Performance Verification of Anti-Islanding of Reactive Power Variation Method using Positive Feedback (정궤환을 이용한 무효전력 변동기반의 단독운전 방지 성능 검증)

  • Jo, Jongmin;Shin, Chang-Hoon;Cha, Hanju
    • The Transactions of the Korean Institute of Power Electronics
    • /
    • v.24 no.2
    • /
    • pp.105-110
    • /
    • 2019
  • This study proposed a reactive power variation (RPV) method equipped with positive feedback (PF) for detecting the islanding operation of distributed generation systems. The proposed RPV consists of the constant reactive power component and a certain reactive power term and uses the frequency deviation between the rated and the measured frequencies. The constant reactive power is injected from distributed generation system and power factor is to 0.9975 in grid-connected operation. PF is activated from generation of the frequency deviation and the injected reactive power is continuously increased due to PF when islanding occurs. Consequently, the increasing reactive power causes the point of common coupling frequency to deviate from the maximum/minimum threshold level. Performance of the proposed RPV is verified in a 1.7 kW T-type inverter, and the detection times are 53 and 150 ms.

Simulation of Non-Detection Zone using AFD Method applied to Utility-Connected Photovoltaic Systems for a Variety of Loads (다양한 부하에 따른 계통연계형 태양광발전 시스템에 적용된 AFD 기법의 단독운전 불검출영역 시뮬레이션)

  • Ko, Moon-Ju;Choy, Ick;Choi, Ju-Yeop;Won, Young-Jin
    • 전자공학회논문지 IE
    • /
    • v.43 no.2
    • /
    • pp.63-69
    • /
    • 2006
  • Islanding phenomenon of utility-connected PV power conditioning systems(PV PCS) can cause a variety of problems and must be prevented. If the real and reactive powers supplied by PV PCS are closely matched to those of load, islanding detection by passive methods becomes difficult. The active frequency drift(AFD) method, called the frequency bias method, enables islanding detection by forcing the frequency of the voltage in the islanding to drift up or down. In this paper, non-detection zone(NDZ) of AFD is analyzed for the islanding detection method of utility-connected PV PCS by simulation tool PSIM.

An Assessment on Voltage and Power Quality in Load Facility during the Islanding of Residential Fuel Cell System (가정용 연료전지 시스템의 단독운전 시 부하설비의 전압 및 전력품질 평가)

  • Park, Chan-Eom;Jung, Jin-Soo;Han, Woon-Ki;Lim, Hyun-Sung;Song, Young-Sang;Kim, Choon-Sam;Lim, Duk-Gyu
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.62 no.12
    • /
    • pp.1792-1797
    • /
    • 2013
  • Recently, due to the excessive use of fossil fuels, many studies about the fossil fuels such as solar and fuel cell energy source are progressing. Fuel cell system has high energy conversion efficiency. Also, fuel cell system is environmentally friendly system because the carbon emission is almost not occur. Therefore, the fuel cell system is considered as the core technology of in the fields of the future energy and environmental. Fuel cell system has an effect on distribution power system because another power source of other than large power plants. So, fuel cell system can be reason of power quality in the power system. In this paper, we constructed the system for an assessment on Islanding. The system is composed with power source, Impedance coordination load and linear load, fuel cell system. we are performed assessment on voltage and power quality in customer and the distributed power system during the Islanding of residential fuel cell system. In addition, no change in the impedance of power system, we made a islanding condition only using the actual load, As a variation of generation and load current under islanding, an analysis results based on assessment system showed that the power qualities of distribution system became more aggravation as effect of voltage sag and voltage swell phenomena.

