• 제목/요약/키워드: Islanding

검색결과 189건 처리시간 0.038초

A Novel Anti-Islanding Method for Utility Interconnection of Distributed Power Generation Systems

  • In-Ho
    • KIEE International Transaction on Electrical Machinery and Energy Conversion Systems
    • /
    • 제4B권4호
    • /
    • pp.217-224
    • /
    • 2004
  • A novel anti-islanding method for the distributed power generation system (DPGS) is proposed in this paper. Three different islanding scenarios are explored and presented based on the analysis of real and reactive power mismatch. It is shown via investigation that islanding voltage is a function of real power alone, where its frequency is a function of both real and reactive power. Following this analysis, a robust anti-islanding algorithm is developed. The proposed algorithm continuously perturbs ($\pm$5%) the reactive power supplied by the DPGS while simultaneously monitoring the utility voltage and frequency. In the event of islanding, a measurable frequency deviation takes place, upon which the real power of the DPGS is further reduced to 80%. A drop in voltage positively confirms islanding and the DPGS is then safely disconnected. This method of control is shown to be robust: it is able to detect islanding under resonant loads and is also fast acting (operable in one cycle). Possible islanding conditions are simulated and verified through analysis. Experimental results on a 0.5kW fuel cell system connected to a utility grid are discussed.

Seamless Transfer를 위한 계통연계형 인버터의 간접전류 제어기법 (Indirect Control of Utility Interactive Inverter for Seamless Transfer)

  • 유태식;최세완;김효성
    • 전력전자학회:학술대회논문집
    • /
    • 전력전자학회 2005년도 전력전자학술대회 논문집
    • /
    • pp.329-332
    • /
    • 2005
  • Distributed generation (DG) systems fall in islanding operation when they still in operation even when the main grid is out of electric power Islanding operation is further classified into intentional islanding and unintentional islanding operations. In intentional islanding operation, the DG backs up critical loads while it separates from the main grid on islanding detection. Intentional islanding operation increases utilization of the DG system during the islanding operation. This paper proposes reasonal inverter topology and its control algorithm for seamless transfer of DG systems in intentional islanding operation.

  • PDF

분산 전원의 고립 운전 검출 기법의 개발 (Development of a New Islanding Detection Method for Distributed Resources)

  • 장성일;김광호
    • 대한전기학회논문지:전력기술부문A
    • /
    • 제50권11호
    • /
    • pp.506-513
    • /
    • 2001
  • The islanding detection for distributed resources (DR) becomes an important and emerging issue in power system protection since the distributed generator installations are rapidly increasing and most of the installed systems are interconnected with distribution network. In order to avoid the negative impacts from islanding operations of DR on protection, operation and management of distribution system, it is necessary to effectively detect the islanding operations of DR and rapidly disconnect it from distribution network. Generally, it is difficult to detect islanding operation by monitoring only one system parameter This paper presents a new logic based islanding detection method for distributed resources(DR) which are interconnected with distribution network. The proposed method detects the islanding operation by monitoring four system parameter: voltage variation, phase displacement, frequency variation, and the variation of total harmonic distortion(THD) of current; therefore, it effectively detects island operation of DR unit operating in parallel with the distribution network. We also verified the efficiency of the proposed algorithm using the radial distribution network of IEEE 34 bus model.

  • PDF

계통연계형 태양광 인버터의 단독운전 방지를 위한 새로운 알고리즘 개발 (Development of Novel Algorithm for Anti-Islanding of Grid-Connected PV Inverter)

  • 최정식;고재섭;정동화
    • 조명전기설비학회논문지
    • /
    • 제25권10호
    • /
    • pp.76-86
    • /
    • 2011
  • This paper proposes novel algorithm for anti-islanding of grid-connected photovoltaic(PV) inverter. The islanding of PV systems can cause a variety of problems such as deterioration in power quality and electric shock. To prevent islanding, many anti-islanding methods are researched. Typical methods of anti-islanding are active frequency drift(AFD) and active frequency drift positive feedback(AFDPF). However, the AFD has problem that widely exists non diction zone(NDZ). The AFDPF is a method that improves the AFD method and is detected islanding by changing the chopping fraction(cf). However, The AFDPF does not detect when cf is very small and does not satisfy the IEEE Std. 929-2000 when cf is very big. Therefore, this paper proposes novel anti-islanding method that is simple to implement using virtual resister. The anti-islanding method proposed in this paper is compared with conventional method. The validity of this paper is proved using this result.

A Novel Active Anti-islanding Method for Grid-connected Photovoltaic Inverter

  • Jung, Young-Seok;Choi, Jae-Ho;Yu, Gwon-Jong
    • Journal of Power Electronics
    • /
    • 제7권1호
    • /
    • pp.64-71
    • /
    • 2007
  • This paper proposes a novel active frequency drift (AFD) method to improve the islanding detection performance with minimum current harmonics. To detect the islanding phenomenon of grid-connected photovoltaic (PV) inverters concerning the safety hazards and possible damage to other electric equipment, anti-islanding methods have been described. The AFD method that uses chopping fraction (cf) enables the islanding detection to drift up (or down) the frequency of the voltage during the islanding situation. However, the performance of the conventional AFD method is inefficient and causes difficulty in designing the appropriate cf value to meet the limit of harmonics. In this paper, the periodic chopping fraction based on a novel AFD method is proposed. This proposed method shows the analytical design value of cf to meet the test procedure of IEEE Std. 929-2000 with power quality and islanding detection time. To verify the validation of the proposed method, the islanding test results are presented. It is confirmed that the proposed method has not only less harmonic distortion but also better performance of islanding detection compared with the conventional AFD method.

