• Title/Summary/Keyword: MOV

Search Result 89, Processing Time 0.029 seconds

Protection of MOV Thermal Runaway and Safety Improvement of SPD using Built-in Instantaneous Trip Device (내장 순시 트립장치를 이용한 MOV의 열폭주 보호와 SPD의 안전성 개선)

  • Kim, Ju-Chul;Jeon, Joo-Sool;Ki, Che-Ouk;Choi, Gyung-Ray;Lee, Sang-Joong
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.25 no.2
    • /
    • pp.120-125
    • /
    • 2011
  • SPDs are increasingly being used against lightning and switching surge according to the applicable revised standard and equipotential grounding system. SPDs are equipped usually with a MOV voltage regulating element. The MOV, however, always is exposed to the danger of thermal runaway resulting from inrushing temporary overvoltage and deterioration. In this paper, the authors made two prototype SPDs built-in Instantaneous trip device and analyzed their limiting voltage through test of the MOV breakdown. As the result of the analysis, the SPDs built-in Instantaneous trip device was proven to be effective for protecting MOV against thermal runaway and Instantaneous trip device react for limiting voltage is considered that is applicable to SPD.

A study on the degradation of the AC stressed MOV by using of the DLTS technique (DLTS기법에 의한 MOV소자의 교류과전경시 변화특성에 관한 연구)

  • 이동희
    • Electrical & Electronic Materials
    • /
    • v.9 no.7
    • /
    • pp.719-726
    • /
    • 1996
  • DLTS measurements were performed to study the annealing induced changes of the trap centers in MOV and to shed more light on the stability mechanism of the MOV. Two electron traps, Ec-0.26[eV] and Ec-(O.2-0.3)[eV], were observed in the unannealed samples in large quantities(7-9 X 1014[CM 3]), whereas the three electron traps Ec-0.17 [eV], Ec-0.26[eV] and Ec-(O.2-0.3)[eV] were observed far less in the annealed samples. The minima in the Ec-0.26[eV] trap density, coupled with the presented results that unannealed devices are unstable whereas 600.deg. C annealed devices are most stable, suggests that the instability of the MOV under long term electrical stressing is related to the Ec-0.26[eV] trap. This results support that the ion migration model for the device instability where the Ec-0.26[eV] defects may be the interstitial zinc or the migrating ions. The interstitial zinc originated as a result of the nonstoichiometric nature of ZnO might cause the degradation of the I-V characteristics of the MOV with long term electrical stressing.

  • PDF

Failure Rate Estimation of MOV for Condition Monitoring of Surge Protective Devices (서지보호기의 상태 감시를 위한 MOV의 고장률 예측)

  • Kim, Dong Jin;Kim, Young Sun;Park, Jae Jun;Lee, Ki Sik
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.62 no.9
    • /
    • pp.1302-1307
    • /
    • 2013
  • MOV(Metal Oxide Varistor) is the most important part of SPD(Surge Protective Device) which can protect electric facilities from an impulse current such as a lightning. So far, the fault of MOVs have decided only by surge count without considering magnitude of surge current and an amount of input energy. This paper proposed the fault prediction algorithm for the MOV using look up table made by surge count and input current data which have non-linear characteristics for input current and are estimated by high voltage experimental results. Proposed algorithm was proved by experiment on verification at a high voltage laboratory.

A Study for the Improvement Method of Flexible Wedge Gate Valve Operation Capability (Flexible Wedge Gate 밸브의 운전 성능향상 방안에 관한 연구)

  • Kim, Dae-Woong;Lee, Do-Hwan;Kang, Sin-Chul;Kim, In-Whan;Park, Sung-Keun
    • Proceedings of the KSME Conference
    • /
    • 2001.06a
    • /
    • pp.644-651
    • /
    • 2001
  • The purpose of this study is to develop the improvement method of MOV(Motor Operated Valve) operability without major modification or change of MOV which needs a great expense and manpower. We studied valve stem lubrication, stem packing thrust and actuator control switch which could give an major effect to MOV operability, and found the some consequences. First, the stem/stem-nut friction coefficient and stem factor is significantly effected by stem lubrication state. Second, the measured packing thrust value is appeared higer than the design value for tested valves and the preparation of optimal value selection criteria is needed. Finally, optimization of MOV control switch is another major factor for MOV operability and structual integrity.

  • PDF

Study on the Condition and Performance Monitoring Technology of Motor-Operated Valve (모터구동밸브의 고장 및 성능감시 기술에 대한 연구)

  • Kwon, Seok-Jun;Sung, Key-Yong;Lee, Heung-Ho
    • Proceedings of the KIEE Conference
    • /
    • 2003.07d
    • /
    • pp.2778-2780
    • /
    • 2003
  • 본 논문에서는 모터구동밸브의 모터 토크를 전기적인 신호만으로 예측하고, 계산된 모터 토크신호를 주파수영역에서 분석하여 Motor Speed, Slip pole 주파수, WGTM(Worm Gear Tooth Mesh)과 같은 MOV의 기계적 특성 성분을 확인하였다. 또한 모의 고장 실험을 통해 MOV 기계적 고장이 이 특성성분의 변화로 나타나는 것을 확인하므로, 이 정보를 MOV의 고장 감시 기술로 적용할 수 있다. 아울러 전기 신호를 이용하여 Condition Monitoring 기법을 개발하고, MOV 고장 감시 Software를 개발하므로, MOV 주기적 확인에 대비한 규제검증 기술 및 정보를 제공하고자 한다.

