• Title/Summary/Keyword: Islanding Protection

Search Result 33, Processing Time 0.033 seconds

Development of a New Islanding Detection Method for Distributed Resources (분산 전원의 고립 운전 검출 기법의 개발)

  • Jang, Seong-Il;Kim, Gwang-Ho
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.50 no.11
    • /
    • pp.506-513
    • /
    • 2001
  • The islanding detection for distributed resources (DR) becomes an important and emerging issue in power system protection since the distributed generator installations are rapidly increasing and most of the installed systems are interconnected with distribution network. In order to avoid the negative impacts from islanding operations of DR on protection, operation and management of distribution system, it is necessary to effectively detect the islanding operations of DR and rapidly disconnect it from distribution network. Generally, it is difficult to detect islanding operation by monitoring only one system parameter This paper presents a new logic based islanding detection method for distributed resources(DR) which are interconnected with distribution network. The proposed method detects the islanding operation by monitoring four system parameter: voltage variation, phase displacement, frequency variation, and the variation of total harmonic distortion(THD) of current; therefore, it effectively detects island operation of DR unit operating in parallel with the distribution network. We also verified the efficiency of the proposed algorithm using the radial distribution network of IEEE 34 bus model.

  • PDF

Development of a Islanding Protection Algorithm for Distributed Resources (분산 전원의 고립 운전 진단 알고리즘 개발)

  • Jang, S.I.;Park, J.Y.;Kim, K.H.
    • Proceedings of the KIEE Conference
    • /
    • 2001.07b
    • /
    • pp.1287-1289
    • /
    • 2001
  • This paper presents the logic based islanding protection algorithm for distributed resources(DR) which are interconnected with distribution network. Due to the negative impacts from islanding operations of DR on protection, operation and management of distribution system, it is necessary to effectively detect the islanding operations of DR and disconnect it from distribution network rapidly. Generally, it is difficult to detect islanding operation by monitoring only one system parameter. The proposed islanding protection algorithm utilizes multi-criteria, voltage variation, phase displacement frequency variation, the variation of total harmonic distortion(THD) of current; therefore it effectively detects island operation of DR unit. We also verified the efficiency of the proposed algorithm using the radial distribution network of IEEE 34 bus model.

  • PDF

Islanding Detection Method of Embedded Generator connected to Power Distribution System (분산형전원이 도입된 배전계통에 대한 ISLANDING DETECTION METHOD)

  • Hwang, J.S.;Kim, J.E.
    • Proceedings of the KIEE Conference
    • /
    • 2000.07a
    • /
    • pp.522-524
    • /
    • 2000
  • The installation of small sized Embedded Generator(EG) in parallel with the utility supply was required several technical complications for protection of the system. One of the most important protection is to provide protection against islanding and out of synchronism reclosing with the utility source. This paper explains several current methods of detecting 'Loss Of Mains'(LOM). But they have not proved completely dependable, in particular when the islanded load's capacity matches that of the EG. A new loss of mains protection algorithm is presented in this paper which based on measurement of the reactive power and node voltage for detecting the islanding condition even though the EG operate in the capacity.

  • PDF

A Control and Protection Model for the Distributed Generation and Energy Storage Systems in Microgrids

  • Ballal, Makarand Sudhakar;Bhadane, Kishor V.;Moharil, Ravindra M.;Suryawanshi, Hiralal M.
    • Journal of Power Electronics
    • /
    • v.16 no.2
    • /
    • pp.748-759
    • /
    • 2016
  • The microgrid concept is a promising approach for injecting clean, renewable, and reliable electricity into power systems. It can operate in both the grid-connected and the islanding mode. This paper addresses the two main challenges associated with the operation of a microgrid i.e. control and protection. A control strategy for inverter based distributed generation (DG) and an energy storage system (ESS) are proposed to control both the voltage and frequency during islanding operation. The protection scheme is proposed to protect the lines, DG and ESS. Further, the control scheme and the protection scheme are coordinated to avoid nuisance tripping of the DG, ESS and loads. The feasibility of the proposed method is verified by simulation and experimental results.

Detection Performance and THD Analysis of Active Frequency Drift for Anti-Islanding (단독운전 방지를 위한 능동적 주파수 변환 기법의 검출 성능 및 THD 분석)

  • Jo, Yeong-Min;Choi, Ju-Yeop;Song, Seung-Ho;Choy, Ick;Lee, Young-Kwoun
    • Journal of the Korean Solar Energy Society
    • /
    • v.35 no.2
    • /
    • pp.11-19
    • /
    • 2015
  • Islanding is a phenomenon that EPS(Electric Power System) is continuously energized by PV PCS(Photovoltaic Power Conditioning System) even when EPS is isolated from the grid. Unintentional islanding will result in safety hazard, power quality degradation and many other issues. So, islanding protection of grid-connected PV PCS is a key function for standards compliance. Nowadays, many anti-islanding schemes are researched. But existing anti-islanding schemes used in PV PCS have power quality degradation and non-detection zone issues. This paper analyses not only detection performance of existed anti-islanding schemes using active frequency drift but also THD of PCS output current according to each value disturbance for anti-islanding. In addition, the lowest value of disturbance in each scheme was tabulated under guarantee of anti-islanding condition.

