• Title/Summary/Keyword: Insulation design

Search Result 889, Processing Time 0.039 seconds

Multi-layered Effect for the Insulation Design of a HTS Cable (고온초전도 케이블의 절연설계를 위한 적층효과)

  • Kwag, Dong-Soon;Cheon, Hyeon-Gweon;Kim, Hae-Jong;Cho, Jeon-Wook;Chung, Soon-Yong;Kim, Sang-Hyun
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.18 no.10
    • /
    • pp.950-955
    • /
    • 2005
  • For the insulation design of a high temperature superconducting(HTS) cable, three kinds of design method were proposed, which used AC and impulse withstand voltage and partial discharge inception strength. However, the designed insulation thickness by AC and impulse could not be applied to cable fabrication process due to much low electrical breakdown strength. The effect of the multi-layered insulation paper was not considered on the previous insulation design and the insulation thickness by partial discharge inception strength could be applied only. In this paper, the electrical breakdown characteristic, which considered the effect of multi-layered of LPP, was investigated to design the insulation thickness.

Design of Insulation and Bending Test for a 154 kV Class HTS Cable (154 kV급 HTS 케이블의 절연설계 및 굴곡시험)

  • Choi, Jin-Wook;Choi, Jae-Hyeong;Lim, Eung-Choon;Kim, Hae-Jong;Cho, Jeon-Wook;Kim, Sang-Hyun
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.21 no.11
    • /
    • pp.1024-1028
    • /
    • 2008
  • It is important that study on cryogenic electrical insulation design to develop the cold dielectric(CD) type HTS cable because the cable is operated under the high voltage environment in cryogenic temperature. This paper proposes two types of insulation design to carry out the maximum insulation design for 154 kV-class HT cable. The proposed insulation design method takes into consideration AC and lightning impulse withstand voltage so as to prevent AC breakdown for power frequency operating voltage during operating the cable and breakdown for lightning impulse voltage. The final insulation thickness is determined by selecting high value out of two insulation thickness calculated through the two insulation design methods. And we researched electrical insulation characteristics of HTS cable according to bending ratio and the number of bending.

Electrical Insulation Design of a 154 kV Class HTS Cable and Termination (154 kV급 고온초전도 케이블 및 단말의 전기절연 설계)

  • Kwag, Dong-Soon;Cheon, Hyeon-Gweon;Choi, Jae-Hyeong;Kim, Hae-Jong;Cho, Jeon-Wook;Kim, Sang -Hyun
    • Progress in Superconductivity and Cryogenics
    • /
    • v.9 no.1
    • /
    • pp.61-66
    • /
    • 2007
  • A transmission class high-temperature superconducting(HTS) power cable system is being developed in Korea. For insulation design of this cable the grading method of insulating paper is proposed. Two kinds of laminated polypropylene paper that has different thickness has been used as the electrical insulation material. The use of graded insulation gives improved mechanical bending properties of the cable. In a HTS cable technology the terminations are important components. A HTS cable termination is energized with the line-to-ground voltage between the coaxial center and outer surrounding conductors. in the axial direction. There is also a temperature difference from ambient to about 77 K. For insulation design of this termination, glass fiber reinforced plastic(GFRP) was used as the insulation material of the termination body, and the capacitance-graded method is proposed. This paper will report on the experimental investigations on impulse breakdown and surface flashover characteristics of the insulation materials for insulation design of a transmission class HTS power cable and termination. Based on these experimental data, the electrical insulation design of a transmission class HTS power cable and termination was carried out.

Experiment on Coolability through External Reactor Vessel Cooling according to RPV Insulation Design (국내원전 단열재 설계특성에 따른 외벽냉각 효과검증 실험)

  • Kang, Kyoung-Ho;Park, Rae-Joon;Kim, Snag-Baik
    • Proceedings of the KSME Conference
    • /
    • 2003.04a
    • /
    • pp.1578-1583
    • /
    • 2003
  • LAVA-ERVC experiments have been performed to investigate the effect of insulation design features on the coolability in case of the external reactor vessel cooling (ERVC). All the 4 tests have been performed using Alumina iron thermite melt as a corium simulant. Due to the limited steam venting through the insulation, steam binding occurred inside the annulus in the KSNP case simulation. On the contrary, in the tests which were performed for simulating the APR1400 insulation design, sufficient water ingression and steam venting through the insulation lead to effective cool down of the vessel characterized by nucleate boiling. It could be found from the experimental results that modification of the insulation design allowing sufficient ventilation could increase the positive effects of the external reactor vessel cooling.

  • PDF

Insulation Design for a 154 kV Class HTS Power Cable (154kV급 고온초전도 전력케이블의 전기절연 설계)

  • Kwag, Dong-Soon;Cheon, Hyeon-Gweon;Choi, Jae-Hyeong;Kim, Hae-Jong;Cho, Jeon-Wook;Yun, Mun-Soo;Kim, Sang-Hyun
    • Progress in Superconductivity and Cryogenics
    • /
    • v.8 no.1
    • /
    • pp.29-33
    • /
    • 2006
  • A 154 kV class high temperature superconducting (HTS) power cable system is developing in Korea. For insulation design or this cable, the grading method of insulating paper is proposed. The use of graded insulation gives improved bending properties of the cable. Therefore, we discussed the electrical stress distribution and calculation for grading insulation design of a HTS cable. Also. the basic insulation design of 154 kV class HTS power cable was done.

