• Title/Summary/Keyword: Line-Interactive

Search Result 211, Processing Time 0.026 seconds

A Study on the Line-Interactive UPS with Power Factor correction (Line - Interactive UPS의 역률 개선 방안에 관한 연구)

  • Jang Hoon;Lee Woo-Cheol;Lee Taeck-Kie;Hyun Dong-Seok
    • Proceedings of the KIPE Conference
    • /
    • 2001.12a
    • /
    • pp.93-96
    • /
    • 2001
  • This paper proposed on the Line-Interactive UPS with power factor correction. The paper Line-Interactive UPS topology with its advantages is reviewed. Next introduces Line -Interactive UPS of the series active compensator. The series active compensator controls input currents and power factor.

  • PDF

Voltage Control in a Novel Three-Phase Line Interactive UPS System with Parallel-Series Active Power Line Conditioning Capabilities using AC Line Reactor (AC 라인 리액터와 병렬 및 직렬 능동필터를 가지는 새로운 3상 Line-Interactive UPS 시스뎀의 전압제어)

  • Ji, Jun-Keun
    • Journal of the Korea Academia-Industrial cooperation Society
    • /
    • v.7 no.6
    • /
    • pp.1072-1077
    • /
    • 2006
  • In this paper a novel 3-phase line interactive UPS(Uninterruptible Power Supply) system with parallel-series active power-line conditioning capability using AC line reactor and two four-leg PWM VSCs(Voltage Source Converters) is proposed. And the strategy of voltage control in proposed UPS system is explained. The objective of voltage control in parallel(shunt) and series PWM VSC of proposed UPS system is to guarantee satisfactory characteristics in steady state and transient state.

  • PDF

Voltage Control Strategy of new 3-phase Line-Interactive UPS System using AC Line Reactor and Parallel-Serise Active Filter (AC 라인 리액터와 병렬 및 직렬 능동필터를 가지는 새로운 3상 Line-Interactive UPS 시스템의 전압제어 방식)

  • Ji, Jun-Keun
    • Proceedings of the KIPE Conference
    • /
    • 2005.07a
    • /
    • pp.201-203
    • /
    • 2005
  • A new 3-phase line-interactive UPS(Uninterruptible Power Supply) system with parallel-series active power-line conditioning capability using AC line reactor and two four-leg PWM VSCs(Voltage Source Converters) was introduced recently, In this paper, the strategy of voltage control in suggested UPS system is explained. The objective of proposed voltage controllers in parallel(shunt) and series PWM VSC is to guarantee satisfactory characteristics in steady state and transient state.

  • PDF

Voltage Control Strategy of new 3-phase Line-Interactive UPS System using AC Line Reactor and Parallel-Series Active Filter (AC 라인 리액터와 병렬 및 직렬 능동필터를 가지는 새로운 3상 Line-Interactive UPS 시스템의 전압제어 방식)

  • Ji, Jun-Keun;Kim, Jang-Hwan;Sul, Seung-Ki
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.56 no.3
    • /
    • pp.538-546
    • /
    • 2007
  • A new 3-phase line-interactive UPS(Uninterruptible Power Supply) system with parallel-series active power-line conditioning capability using AC line reactor and two four-leg PWM VSCs(Voltage Source Converters) was introduced recently. In this paper, the strategy of voltage control in suggested UPS system is explained. The objective of proposed voltage controllers in parallel(shunt) and series PWM VSC is to guarantee satisfactory characteristics in steady state and transient state. Therefore the experimental results to prototype UPS system having power rating of 60kVA is shown to prove the verification of voltage control strategy.

Line-Interactive UPS for Low-Voltage Microgrids

  • Zhang, Ping;Cai, Huanyu;Zhao, Hengyang;Shi, Jianjiang;He, Xiangning
    • Journal of Power Electronics
    • /
    • v.15 no.6
    • /
    • pp.1628-1639
    • /
    • 2015
  • Line-interactive uninterruptible power supply (UPS) systems are good candidates for providing energy storage within a microgrid. In this paper, a control scheme for a line-interactive UPS system applied in a low-voltage microgrid is presented. It is based on the Q-w and P-E droop control to achieve a seamless transition between grid-connected and stand-alone operation modes. Moreover, a new model for designing the controllers is built in the dq-frame based on the instantaneous power definition. The new-built model takes into account the dynamic performance of the output impedance of the inverter in the dq-frame and can be evaluated in the time domain. Compared to the traditional model based on the instantaneous power definition, the new-built model is more accurate to describe the dynamic performance of the system. Simulation and experimental results obtained with a microgrid consisting of two 40-kW line-interactive UPS systems are given to validate the control strategy of the line-active UPS system and the accuracy of the new-built model.

