• 제목/요약/키워드: Induction Voltage

검색결과 1,175건 처리시간 0.032초

Using the Under Voltage Load Shedding for Stability Enhancement of Power Systems Considering Induction Motor Load (유도전동기 부하 고려 시 저전압 부하차단을 이용한 전력계통 안정도 향상 방안)

  • Lee, Yun-Hwan
    • The Transactions of the Korean Institute of Electrical Engineers P
    • /
    • 제65권1호
    • /
    • pp.1-6
    • /
    • 2016
  • Recently, proportion of the induction motor load is gradually increased. When a contingency in the power systems, it has been discovered phenomenon that the voltage is delayed recover caused mechanical characteristics of the induction motor load. It can be a serious impact on the voltage stability of the power system considering induction motor load. The scheme to mitigate this phenomenon tripping off the motors to prevent voltage drop and delayed voltage recovery on the load demand side. Fault induced delayed voltage recovery phenomenon is caused by stalling of small induction motor load in transmission level contingencies. In this paper, fault induced delayed voltage recovery phenomenon mitigation method implementation under voltage load shedding on the korean power system considering induction motor load.

Analysis on the Switching Surge Characteristics of a High-Voltage Induction Motor Fed by PWM Inverter Using EMTP

  • Kim Jae-Chul;Song Seung-Yeop;Lee Do-Hoon
    • KIEE International Transactions on Power Engineering
    • /
    • 제5A권1호
    • /
    • pp.22-30
    • /
    • 2005
  • The PWM inverter drive may cause an over voltage at the motor terminal, which imposes severe electric stresses on the inter-turn insulation of motor windings. Unlike low-voltage induction motors, high-voltage induction motors have a stator type of form-wound coil for insulation and are insulated to the slot and the coil. So, this paper presents a PWM 3-level inverter, H-Bridge cascaded 7-level inverter and High-voltage induction motor model. It then analyzes the voltage that generates at the input terminal of the high-voltage induction motor fed by each inverter. Also, in order to examine a factor that influences the switching surge voltage, this paper proposes the system equivalent model and performs the case studies using EMTP.

Soft Start-up Characteristics Analysis of Squirrel Cage Induction Generator (농형 유도 발전기의 소프트 기동 특성 해석)

  • Kim, Jong-Gyeum;Park, Young-Jeen
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • 제65권1호
    • /
    • pp.103-107
    • /
    • 2016
  • In general, the voltage stability of induction generator is lower than synchronous generator. Induction generator has a number of advantages over the synchronous generator on the side of price and maintenance. So Induction generator has been applied to the small hydroelectric power of low output. Induction generator usually generates a high current during grid connection. The high current that occurs during grid connection can cause a voltage drop in the system. In order to increase the supply of the induction generator, it is necessary to propose a method of reducing high current. This paper proposes some method of the soft start to reduce voltage drop caused by the large starting current. soft-start method has high voltage drop effect than direct start method, control of firing angle can be increased the voltage drop effect.

Analysis for Voltage Fluctuation and Power Flow at the Grid-Connected Time of Squirrel-Cage Induction Generator (농형 유도발전기의 계통 연계시 전압 변동 및 전력 흐름 분석)

  • Kim, Jong-Gyeum
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • 제28권6호
    • /
    • pp.45-51
    • /
    • 2014
  • Synchronous generators and induction generators are mainly used in hydroelectric power generation. Synchronous generator is mainly applied to large hydroelectric plants but induction generator is applied to the small hydro power plants. Stability of induction generator is slightly less than the synchronous generator. However, induction generator has many advantages rather than a synchronous generator in terms of price and maintenance. So Induction generator is used primarily in small hydroelectric power station less than 1,000kW recently. Squirrel cage induction generator generates a high inrush current at the grid-connection. This high inrush current causes a voltage drop on the grid. In order to reduce the voltage drop and to analyze the power flow, the analysis for operating characteristics of the induction generator should be reviewed in advance. In this study, we analyzed the voltage drop and power flow analysis when a 1500kW induction generator is connected to the grid. The voltage drop is slightly higher than the acceptable range of distributed power supply voltage and the power flow of the generator is performed well.

A Study on the Voltage Drop of Induction Generator along the Rotor Shape (회전자 형상에 따른 유도발전기 전압강하에 대한 연구)

  • Kim, Jong-Gyeum
    • The Transactions of the Korean Institute of Electrical Engineers P
    • /
    • 제64권2호
    • /
    • pp.62-66
    • /
    • 2015
  • Induction generator is easy to durability and maintenance than the synchronous generator. So, recently Induction generator has been widely applied to small-scale hydroelectric power plant. When the rotor is operating faster than synchronous speed, induction machine can generate electric power. Induction generator has a large inrush currents, such as the starting current of the induction motor. Induction motor has been designed a variety of rotor shape in order to reduce starting current. Since the occurrence of high inrush current cause a voltage drop to the system, it will need to reduce possible. Because the starting current of the squirrel-cage induction motor varies in accordance with the rotor shape, it is necessary to analyze the magnitude of inrush current in order to apply to the generator. In this study, we analyzed the inrush current and the voltage drop caused in accordance with the rotor shape of 1500kw induction generator.

