• Title/Summary/Keyword: IEC 61000 Std

Search Result 14, Processing Time 0.029 seconds

Time-varying Harmonics Measurement and Assessment of the Electric Arc Furnace Loads (시간에 따라 변하는 전기로 부하의 고조파 측정 및 평가)

  • Kim, Kyung-Chul;Jin, Seong-Eun;Park, Sang-Young;Lee, Joo-Hong;Lee, Il-Moo;Jeon, Young-Soo
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.20 no.1
    • /
    • pp.91-99
    • /
    • 2006
  • Large steel industries have nonlinear loads including electric arc furnaces and harmonic field measurements have shown that harmonic content of a waveform varies with time. Since the large loads are supplied from the power system grid, it must be recognized that not only will the system of utility be impacted, but neighboring customer system could be impacted as well. In this paper time-varying harmonics are evaluated by international harmonic standards IEEE Std. 519 and IEC 61000-3-6 using a cumulative probablistic approach.

A Study on the Harmonics Measurement, Assessment and Resonant Filter Application of the Electric Arc Furnace Loads (전기로 부하의 고조파 측정, 평가 및 동조필터 적용에 관한 연구)

  • Kim, Kyung-Chul;Jin, Seong-Eun;Lee, Joo-Hong
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.20 no.6
    • /
    • pp.35-42
    • /
    • 2006
  • Large steel industries have nonlinear loads including electric arc furnaces. These nonlinear loads generate harmonic currents and create distortions on the sinusoidal voltage of the power system. This paper provides an in depth analysis on harmonics field measurement of the electric arc furnace loads, adding a single-tuned filter at the customer bus for reducing harmonic distortion and harmonics assessment by the international harmonic standards IEC 61000-3-6 and IEEE Std. 519. The EDSA program was used as a simulation tool for the case study.

A Study on the Harmonics Measurement, Assessment and Resonant Filter Application of the Electrolyzer Loads (전해조 부하의 고조파 측정, 평가 및 동조필터 적용에 관한 연구)

  • Kim, Kyung-Chul;Jin, Seong-Eun;Lee, Joo-Hong;Seo, Beom-Gwan;Jeon, Young-Soo
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.20 no.4
    • /
    • pp.12-20
    • /
    • 2006
  • Heavy chemical industries have nonlinear loads including electrolyzers. The electrolysis consists of AC-BC converters which generate harmonic currents and create distortions on the sinusoidal voltage of the power system. This paper provides in depth an analysis on harmonics field measurement for the electrolyzer loads, adding a single-tuned filter at the customer bus for reducing harmonic distortion and harmonic assessment by the international harmonic standards IEC 61000-3-6 and IEEE Std. 519. The EDSA program was used as a simulation tool for the case study.

Time-varying Harmonics Measurement and Evaluation of the High Speed Electric Train Loads (시간에 따라 변하는 고속철 부하의 고조파 측정 및 평가)

  • Jin, Seong-Eun;Kim, Kyung-Chul;Lee, Joo-Hong;Jeon, Young-Soo
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.20 no.7
    • /
    • pp.29-37
    • /
    • 2006
  • High speed electric trains have nonlinear loads including converters and inverters for the control synchronous motors. Harmonics produced by these devices are large, but also have noticeable time varying characteristics. Since the large loads are supplied from the power system grid, it must be recognized that not only will the system of utility be impacted, but neighboring customer system could be impacted as well. In this paper time-varying harmonics for high speed electric train loads are measured and evaluated by international harmonic standards IEEE Std. 519 and IEC 61000-3-6 using a cumulative probablistic approach.

A Study on the Harmonics Effect of SVC in Electric Arc Furnace Loads

  • Kim, Kyung-Chul;Jin, Seong-Eun
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.20 no.9
    • /
    • pp.54-60
    • /
    • 2006
  • Large steel industries have time-varying nonlinear loads such as electric arc furnaces. These nonlinear loads generate harmonic currents and create distortions on the sinusoidal voltage of the power system. The main objective of the static var compensator is to maintain the rms voltage at the point of common coupling within the limit. In this research, harmonic mitigation studies were conducted with and without the SVC, and time-varying harmonics were evaluated according to the international harmonic standards (IEC 61000-3-6 and IEEE Std. 519) using a cumulative probabilistic approach.

A Study on the Hormonic Analysis of on Electronic Ballast (전자식 안정기의 고조파 저감 대책)

  • Hong, Soon-Seuk;Oh, Jung-Suk;Yoo, Tae-Kun
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.19 no.2
    • /
    • pp.35-41
    • /
    • 2005
  • Electric ballast is widely used to turn on the fluorescent. Electric ballast measure occurrence of harmonic through the actual measurement and it is simulated by modeling equivalent circuit for harmonic analysis. The purpose of this paper is to give an equivalent circuit modeling methodology for the harmonic currents generated by single-phase loads to evaluate a commercially available series resonant filter for the harmonic currents compensation based on the IEC 61000-3-2 and IEEE Std 519-1992 standards for limiting harmonic distortion.

