Development of 25.8kV class solid insulated switchgear (25.8kV 고체절연스위치기어 개발)

  • Lee, J.H.;Ma, J.H.;Yu, L.;Lee, J.G.;Won, S.Y.;Lee, S.W.;Kim, Y.G.;Kil, G.S.
    • Proceedings of the KIEE Conference
    • /
    • 2008.10c
    • /
    • pp.226-228
    • /
    • 2008
  • In recent years, the companies of electric power equipment for MV and HV classes trend to develop the eco-friendly insulated(solid, eco-gas, air etc.) switchgear which replaces existent SF6 gas insulated switchgear due to environmental problems such as global warming and so on. This paper makes reference to the newly developed Solid Insulated Switchgear (SIS) which uses the eco-friendly material such as epoxy for insulation. The insulation of the solid insulated switchgear (SIS) is composed of an epoxy, vacuum and air. The solid insulated switchgear (SIS) is a slate of the art product. The advantages of SIS are advanced reliability, economical efficiency, safety, maintenance free, reduction of installation area and the protection of environment. The solid insulated switchgear (SIS) is FE Analyzed such as electromagnetic, mechanical, thermal and fluid in order to find the optimal design. Thens SIS has been verified by international standard test. (IEC 62271 - 100 and so on.) As a result of this, the solid insulated switchgear (SIS) has been estimated as an alternative for eco-friendly MV class switchgear.

  • PDF

30 Magnetic Analysis on Temperature Rise Resulting from Induced Eddy current In Gas Insulated Switchgear (3차원 자계해석을 통한 GIS 모선의 와전류에 의한 온도 상승)

  • Lee, B.W.;Sohn, J.M.;Kang, J.S.;Seo, J.M.
    • Proceedings of the KIEE Conference
    • /
    • 1999.07e
    • /
    • pp.2274-2276
    • /
    • 1999
  • In this work, temperature rise and eddy current distribution on the enclosure and conductor of 3 pole gas insulated switchgear were investigated using analytical and experimental measures. The design of the diameters of the conductors and the enclosures of a meal clad gas insulated switchgear is primarily based on the insulation requirements. It is very difficult problem to predict the temperature rise of enclosed switchgear due to the complexity of the phenomena of heat transfer and existence of eddy current loss. To overcome this situations, we focused on the eddy current distribution on the enclosure of switchgear caused by high current 3 pole conductor as a fundamental basis. The experimental results about temperature distribution of 3 pole gas insulated switchgear were reported and measurements are compared with predictions of three-dimensional thermal model for eddy current analysis. As a result, three dimensional numerical analysis found to be in close relationship with experimental results and thermal model is efficient to predict the abnormal temperature rise in switchgear.

  • PDF

MV Switchgear Technology Trend and Diagnosis Technology (중전압 차단 개폐장치의 기술동향과 진단기술)

  • Lee, H.D.;Lee, S.W.;Sin, Y.S.;Kim, Y.G.
    • Proceedings of the KIEE Conference
    • /
    • 2005.05b
    • /
    • pp.10-12
    • /
    • 2005
  • This paper describes MV switchgear technology trends and diagnosis technology. MV switchgear has been rapidly changed into compact, reliability and safety situation. And suggested road-map to implement condition assessment or condition based maintenance. On-line diagnosis technology, life evaluation technology and system technology are suggested.

  • PDF

The Prototype-Making of a Three-Phase Power Management Device for the Industrial Switchgear (산업용 분전반 적용을 위한 3상 전력 관리 장치 시작품 제작에 대한 연구)

  • Ko, Yun-Seok;Shin, Hyun-Yong
    • The Journal of the Korea institute of electronic communication sciences
    • /
    • v.5 no.5
    • /
    • pp.498-503
    • /
    • 2010
  • Recently, the industrial electric customers require a digital switchgear which can improve the safety and reliability of the power supply, and the quality of electric power by on-line monitoring the electric power information based on the internet under the ubiquitous environments. Accordingly, in this paper, a industrial switch-gear prototype is designed based on the power supply method of three phase, four-line type, and then a three-phase electric management module of the digital switchgear is made for industrial electric customer system. Finally, the three-phase voltage and current measuring function of the prototype is verified from real power load test.

Partial Discharge Monitoring for $SF_6$ Insulated MV Switchgear using UHF sensors (UHF Sensor를 이용한 SF6 절연 MV 개폐기의 부분방전 검출 시스템)

  • Lee, Do-Hoon;Kang, Won-Jong;Shin, Yang-Sop;Kim, Young-Geun;Oh, Il-Sung;Kim, Dong-Myung;Kwon, Tae-Ho
    • Proceedings of the KIEE Conference
    • /
    • 2007.07a
    • /
    • pp.2040-2041
    • /
    • 2007
  • In this paper, the UHF PD(Partial Discharge) sensors for $SF_6$ insulated MV $SF_6$ switchgear have been proposed and related investigations have been performed in order to detect the PD which were produced inside the MV $SF_6$ switchgear. Firstly, the internal type UHF PD sensor based on spiral antenna theory has been developed. This type sensor is highly sensitive and has lowly effect on by on-site noise. Secondly, the external type UHF PD sensor was developed based on log periodic antenna concept. This type sensor is removable and detectable for operating switchgear. These sensors were designed and simulated using RF simulation tool. In order to verify the sensitivity of these sensors, we performed the on-site test using the mock-up switchgears including the artificial defects which were the protrusion on high voltage conductor, free moving metal particle and surface defect on insulator. These mock-up switchgear were installed on the test distribution line.