Analysis on the Effect of Filter to Mitigate Transient Overvoltage on the High Voltage Induction Motor Fed by Multi Level Inverter using EMTP (EMTP를 이용한 멀티레벨 인버터 구동 고압유도전동기에서 발생하는 과도과전압 저감필터의 효과분석)

  • Kwon, Young-Mok;Kim, Jae-Chul
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • 제20권10호
    • /
    • pp.82-93
    • /
    • 2006
  • In this paper, filters are designed to reduce transients overvoltage in inverter fed high-voltage large-capacity induction motor drive system. Design issues for a LCR filter at the inverter output terminals to reduce the dv/dt of the inverter output pulse and a RC filter at the induction motor input terminals to match the characteristic impedance between cable and induction motor are examined in detail. These filters are modeled to be suitable to high-voltage large-capacity induction motor. The performance of the filter is evaluated through simulation using EMTP(ElectroMagnetic Transients Program). We presented filters that used high voltage large-capacity induction Motor on the basis of this. Effect of the filter is analyzed for variation of the cable length. Characteristics of filters are analyzed to reduce harmonic in voltage waveform of induction motor input terminal. The switching surge voltage became the major cause to occur the insulation failure by serious voltage stress in the stator winding of induction motor. Filter for to mitigate transients overvoltage presents a required component in drive system of high-voltage large-capacity induction motor. Also, proposed filters are proved through simulation using EMTP.

Analysis on the effect of RC filter to mitigate transient overvoltage on the high voltage induction motor fed by Multi level inverter (멀티레벨 인버터 구동 고압유도전동기에서 발생하는 과도과전압 저감을 위한 RC필터의 효과분석)

  • Kwon, Young-Mok;Kim, Jae-Chul;Kim, Young-Sung;Lee, Yang-Jin
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 한국조명전기설비학회 2005년도 학술대회 논문집
    • /
    • pp.399-403
    • /
    • 2005
  • In this paper, we analyze on the effect of RC filter to mitigate transient overvoltage on the high voltage induction motor fed by H-bridge cascaded 7-level inverter. The switching surge voltage becomes the major cause to occur the insulation failure by serious voltage stress in the stator winding of high voltage induction motor. The effect of switching surge appears more serious in high voltage induction motor than low voltage induction motor. Consequently, we demonstrated that the RC filter connected to the motor terminals greatly reduces the transient voltage stress md ringing. The results of simulation show the suppression of transient overvoltage at the motor end of a long cable. using EMTP

  • PDF

A Study on the Susceptibility of Single-phase Sensitive Loads and the Three-phase Induction Motor by Voltage Sag (순간전압강하에 의한 단상 민감부하 및 삼상 유도전동기의 외란 민감도에 관한 연구)

  • Yun Sang-Yun;Moon Jong-Fil;Kim Jae-Chul;Lee Hee-Tae
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • 제55권1호
    • /
    • pp.37-44
    • /
    • 2006
  • In this paper we explore the susceptibility of common sensitive loads by voltage sags of power distribution systems. The experimental approach was used for obtaining the susceptibility of single-phase loads and the three-phase induction motor. The experimental result of single-phase loads was transformed to the ITIC(Information of Technology Industry Council) format and used for evaluating the adverse impacts of a individual and repetitive sags using the performance contour of the foreign standard data. In order to assess the impact of voltage sags on three-phase induction motor, also, the experiment was peformed. The experiment was focused on the current, torque, and speed loss of the motor during a voltage sag. For comparing the impacts of individual and repetitive voltage sags, the variations of motor torque is focused among the experimental results. The sensitive curves of instantaneous current peak are used to describe the susceptibility of three-phase induction motor and 진so it were used for the quantitative analysis of the impact of three-phase induction motor due to voltage sags. Through the results of experiment, we verified that some types loads have more severe impact at repetitive voltage sags than individual ones and proposed method can be effectively used to evaluate the actual impact of voltage sags.

An Investigation of Induction Motor Saturation under Voltage Fluctuation Conditions

  • Ghaseminezhad, Morteza;Doroudi, Aref;Hosseinian, Seyed Hossein;Jalilian, Alireza
    • Journal of Magnetics
    • /
    • 제22권2호
    • /
    • pp.306-314
    • /
    • 2017
  • Nowadays power quality effects on induction motors have gained significant attention due to wide application of these motors in industry. The impact of grid voltage fluctuations on the induction motor behavior is one of the important issues to be studied by power engineers. The degree of iron saturation is a paramount factor affecting induction motors performance. This paper investigates the effects of voltage fluctuations on motor magnetic saturation based on the harmonic content of airgap flux density by finite element method (FEM). It is clarified that the saturation harmonics under normal range of voltage fluctuations have not changed significantly with respect to pure sinusoidal conditions. Experimental results on a 1.1 kW, 380 V, 50 Hz, 2 pole induction motor are employed to validate the accuracy of the simulation results.

Impoved Performance of Sensorless Induction Motor Drive in Low Speed Range Using Variable Link Voltage (가변 링크전압에 의한 센서리스 유도전동기의 저속운전 성능개선)

  • 김상균;권영안
    • The Transactions of the Korean Institute of Electrical Engineers B
    • /
    • 제53권2호
    • /
    • pp.90-98
    • /
    • 2004
  • Variable-speed drives are being continually innovated. Recently, sensorless induction motor drives have been much studied due to several advantages. Most sensorless algorithms are based on the mathematical modeling of motors, and all the information is obtained from the monitored voltages and currents. Therefore, the accuracy of such variables largely affects the performance of a sensorless induction motor drive. However, the output voltage of the SVPWM-VSI which is widely used in a sensorless induction motor drive has a considerable error, especially in a low speed range. This paper proposes a variation of the dc link voltage as a high-performance strategy for overcoming the above problem. The proposed strategy leads to an improved resolution of the output voltage of the SVPWM-VSI in a sensorless induction motor drive. Simulation and experiment have been performed for the verification of the proposed strategy.