A Study on Islandig Characteristics using Phase Angle Adjustment of Distributed Generation (배전계통연계 분산전원의 위상변화에 따른 고립운전 파라미터 특성)

  • Bang, Ji-Yoon;Kim, Hak-Man;Lee, Bock-Ku;Sim, Jae-Sun;Shin, Myong-Chul
    • Proceedings of the KIEE Conference
    • /
    • 2006.07a
    • /
    • pp.525-526
    • /
    • 2006
  • Recently, much research has been done and many improvements have been developed for islanding protection of distributed generation(DG). Anti-islanding protection for DG must be act very quickly to prevent equipment damage at the time of disconnection and for the safety of maintenance and repair personnel. DG-based detection methods have included both passive and active types, and now research has shifted towards new anti-islanding detection methods that make up for the defects of the previous types. Because differences occur between the utility grid and the DG when connecting and disconnecting depending on the phase difference, voltage, current, relative capacity of electric power, and system operation characteristics, voltage phase angle is an important consideration. In this paper, we simulated islanded operation characteristics comparing phase difference of DG and the connected utility grid, and analyzed various parameters (real power, reactive power, RMS voltage, RMS current, power factor angle, and frequency) by varying the DG's voltage phase angle. Using this information, we propose a suitable DG voltage phase angle for enhanced passive islanding detection techniques.

  • PDF

Single-Phase Inverter for Grid-Connected and Intentional Islanding Operations in Electric Utility Systems

  • Lidozzi, Alessandro;Lo Calzo, Giovanni;Solero, Luca;Crescimbini, Fabio
    • Journal of Power Electronics
    • /
    • v.16 no.2
    • /
    • pp.704-716
    • /
    • 2016
  • Small distributed generation units are usually connected to the main electric grid through single-phase voltage source inverters. Grid operating conditions such as voltage and frequency are not constant and can fluctuate within the range values established by international standards. Furthermore, the requirements in terms of power factor correction, total harmonic distortion, and reliability are getting tighter day by day. As a result, the implementation of reliable and efficient control algorithms, which are able to adjust their control parameters in response to changeable grid operating conditions, is essential. This paper investigates the configuration topology and control algorithm of a single-phase inverter with the purpose of achieving high performance in terms of efficiency as well as total harmonic distortion of the output current. Accordingly, a Second Order Generalized Integrator with a suitable Phase Locked Loop (SOGI-PLL) is the basis of the proposed current and voltage regulation. Some practical issues related to the control algorithm are addressed, and a solution for the control architecture is proposed, based on resonant controllers that are continuously tuned on the basis of the actual grid frequency. Further, intentional islanding operation is investigated and a possible procedure for switching from grid-tied to islanding operation and vice-versa is proposed.

Performance Improvement of an Anti-Islanding Algorithm using the Variation of Reactive Power with an Improved DFT Method (개선된 DFT을 이용한 무효전력변동 단독운전 검출기법의 성능 개선)

  • Kang, Duk-Hong;Choi, Dae-Keun;Lee, Kyo-Beum
    • The Transactions of the Korean Institute of Power Electronics
    • /
    • v.15 no.3
    • /
    • pp.179-187
    • /
    • 2010
  • This paper proposes a new anti-islanding method for single-phase grid-connected photovoltaic (PV) systems using Goertzel algorithm. The proposed scheme is based on inducing increases or decreases of frequencies of load voltage and current that is in the form of existences or periodical variations of the reactive power components. The frequency detection is needed to apply this power variation method to the grid-connected power converter. The proposed method is able to get a fast detection for anti-islanding without the effect of harmonics and noises. The simulation and experiment results validate the effectiveness of the proposed method.