A Study on the Time-varying Harmonics Measurement, Assessment and Simulation of the Electric Arc Furnace Loads (시간에 따라 변하는 전기로 부하의 고조파 측정, 평가 및 시뮬레이션에 관한 연구)

  • Kim, Kyung-Chul;Jin, Seong-Eun;Lee, Joo-Hong;Jeon, Young-Soo
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.20 no.5
    • /
    • pp.9-17
    • /
    • 2006
  • Large steel industries have nonlinear loads such as electric arc furnaces. Harmonic field measurements have shown that the harmonic contents of a waveform varies with time. Direct application of the harmonic assessment to the snapshot measurements would result in ambiguous conclusions depending on which instant is sampled. A cumulative probablistic approach is the most commonly used method to solve time-varying harmonics. Harmonic simulations are performed to evaluate the harmonic voltage and current distortions throughout the system. This paper provides an in depth analysis on harmonics field measurement of the electric arc furnace loads, harmonics assessment by the international harmonic standards IEC 61000-3-6 and IEEE Std. 519 and harmonic simulation for the time-varying harmonics. The EDSA program was used as a simulation tool for the case study.

A Study on the Harmonics Simulation of the High Speed Electric Train Loads by Field Tests (현장시험에 의한 고속전철 부하의 고조파 시뮬레이션에 관한 연구)

  • Kim, Kyung-Chul;Kim, You-June
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.21 no.6
    • /
    • pp.40-47
    • /
    • 2007
  • High speed electric trains have nonlinear loads including converters and inverters for the control synchronous motors. Harmonic field measurements have shown that the harmonic contents of a waveform varies with time. Direct application of the harmonic assessment to the snapshot measurements would result in ambiguous conclusions depending on which instant is sampled. A cumulative probablistic approach is the most commonly used method to solve time varying harmonics. Harmonic simulations are performed to evaluate the harmonic voltage and current distortions throughout the system. This paper provides an in depth analysis on harmonics field measurement of the high speed electric train loads, harmonics assessment by the international harmonic standards IEC 61000-3-6 and IEEE Std. 519-l992, and harmonics simulation using EDSA program for the case study.

A Study on the Economical PQMS of the Utility Distribution Power System (전력회사 관점의 배전계통 경제형 PQM 시스템 구축방안)

  • Park, Yong-Up;Lee, Keon-Hang
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.59 no.9
    • /
    • pp.1523-1529
    • /
    • 2010
  • This paper describes the distribution power system econimical PQMS(Power quality monitoring system) of Utility. Recently, the korea power quality standard has been established based on the IEC Std. By IEC Std., the power quality assessment point is measured in PCC(Point of common coupling). In this case, the utility has to construct PQM system in all customer PCC point and the PQ meter cost would be very high in order to acquire the suitable data. Also the distribution system would be encounter the communication overload problem due to the huge data. Accordingly the utilities could not apply to PQM system in the distribution power system by the cost and communication problem. In this paper, the proposed economical PQMS has the voltage and current signal reiteration function and FFT operation function is transferred the server. Also the voltage and current measurement channels are minimized by a classified substation construction.

Power Signal Compression Technique Using DCT (DCT를 이용한 전력신호 압축 기법)

  • Kim, Dae-Bong;Oh, Jong-Myung;Hong, Chan-Yung;Lee, Kyeong-Pyo;Lee, Myung-Sik;Park, Min-Sik
    • Proceedings of the KIEE Conference
    • /
    • 2011.07a
    • /
    • pp.105-106
    • /
    • 2011
  • 전력계통에서 비선형부하와 시변부하 사용의 증가 및 분산전원의 보급 증가로 전력품질(power quality)에 대한 관심이 증대되고 있다. 전력계통에서 전력품질은 전력신호를 통해 모니터링이 가능하다. 하지만 전력신호 상시 관측을 통한 전력품 모니터링은 많은 신호 데이터양이 필요하여 전력 신호 압축이 요구된다. 이에 따라 본 연구에서는 신호 압축 성능이 우수한 DCT(discrete cosine transform)기법을 이용하여 전력신호를 압축, 복원하는 방법을 제안한다. 그리고 DSP (digital signal processor) 보드를 통해서 압축 저장 된 신호를 오차 범위 5% 이내로 복원한다. 따라서 정전과 같은 이벤트(event)가 발생하였을 때 특정시간, 장소에서의 전압과 전류 파형을 볼 수 있게 한다. IEC 61000-4-30, IEEE std 1159에 근거하여 Matlab 프로그램 상에서의 성능을 평가하고 DSP보드를 이용하여 DCT를 이용한 데이터압축 시스템을 구현하였다.

  • PDF