Islanding Detection for a Micro-Grid based on the Instantaneous Active and Reactive Powers in the Time Domain (시간영역에서 순시 유효/무효전력을 이용한 마이크로그리드의 단독운전 판단)

  • Lee, Young-Gui;Kim, Yeon-Hee;Zheng, Tai-Ying;Kim, Tae-Hyun;Kang, Yong-Cheol
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.61 no.1
    • /
    • pp.22-27
    • /
    • 2012
  • Correct and fast detection of a micro-grid (MG) islanding is essential to the MG since operation, control and protection of the MG depend on an operating mode i.e., an interconnected mode or an islanding mode. When islanding occurs, the frequency of the point of common coupling (PCC) is not the nominal frequency during the transient state owing to the frequency rise or drop of generators in the MG. Thus, the active and reactive power calculated by the frequency domain based method such as Fourier Transform might contain some errors. This paper proposes an islanding detection algorithm for the MG based on the instantaneous active and reactive powers delivered to the dedicated line in the time domain. During the islanding mode, the instantaneous active and reactive powers delivered to the dedicated line are constants, which depend on the voltage of the PCC and the impedance of the dedicated line. In this paper, the instantaneous active and reactive powers are calculated in the time domain and used to detect islanding. The performance of the proposed algorithm is verified under various scenarios including islanding conditions, fault conditions and load variation using the PSCAD/EMTDC simulator. The results indicate that the algorithm successfully detects islanding for the MG.

Islanding Detection for Grid-connected PV Inverter under Parallel Operation (계통연계형 태양광 인버터 병렬운전 상황에서의 단독운전 검출)

  • Jo, Yeong-Min;Kim, Dong-Gyun;Song, Seung-Ho;Choy, Ick;Lee, Young-Kwoun;Cho, Sang-Yoon;Choi, Ju-Yeop
    • The Transactions of the Korean Institute of Power Electronics
    • /
    • v.21 no.4
    • /
    • pp.283-289
    • /
    • 2016
  • Islanding protection of a grid-connected photovoltaic (PV) inverter is a key function for standards compliance. Unintentional islanding results in safety hazards, reliability, and many other issues. Therefore, many anti-islanding schemes have been examined. However, existing anti-islanding schemes have poor power quality and non-detection zone issues. Moreover, most schemes have problems that deteriorate the performance of islanding detection under parallel operation. Therefore, this paper proposes a novel anti-islanding scheme that has negligible power quality degradation and has no non-detection zone and islanding detection under a parallel operation. Both simulation and experimental results validate the proposed scheme.

Performance Analysis of Anti-islanding Function for Grid-connected PV Inverter Systems under Parallel Connections (병렬운전하는 계통연계형 태양광 발전용 인버터의 단독운전 검출 성능 분석)

  • Jung, Young-Seok;Yu, Byung-Gyu;Kang, Gi-Hwa
    • Journal of the Korean Solar Energy Society
    • /
    • v.33 no.5
    • /
    • pp.34-40
    • /
    • 2013
  • Islanding phenomenon of photovoltaic system is undesirable because it leads to a safety hazard to utility service personnel and may cause damage to power generation and power supply facilities as a result of unsynchronized re-closure. Anti-islanding protection is an important technical requirement for grid-connected PV system. Until now, various anti-islanding methods for detecting and preventing islanding of photovoltaic and other distributed generations have been proposed. Most of them are focusing on the anti-islanding performance of single PV system according to the related international and domestic standard test procedures. There are few studies on the islanding phenomenon for multiple photovoltaic operation in parallel. This paper presents performance analysis of anti-islanding function for grid-connected PV inverter systems when several PV inverters are connected in parallel.

A Study of Islanding Detection of Grid-connected Three-phase Photovoltaic Power Conditioning System

  • Jung Y.S.;Yu G.J.;Choi J.Y.;Choi J.H.
    • Proceedings of the KIPE Conference
    • /
    • 2003.07b
    • /
    • pp.761-764
    • /
    • 2003
  • Islanding phenomenon of a grid-connected photovoltaic (PV) power conditioning system (PCS) is said to occur if the PCS continues to power a section of the utility system after that section has been disconnected from the utility source. Since islanding creates hazards for personnel and equipment, PCSs are required to detect and prevent Et. In this paper, several islanding detection methods (IDMs) and reactive power variation method are described. Islanding test results for 9kW PCS are presented for verification.

  • PDF

A Simulation for Anti-islanding Method in PV-AF System and Existing Anti-islanding Method (PV-AF시스템에서 단독운전 방지기법 및 기존 단독운전 방지기법의 시뮬레이션 해석 및 비교)

  • Kim, Gyeong-Hun;Seo, Hyo-Ryong;Lee, Soek-Ju;Park, Min-Won;Yu, In-Keun;Jeon, Jin-Hong;Kim, Seul-Gi;An, Jong-Bo
    • Proceedings of the KIEE Conference
    • /
    • 2007.07a
    • /
    • pp.206-207
    • /
    • 2007
  • Islanding is the electrical phenomenon in a part of a power network disconnected from the utility, where the loads are entirely supplied by PV systems, and where the voltage and frequency are maintained around nominal values. But islanding may result in power-quality issues, interference to grid-protection devices, equipment damage, and even personnel safety hazards[4]. Therefore, islanding must be detected and stopped. The existing anti-islanding methods have NDZ(None-detection Zone) or power quality degradation. But PV-AF power generation system has the function of not only shunt active filter but also anti-islanding method without NDZ. In this paper, It is proved that PV-AF system has originally the function of anti-islanding without not only NDZ and but current distortion

  • PDF