Analysis of Active Islanding Dectetion Methods for a Single-phase Photovoltaic Power Conditioning Systems (단상 계통연계형 PCS의 단독운전 검출기법 비교 분석)

  • Jung Youngseok;So Jeonghun;Yu Gwonjong;Kang Gihwan;Choi Jaeho
    • Proceedings of the KIEE Conference
    • /
    • summer
    • /
    • pp.1477-1479
    • /
    • 2004
  • Increasing numbers of photovoltaic arrays are being connected to the power utility through the power conditioning systems (PCS). This has raised potential problems of network protection. If, due to the action of the PCS, the local network voltage and frequency remain within regulatory limits when the utility is disconnected, then islanding is said to occur. In this paper, the representative methods to prevent the islanding are described and a PSIM-based model and analysis of the reactive power variation (RPV) method are presented. A novel phase detector using the all-pass filter and digital phase locked loop (DPLL) is proposed especially for the single-phase PCS. Finally, this paper provides the simulation and experimental results with a single-phase 3kW prototype PCS. Islanding test method of IEEE Std. 929-2000 was performed for verification.

  • PDF

Design of Anti-Islanding Algorithm for Utility interactive Photovoltaic System (계통연계형 태양광 발전시스템에서 역충전방지 알고리즘 설계)

  • Gho, J.S.;Kim, H.S.;Choe, G.H.;Kim, H.S.;Lee, Y.J.;You, G.J.;Song, J.S.
    • Proceedings of the KIEE Conference
    • /
    • 1995.07a
    • /
    • pp.440-442
    • /
    • 1995
  • In a recently as renewable energy source photovoltaic(PV) system using solar energy has been very widely researched because of its pollution-free and infinity. Especially many researches are intensively focused on small scale utility interactive PV system which can use dead space and easily make power stabilized from unstable natural energy source. In this system one of the most important matters is islanding protection. Islanding phenomenon appears when power failure occurs. For the safety of utility interactive PV system must has the function of not only system protection but also detection of islanding. This paper describes parallel operating alghorithm using reactive power variation method and twin peak band pass filter. This alghorithm is verified useful by simulation.

  • PDF

Analysis of the Effect of the Grid-connected Photovoltaic System in Fault Case of Power System (전력계통 고장시 계통연계형 태양광발전시스템의 영향분석)

  • Park, Sung-Hun;Lee, Yong-Sik;Jeong, Sung-Won;Gim, Jae-Hyeon
    • Journal of the Korean Solar Energy Society
    • /
    • v.39 no.4
    • /
    • pp.69-77
    • /
    • 2019
  • Among the main functions of the grid-connected photovoltaic (PV) system, the anti-islanding operation function is a very important problem. Recently, due to the improvement in power generation efficiency and the maintenance advantages in PV system, the use of string inverter has increased so that the possibility of islanding operation has been raised. Generally, when a power system faults, the PV inverter must be disconnected from power system within 10 cycles by the anti-islanding operation function. However, in the real-time of power system, the output power of the PV system within 10cycles is effected. In this paper, we analyzed the effect of grid-connected PV system on power quality in a short time within 10 cycles on fault case of power system using the Matlab Simulink program.

A Study on Anti-Islanding Evaluation of Grid-Connected Power Conditioning System for Fuel Cell System in Parallel Operation (병렬 연결된 계통연계형 연료전지 전력변환장치의 단독운전방지 평가 연구)

  • Choi, Young-Joo;Oh, Gun-Woo;Kim, Min-Woo;Lee, Seung-Kuk;Park, Ga-Woo
    • Journal of the Korean Institute of Gas
    • /
    • v.22 no.5
    • /
    • pp.124-132
    • /
    • 2018
  • The supply of renewable energy has become more vigorous due to Paris Agreement. In Korea, supply policies of renewable energy is being promoted with priority given to public buildings, so, the supply of fuel cell system that are relatively easy to install in buildings is expected to expand, so it is important that study on anti-islanding evaluation of grid-connected power conditioning system(PCS) for fuel cell. In this study, we consider that KGS AB934 PC53 in domestic certification standard of PCS for fuel cell correspond with abroad standard and analyze anti-islanding evaluation that important safety performance when connected grid. Additionally, we constructed a prototype for anti-islanding evaluation of PCS for fuel cell connected in parallel and carried out the demonstration evaluation, so, we have conducted ways that ensure safety performance in accordance with the circumstances where several fuel cell systems are installed.