  • PDF

Thermal Runaway Prevention of MOV and Safety Improvement of Power Line System and Internal Electronic Device Circuit Using a Phosphorous Switching Module (인청동 스위칭 모듈을 이용한 전력계통 및 전자기기 내부회로의 MOV 열폭주 방지와 안전성 개선)

  • Kim, Ju-Chul;Choi, Gyung-Ray;Lee, Sang-Joong
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.25 no.9
    • /
    • pp.75-79
    • /
    • 2011
  • The MOV(Metal Oxide Varistor), a voltage limiting element, has been installed in the SPD(Surge Protective Device) or inside the internal circuit of an electronic appliance for protection of the electric power system and electronic device against electrical surge. Such an MOV is exposed, however, to the risk of the thermal runaway resulting from excessive voltage and deterioration. In this paper, a reciprocal action has been tested and analyzed using a phosphorus bronze switching module and the low-temperature solder. And a short current break characteristic test linked with the circuit breaker has been performed to limit the inrush current when the MOV breaks down. It has been proven that the phosphorus bronze switching module installed inside the internal circuit can improve the safety of the power line system and the electronic device.

Categorization of Motor Operated Valve Safety Significance for Its Periodic Safety Verification (모터구동 밸브 주기적 안전성 확인을 위한 중요도 분류)

  • Sung, Tae-Young;Kim, Kil-Yoo;Kang, Dae-Il
    • Journal of the Korean Society of Safety
    • /
    • v.17 no.2
    • /
    • pp.92-99
    • /
    • 2002
  • Safety-related motor operated valve(MOV) safety significance for Ulchin Unit 3 was categorized. The safety evaluation of MOV of domestic nuclear power plants affects the generic data used for the quantification of MOV common cause failure(CCF) events in Ulchin Units 3&4 PSA. Therefore, in this paper, MGL(multiple greek letter)parameter ${\beta}$, used for the evaluation of MOV CCF probabilities in Ulchin Units 3&4 probabilistic safety assessment(PSA), was re-estimated and the MOV safety significance was categorized. The re-estimation results of MGL parameter show that the value of(is decreased by 30% compared with the current value used in Ulchin Unit 3&4 PSA. The categorization results of MOV safety significance using the changed value of MGL parameter(show that the number of HSSCs(high safety significant components) is decreased by 54.5% compared with those using the current value of it used in Ulchin Units 3&4 PSA.

Experimental Study on Temporary Overvoltage Characteristics of MOV Based Surge Protective Devices (MOV 기반 서지보호기의 일시과전압 특성에 대한 실험적 연구)

  • Shim, Hae-Sup;Jeon, Tae-Hyun
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.24 no.1
    • /
    • pp.71-77
    • /
    • 2010
  • Protection against lightning surge is an essential part of almost any electrical and electronic equipment today. Metal Oxide Varistor(MOV) is the single most important component in the overwhelming majority of the Surge Protective Devices(SPD) designated to provide such protection. In this paperr various types of MOV based SPD are inspected and experiments are carried out on the side effects of the low Measured Limiting Voltage(MLV) characteristics. Experiment results show that a lower MLV could cause a higher Temporary Overvoltage(TOV)-induced SPD failure rate in the field, and SPD are more likely to be victims rather than protectors in a TOV scenario. This means that from a safety perspective, the SPD should be specified with higher TOV withstand capability(UT) and faster SPD disconnector.

System Design and Implementation for New Move Picture Solution EZ-MOV Using FLV (FLV를 이용한 새로운 동명상 솔루션 EZ-MOV 대한 시스템 설계 및 구현)

  • Kwon, O-Byoung;Shin, Hyun-Cheul
    • Convergence Security Journal
    • /
    • v.9 no.2
    • /
    • pp.79-84
    • /
    • 2009
  • Recently, Move Picture Files have the same file format and a compression technique as Window Media Video form. but Moving Pictures using file format and a compression technique have question about Motion blur and compressibility. In this paper, we design and Implement for new Move Picture Solution EZ-MOV using FLV different from developed FLV(Flash Video) in the Macromedia company. EZ-MOV have advantages as follow. first, FLV player is able to compact disk access time and DRM (Digital Rights Management) with a built-in self and unable to an illegal video recording, second, whenever WMV formal file encoded FLV are able to lossless compression to fifty percent, third, FLV is able to Moving Picture streaming no buffering. fourth, FLV file is able streaming service no streaming server. fifth, FLV file is able to streaming service keep pace with download and streaming. sixth, FLV file is able to full duplex service.

  • PDF

Design and Fabrication of a Surge Generator with Coupling/Decoupling Networks (커플링/디커플링 네트워크 내장 서지발생장치의 설계 및 제작)

  • Kim, Nam-Hoon;Kang, Tae-Ho;Shin, Han-Sin;Kil, Gyung-Suk
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.33 no.2
    • /
    • pp.130-134
    • /
    • 2020
  • Metal oxide varistors (MOVs) protect circuits and devices from transient overvoltages in electric power systems. However, a MOV continuously deteriorates owing to manufacturing defects or repetitive protective operations from transient overvoltages. A deteriorated MOV may result in a short circuit or a line-ground accident. Previous studies focused on the analysis of deterioration mechanisms and condition diagnosis techniques for MOVs owing to their recent growth of use. An accelerated deterioration experiment under the same conditions in which a MOV operates is essential. In this study, we designed and fabricated a surge generator that can apply a surge current to a MOV connected to AC mains. The coupling network operates at a low impedance against the surge current from the surge generator and transfers the surge current to the MOV under test. It also acts as a high impedance against AC mains for the AC voltage not to be applied to the surge generator. The decoupling network operates at a high impedance against the surge current and blocks the surge current from AC mains. It also acts as a low impedance against AC mains for the AC voltage to be applied to the MOV under test. The prototype surge generator can apply the 8/20 us up to 15 kA on AC voltages in the approximate range of 110~450 V, and it fully operates on a LabVIEW-based program.