단독운전 방지를 위한 능동적 주파수 변환 기법의 검출 성능 및 THD 분석 (Detection Performance and THD Analysis of Active Frequency Drift for Anti-Islanding)

  • 조영민;최주엽;송승호;최익;이영권
    • 한국태양에너지학회 논문집
    • /
    • 제35권2호
    • /
    • pp.11-19
    • /
    • 2015
  • Islanding is a phenomenon that EPS(Electric Power System) is continuously energized by PV PCS(Photovoltaic Power Conditioning System) even when EPS is isolated from the grid. Unintentional islanding will result in safety hazard, power quality degradation and many other issues. So, islanding protection of grid-connected PV PCS is a key function for standards compliance. Nowadays, many anti-islanding schemes are researched. But existing anti-islanding schemes used in PV PCS have power quality degradation and non-detection zone issues. This paper analyses not only detection performance of existed anti-islanding schemes using active frequency drift but also THD of PCS output current according to each value disturbance for anti-islanding. In addition, the lowest value of disturbance in each scheme was tabulated under guarantee of anti-islanding condition.

시간영역에서 순시 유효/무효전력을 이용한 마이크로그리드의 단독운전 판단 (Islanding Detection for a Micro-Grid based on the Instantaneous Active and Reactive Powers in the Time Domain)

  • 이영귀;김연희;정태영;김태현;강용철
    • 전기학회논문지
    • /
    • 제61권1호
    • /
    • pp.22-27
    • /
    • 2012
  • Correct and fast detection of a micro-grid (MG) islanding is essential to the MG since operation, control and protection of the MG depend on an operating mode i.e., an interconnected mode or an islanding mode. When islanding occurs, the frequency of the point of common coupling (PCC) is not the nominal frequency during the transient state owing to the frequency rise or drop of generators in the MG. Thus, the active and reactive power calculated by the frequency domain based method such as Fourier Transform might contain some errors. This paper proposes an islanding detection algorithm for the MG based on the instantaneous active and reactive powers delivered to the dedicated line in the time domain. During the islanding mode, the instantaneous active and reactive powers delivered to the dedicated line are constants, which depend on the voltage of the PCC and the impedance of the dedicated line. In this paper, the instantaneous active and reactive powers are calculated in the time domain and used to detect islanding. The performance of the proposed algorithm is verified under various scenarios including islanding conditions, fault conditions and load variation using the PSCAD/EMTDC simulator. The results indicate that the algorithm successfully detects islanding for the MG.

분산형 태양광발전시스템의 단독운전 검출기법 (Anti-islanding method for distributed PV generation systems)

  • 황인호;안교상
    • 전력전자학회:학술대회논문집
    • /
    • 전력전자학회 2005년도 전력전자학술대회 논문집
    • /
    • pp.64-67
    • /
    • 2005
  • Many anti-islanding methods have been developed and tested in pratice. Generally, it seems to be possible to include effective and reliable anti-islanding methods in the PV inverter However, it is difficult to detect islanding phenomenon in the case of multiple systems in the same distribution line. In this paper, the islanding possibility of distributed PV generation system is analyzed and discussed to detect islanding phenomenon.

  • PDF

병렬연결된 다수 대 계통연계형 인버터를 위한 단독운전 방지 기법 (Anti-Islanding Scheme for a Number of Grid-connected Inverters under Parallel Operation)

  • 김동균;박관남;조상윤;이영권;유권종;송승호;최익;최주엽
    • 전력전자학회:학술대회논문집
    • /
    • 전력전자학회 2016년도 전력전자학술대회 논문집
    • /
    • pp.351-352
    • /
    • 2016
  • Since anti-islanding scheme of grid-connected inverter is a key function of standards compliance, unintentional islanding results in safety hazards, reliability, and many other issues. Therefore, many anti-islanding schemes have been researched, however, existing anti-islanding schemes show poor power quality and non-detection zone issues. Besides, most of them have problems which deteriorate performance of islanding detection under parallel-operation. Therefore, this paper proposes a new anti-islanding scheme that has both negligible power quality degradation, no non-detection zone and precise islanding detection under parallel-operation. Finally, both simulation and experimental results validate the proposed scheme.

  • PDF

고조파 주입에 의한 계통연계형 태양광발전시스템의 고립운전 검출 (Islanding Detection by Harmonic Current Injection Method for Utility Interactive Photovoltaic System)

  • 고재석;채영민;강병희;최규하
    • 전력전자학회논문지
    • /
    • 제8권2호
    • /
    • pp.199-210
    • /
    • 2003
  • 본 논문에서는 계통연계형 태양광발전시스템의 고립운전방지를 위한 새로운 고리운전 검출기법을 연구한다. 이를 위하여 계통연계형 태양광발전시스템 및 고립운전시의 특성에 대하여 기술하였다. 또한 고립운전의 검출특성을 향상시키기 위한 새로운 검출기법을 제시하고 해석하였으며 검출시험을 위한 부하조건 선정을 위한 부하임피던스 곡선을 해석적으로 유포하였다 ACSL 시뮬레이션 및 실험을 통하여 제시한 고립운전 검출기법 및 해석결과를 검증하였다.