The Electrical Insulation Design of 600kJ Conduction Cooled HTS SMES (600kJ 전도냉각 고온초전도 SMES의 전기절연 설계)

  • Choi, Jae-Hyeong;Kwag, Dong-Soon;Cheon, Hyeon-Gweon;Min, Chi-Hyun;Kim, Hae-Jong;Seong, Ki-Chul;Kim, Sang-Hyun
    • Progress in Superconductivity and Cryogenics
    • /
    • v.9 no.3
    • /
    • pp.67-71
    • /
    • 2007
  • The electrical insulation design of 600 kJ conduction cooled high-Tc superconducting magnetic energy storage (SMES) have been studied in this paper. The high voltage is applied to both ends of magnet of high-Tc SMES by quench or energy discharge. Therefore. the insulation design of the high voltage needs for commercialization. stability. reliability and so on. In this study. we analyzed the insulation composition of a high-Tc SMES. and investigated about the insulation characteristics of the materials such as Kapton. AIN. $Al_2O_3$. GFRP and vacuum in cryogenic temperature. Base on these results. the insulation design for 600 kJ conduction cooled high-Tc SMES was performed.

Study on Insulation Design of Surge Voltages for Convex Winding type Ribbon Core Transformer (Convex형 권선배치방식을 취한 권철심변압기의 충격파절연설계에 관한 연구)

  • 황영문;조철제;김중한
    • 전기의세계
    • /
    • v.22 no.3
    • /
    • pp.13-24
    • /
    • 1973
  • In this report, as a method to solve the problems on impulse insulation coordination in ribbon core transformer owing to it's BIL stepping up, new design to alter winding distribution of multiple-layer concentric winding to Convex type winding is proposed. The main focus of this method is to settle the weakness of axial direction insulation strength and as a result of theoretical analysis through experiment of model transformers, the following conclusions are obtained; (a) As the electric loadings in a design which increases by strengthenning axial direction insulation endurance in presently avarilable transformers owing to it's BIL stepping up can be restricted in Convex type winding, reasonable design will be suited to the transformer with higher BIL. (b) Convex type winding is a very improved insulation design in respect of insulation coordination because it has shield plate effect to even impulse oscillation. (c) There is a disadvantage to cause leakage flux to increase in Convex type winding, however, the constancy of electric loadings in a design in spite of BIL stepping up restricts the increase of leakage flux to some extent.

  • PDF

Design & system construction of insulation on the traction motor for EMU (철도차량용 견인전동기의 절연설계 및 절연시스템 구성)

  • 왕종배;홍선호;조연옥;김명룡
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2001.07a
    • /
    • pp.194-197
    • /
    • 2001
  • Traction motors driven by high speed switching inverters is demanded higher operating temperature, severe duty cycles, higher starting current, frequent voltage transients and finally severe environmental exposure. For applications to inverter duty, traction motors needs a special insulation system, which has characteristics of increased bond strength, lower operating temperature and higher turn-to-turn insulation. In this paper, design considerations and manufacturing procedure of 200 Class insulation system with polyimde(Kapton) main insulation and silicone resin VPI process on the traction motor for EMU will be reviewed. And performance test and long life evaluation test which prove stability and long life evaluation test which prove stability and reliability of insulation system for traction motor will be introduced.

  • PDF

Research on Multi-layered Effect for the Insulation Design of a HTS Cable (고온초전도 케이블의 절연설계를 위한 적층효과에 관한 연구)

  • Kwag, Dong-Soon;Kim, Hae-Jong;Cho, Jeon-Wook;Kim, Hae-Joon;Kim, Jae-Ho;Cheon, Hyeon-Gweon;Kim, Sang-Hyun
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2005.07a
    • /
    • pp.560-561
    • /
    • 2005
  • For the insulation design of a HTS cable, the withstand voltage of three kinds were proposed. One of them is the AC design withstand voltage, another is the impulse design withstand voltage, and the other is the partial discharge inception stress. However, the multi-layered effect was not considered on insulation design of a HTS cable at existent design process. Therefore in this paper, the electrical breakdown characteristics by multi-layered effect of LPP insulation paper were investigated. Based on these results, the insulation thickness of 22.9 kV class HTS cable was designed, and compared with existent design process.

  • PDF

Electrical Insulation Design and Experimental Results of a High-Tc Superconducting Cable (고온초전도 케이블의 전기절연 설계 및 시험평가)

  • Kwag, Dong-Soon;Cheon, Cheon-Gweon;Choi, Jae-Hyeong;Kim, Hae-Jong;Cho, Jeon-Wook;Kim, Sang-Hyun
    • The Transactions of the Korean Institute of Electrical Engineers B
    • /
    • v.55 no.12
    • /
    • pp.640-645
    • /
    • 2006
  • A 22.9kV/50MVA class high temperature superconducting(HTS) power cable system was developed in Korea. For the optimization of electrical insulation design for a HTS cable, it is necessary to investigate the ac breakdown impulse breakdown and partial discharge inception stress of the liquid nitrogen/laminated polypropylene paper(LPP) composite insulation system. They were used to insulation design of the model cable for a 22.9kV class HTS power cable and the model cable was manufactured. The insulation test of the manufactured model cable was evaluated in various conditions and was satisfied standard technical specification in Korea. Base on these experimental data, the single and 3 phase HTS cable of a prototype were manufactured and verified.