter for male students. The angle valve and hose are connected, and the time to untwist and prepare for waterproofing after withdrawing the fire hose with the hose and nozzle connected was shorter than the unconnected state. In the rolling method, when a hose connected with two 15 m fire hoses was used and the angle valve-hose was connected, but the hose-nozzle was not connected, the least kinking occurred. The time to untwist and prepare for waterproofing was also the shortest. As a result, in the withdrawal method of the donut-type loaded fire hose in the indoor hydrant system, it is a rolling method rather than a central withdrawal method. With the angle valve and hose connected, unfold the fire hose with the hose and nozzle connected, if a large number of people unwind the twisted hose, the time to prepare for waterproofing can be shortened.

Analysis of the Number of Kinks with the Fire Hose Staking Method of Indoor Hydrant System (옥내소화전설비의 소방호스 적재방식에 따른 꼬임횟수 분석)

  • Hong, Suk-Hwan;Kong, Ha-Sung
    • Journal of the Korea Safety Management & Science
    • /
    • v.23 no.4
    • /
    • pp.61-66
    • /
    • 2021
  • In this study, according to the staking method of the fire hose in the indoor hydrant system, the number of kinks when the fire hose is deployed was measured and analyzed to examine how the staking method of the fire hose affects the kink when the hose is deployed. The fire hose staking method was classified into three types: donut-type, accordion-type, and hose hanger-type, and the walking speed and number of kinks were measured by repeating the experiment 5 times for male and female students. The results of the study are as follows. (1) Among the three types of fire hose staking methods, the donut-type staking method had an average of 92 times for male students and 86 times for female students on average. (2) The accordion-type and hose hanger-type staking methods showed similar results with an average of one or two kinks for both male and female students. (3) Regardless of the staking method, it was found that in general, male students with high walking speed had more kinking than female students with slow walking speed.

A Study on Application Formulas of The Reaction Force (반발력 적용식에 대한 연구)

  • Jeong, Kee-Sin
    • Proceedings of the Korea Institute of Fire Science and Engineering Conference
    • /
    • 2011.11a
    • /
    • pp.91-95
    • /
    • 2011
  • There are a few formulas to calculate the reaction force. I have studied these formulas for how to derive and where to use. And also have studied what do we careful to apply to actual fire protection systems such as nozzle of indoor and out door hydrant system. I suggested appropriate method to calculate the reaction force.

  • PDF

Water Jet Experiment of Automatic Fire-tracking Water Cannon Facility combined with Indoor Hydrant Facility in Road Tunnels (도로터널의 옥내소화전설비 겸용 자동화점추적 방수총설비의 방수실험)

  • Kim, Chang-Yong;Kong, Ha-Sung
    • Fire Science and Engineering
    • /
    • v.33 no.1
    • /
    • pp.92-98
    • /
    • 2019
  • To determine if water-jet nozzle moves and water jetting are effective according to the location of the fire, this study examined the automatic fire-tracking water cannon system and aan indoor hydrant system, such as water jet centered directivity, water jet range maintainability and water jet shape uniformity. First, an examination to find the center of fire accurately from this system design showed that the water jet centered test was accurate. Second, the water jet range test results showed that when water is jetted at the maximum water jet radius, the water jet shows an inaccurate result but within the allowable tolerance range. Finally, the water-jet shape test result confirmed that there are no problems in setting the block from the algorithm design.

Consideration on Fire-prevention Facilities for Wooden Cultural Heritages (목조문화재 보존을 위한 소방시설에 대한 고찰)

  • Kim, Tae-Goo
    • 보존과학연구
    • /
    • s.31
    • /
    • pp.155-171
    • /
    • 2010
  • Wooden cultural heritages have many factors of fires and structural characteristics vulnerable to the fire extinguishing. Also, they are surrounded with forests and so remote from fire stations, which make it difficult to handle it quickly when fires break out. Wooden cultural heritages made of wood materials belong to the general fire in a Class A. Taking characteristics such as a smoldering and a backfire from the that fire of wooden materials into consideration, extinguishing the fire by the cooling system is the most effective. If the fire can't be put out at the early stage, it is almost impossible to protect wooden cultural heritages from the fire, because wooden structures can be destroyed in a high temperature and in a short time and it takes around average 7 minutes to reach its peak of flames in the process of a fire. According to the geographical and environmental situation of the cultural heritages, currently, the fire-prevention facilities such as the auto fire detector for the prompt detection, the water mist fire suppression system for the 1st early and urgent fire suppression and the outdoor fire hydrant and the water curtain etc. for the 2nd full-scale suppression and the prevention of the fire gaining force are being installed for the wooden cultural heritages.

  • PDF

Survey Analysis of the Management of Fire Fighting Equipment (소방시설의 관리실태 조사 분석)

  • Mun, Suck-Jin;Rie, Dong-Ho
    • Fire Science and Engineering
    • /
    • v.25 no.6
    • /
    • pp.98-103
    • /
    • 2011
  • Currently, domestic architecture has applied the building fire-fighting equipments to most buildings except conventional houses, villas and facilities, and so on. However, the use of fire-fighting equipments what are not working properly result in a human life and property damages consistently like a fire of Icheon warehouse facilities, Korea cold storage, the tragic incident of subway in Daegu and the recent issue of a fire in the high-rise efficiency apartment, etc. In this study, I'm trying to seek solutions by taking research on the actual condition of fire alarming system, fire escaping equipment, Indoor Fire Hydrant Installation.