  • PDF

A Study on the Diagnostic Techniques of Leakage Current for Switch-Gear Based on LabVIEW (LabVIEW 기반의 수배전반 누설전류 진단기법 연구)

  • Kim, Yong-Seong;Jang, Sung-Il;Choi, Jung-Hwan;Kim, Kwang-Ho
    • Journal of Industrial Technology
    • /
    • v.34
    • /
    • pp.61-66
    • /
    • 2014
  • Recently, Because the consumption of electricity is increased, having stable electricity supply and diagnosis of the power device is important. In this paper, I propose a diagnostic techniques of the leakage current for switchgear based on LabVIEW NI's. Using the data obtained from the leakage current sensor installed in switchgear panels, in performed continuously diagnosis, notifications and warnings can be the administrator immediately results. It is expected accordingly, the administrator will be able to take prompt action. Using the virtual switchgear with a PXI NI's, war tested the proposed techniques.

  • PDF

Pressure-Rise Measurement and Analysis of Low Current Interruption Capability of a 72.5kV 20kA Gas Circuit Breaker for Electrical Railway System (72.5kV 20kA 전철용 가스차단기의 압력상승 측정 및 소전류 차단성능해석)

  • Song, K.D.;Park, K.Y.;Chong, J.K.;Oh, Y.H.;Min, K.S.;Park, Ki-Y.
    • Proceedings of the KIEE Conference
    • /
    • 1998.07a
    • /
    • pp.164-166
    • /
    • 1998
  • This paper presents the results of the measured pressure-rise and the analyzed results of the cold gas flow-field in a 72.5kV 20kA gas circuit breaker for the electrical railway system. The analysis of cold gas flow field and the calculation of electric field strength have been performed in 3 types of interrupters and the low current interruption capability has been estimated for each of the gas circuit breaker considering the opening speed, the nozzle shape and the stroke length.

  • PDF

Development of Permanent Magnet Synchronous Motor for High voltage Gas Insulated Switchgear (초고압 Gas Insulated Switchgear 구동용 전동기 개발)

  • Oh, Young-Jin;Jeong, Gyun-Ha;Lee, In-Woo
    • Proceedings of the KIEE Conference
    • /
    • 2007.07a
    • /
    • pp.919-920
    • /
    • 2007
  • Currently national High Voltage Gas Insulated Switchgear (GIS) operating mechanism is made up of spring operating mechanism or hydraulic operating mechanism. On the contrary, advanced technology trend in foreign countries replace current mechanical mechanism with electrical motor-drive mechanism that leads to participate GIS bid and increase sales with the point of simplification of driving system and IT application. Therefor it is essential to develop high voltage GIS using the motor-drive system to develop national heavy electric machine industries and catch up the technology to the advanced level. This paper therefore presents design and analysis of permanent synchronous motor for high voltage GIS, verifies the performance by the experimental test.

  • PDF

A Study on the Actual Condition Investigation of the Disconnecting Switchgear of 170kV GIS (170kV GIS용 단로기의 현장 사용 실태 조사)

  • Lee, Eun-Suk;Kim, Jong-Seo;Cheon, Jong-Cheol
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2003.07b
    • /
    • pp.1180-1183
    • /
    • 2003
  • 170kV GIS(Gas Insulated Switchgear) is widely used in large industrial factory-electrical facilities of private use because has many benefits. But Other equipments's failures are occurred by GIS failures and give rise economic problems to user. Therefore we will examine the actual condition of the 170kV GIS-electrical facilities of private use and are able to confirm the distribution characteristic analysis of disconnecting switchgear. In this paper, we presents the actual condition investigation of the disconnecting switchgear of 170kV GIS-electrical facilities of private use by post - failure pattern, inspection method, test equipments and so forth.

  • PDF

Development of the replaced Eco-friendly SIS with GIS for 25.8kV class (25.8kV $SF_6$가스절연 스위치기어(GIS)를 대체한 친환경 고체절연 스위치기어(SIS) 개발)

  • Ma, Ji-Hoon;Zheng, Meng-Lei;Yoo, Lyun;Won, Sung-Yoen;Lee, Seog-Won;Kim, Young-Keun
    • Proceedings of the KIEE Conference
    • /
    • 2009.07a
    • /
    • pp.1219_1220
    • /
    • 2009
  • In recent years, the companies of electric power equipment for MV, HV class trend to develop that the eco-friendly insulated(solid, eco-gas, air etc.) switchgear replace with existent SF6 gas insulated switchgear by environmental problems such as global warming and soon. This paper introduces the Solid Insulated Switchgear(SIS) which is the epoxy of eco-friendly insulation material. The characteristic of SIS to introduce in this paper is as following. 1) Eco-friendly. (SF6 gas free) 2) The structure of flexible system. (Expansion) 3) The optimum design. (The Analysis of electrical & mechanical) 4) An Interface treatment between epoxy and insert. (Molding technology) This paper described about some technology for development of SIS.

  • PDF