Analysis of Output Characteristics and Design of LC Filter for Line-Interactive 3-Phase APF (3상 라인인터액티브형 능동전력필터 시스템을 위한 LC필터 출력특성 해석 및 설계)

  • 김응진
    • Proceedings of the KIPE Conference
    • /
    • 2000.07a
    • /
    • pp.127-132
    • /
    • 2000
  • This paper describes a 3-phase Line-Interactive APF system and analyzes its operating characteristics considering LC Filter output characteristics. Topology of APF is similar to that of Off-Line UPS in the point of parallelly operating inverter system. So it is possible to be multi-functioned active compensating system according to power condition. Likewise this actively operating system from APF to UPS and vice versa is often to be called Line-Interactive system. And more than that Line-Interactive system needs precise design of LC filter on converter output side to make this system fully operate in both APF and UPS modes. The problem in this point is how to design LC Filter to be contented with two different system characteristics so this paper analyzes this problem and proposes its design procedures. Then suggested filter design is verified to be contented by the simulations and experimental results

  • PDF

Three-Phase Line-Interactive Dynamic Voltage Restorer with a New Sag Detection Algorithm

  • Jeong, Jong-Kyou;Lee, Ji-Heon;Han, Byung-Moon
    • Journal of Power Electronics
    • /
    • v.10 no.2
    • /
    • pp.203-209
    • /
    • 2010
  • This paper describes the development of a three-phase line-interactive DVR with a new sag detection algorithm. The developed detection algorithm has a hybrid structure composed of an instantaneous detector and RMS-variation detectors. The source voltage passes through the sliding-window DFT and RMS calculator, and the instantaneous sag detector. If an instantaneous sag is detected, the RMS variation detector-1 is selected to calculate the RMS variation. The RMS variation detector-2 is selected when the instantaneous sag occurs under the operation of the RMS variation detector-1. The feasibility of the proposed algorithm is verified through computer simulations and experimental work with a prototype of a line-interactive DVR with a 3kVA rating. The line-interactive DVR with the proposed algorithm can compensate for an input voltage sag or an interruption within a 2ms delay. The developed DVR can effectively compensate for a voltage sag or interruption in sensitive loads, such as computers, communications equipment, and automation equipment.

Development of control algorithm for line interactive UPS using dSPACE (dSPACE를 사용한 Line Interactive UPS의 제어알고리즘 개발)

  • Yu, Tae-Sik;Kim, Du-Hwan;Kim, Hyo-Sung
    • Proceedings of the KIPE Conference
    • /
    • 2010.07a
    • /
    • pp.472-473
    • /
    • 2010
  • 1kW~10kW급의 UPS 토폴로지로서 Line Interactive UPS가 많이 사용되고 있다. Line Interactive UPS는 Single Stage의 AC/DC 변환기 구조를 갖으며 정상상태에서는 적은 전류로 DC측 에너지 저장장치의 충전상태를 유지만 하면 되므로 운전 효율이 높고 가격이 저렴하다. 그러나 고성능의 전류/전압 제어기술이 요구되므로 제품화하는데 어려움이 많다. 본 논문에서는 MATLAB Simulink와 연동하여 간단히 다양한 제어알고리즘을 구현 할 수 있는 dSPACE 장비를 사용하여 실험 장치를 구축하고 Single Stage UPS의 제어알고리즘을 구현하였다.

  • PDF

A Study on Interactive Multimedia Contents Service System (인터랙티브 멀티미디어 콘텐츠 서비스 시스템)

  • 이준희;이재영;류승렬;조용환
    • The Journal of the Korea Contents Association
    • /
    • v.2 no.3
    • /
    • pp.31-40
    • /
    • 2002
  • In this thesis, the interactive multimedia contents service system is proposed. The interactive multimedia contents service system which added the on-line merit on the off-line merit of CD-ROM title can transfer messages among users and update contents immediately. The Interactive multimedia contents service system which Integrated the CD-ROM title and Internet sonics is possible to use in on-line / off-line. The proposed system more improved the fault of CD-ROM title in the conventional main media, the search environment by using mutual correlation of the utilization and method of the Internet CD-ROM title.

  • PDF

A Study of Line-Interactive UPS with Voltage Compensator (Line-Interactive 전압보상기에 관한 연구)

  • Woo Sung-Min;Kang Dae-Wook;Lee Woo-Cheol;Choi Chang-Ho;Hyun Dong-Seok
    • Proceedings of the KIPE Conference
    • /
    • 2001.07a
    • /
    • pp.487-490
    • /
    • 2001
  • Power Quality and Reliability are becoming important issues for critical and sensitive loads. This paper describes the Line Interactive UPS with the function of Voltage Compensator that is 'Line interactive Dynamic Voltage Restorer(LIDVR). The main purpose of a LIDVR is to compensate for voltage sag(dip), outage and overvoltage. The overall system consists of three controller 1) current controller with prediction 2) voltage controller and 3) proposed variable DC LINK controller. The variable DC LINK control technique using the LIDVR protects DC LINK from overflowing the input current. The simulation results are depicted in this paper to show the effect of this proposed system.

  • PDF