• Title/Summary/Keyword: Multiple ESS

Search Result 26, Processing Time 0.029 seconds

Power Allocation Method for Multiple ESS Control Considering SOC Balancing in Microgrids (마이크로그리드에서 SOC균형을 고려한 ESS의 충·방전 전력배분 방법)

  • Lee, Sang-Wook;Park, Juneho
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.66 no.2
    • /
    • pp.292-299
    • /
    • 2017
  • In this paper, multiple ESS(Energy Storage System) control strategy for microgrids is presented. Installation of ESS becomes mandatory when microgrids are used to supply high quality power to the loads. The one of main functions of the ESS is to maintain power balance. However ESS has limitation of its capacity and instantaneous injecting power. Power allocation method based on SOC(State Of Charge) of each ESS is proposed. P-Q control is employed as the basic control strategy for the distributed ESSs. By using the proposed method, the coefficients in the conventional P-Q control method are modified. The ESSs with higher SOC inject more active power, while those with lower SOC inject less, leading to more balanced SOC levels among the ESSs. The proposed method is demonstrated by simulation using PSCAD/EMTDC.

A study on the Multiple ESS operation to consider the Battery Life Cycle Cost. (배터리 수명비용을 고려한 Multiple ESS 운영에 관한 연구)

  • Shin, Jun-Hyun;Jo, Ho-Jun;Kim, Sung-Yul;Mun, Sang-Geun;Kim, Jin-O
    • Proceedings of the KIEE Conference
    • /
    • 2015.07a
    • /
    • pp.627-628
    • /
    • 2015
  • 최근 전력계통은 에너지저장장치(ESS: Energy Storage System)의 도입이 확산되고 있는데, 신재생에너지 출력완화, 송전혼잡 해소, 주파수조정, 전압변동, 에너지차익거래 등의 목적으로 사용되고 있다. 이렇듯 각 ESS는 각기 다른 목적으로 사용하고 있는데, 현재 전력계통 ESS 운영은 각 목적별 ESS를 독립적으로 사용하고 있어, ESS를 효율적으로 사용하지 못하여 설치비용 대비 경제성이 떨어지고 있는 실정이다. 본 논문은 이러한 ESS의 경제성에 관한 문제점을 해결하고자 Multiple ESS상태에서 배터리 수명 비용을 줄이고, 배터리를 효율적으로 사용할 수 있는 방법을 제안하고자 한다. 사례연구에서는 각기 다른 목적으로 사용되고 있는 ESS를 독립적으로 사용하는 경우와 배터리 수명비용을 바탕으로 전력을 분배한 경우의 비용을 분석해 보았다.

  • PDF

Effect Analysis for Frequency Recovery of 524 MW Energy Storage System for Frequency Regulation by Simulator

  • Lim, Geon-Pyo;Choi, Yo-Han;Park, Chan-Wook;Kim, Soo-Yeol;Chang, Byung-Hoon;Labios, Remund
    • KEPCO Journal on Electric Power and Energy
    • /
    • v.2 no.2
    • /
    • pp.227-232
    • /
    • 2016
  • To test the effectiveness of using an energy storage system for frequency regulation, the Energy New Business Laboratory at KEPCO Research Institute installed a 4 MW energy storage system (ESS) demonstration facility at the Jocheon Substation on Jeju Island. And after the successful completion of demonstration operations, a total of 52 MW ESS for frequency regulation was installed in Seo-Anseong (28 MW, governor-free control) and in Shin-Yongin (24 MW, automatic generation control). The control system used in these two sites was based on the control system developed for the 4 MW ESS demonstration facility. KEPCO recently finished the construction of 184 MW ESS for frequency regulation in 8 locations, (e.g. Shin-Gimjae substation, Shin-Gaeryong substation, etc.) and they are currently being tested for automatic operation. KEPCO plans to construct additional ESS facilities (up to a total of about 500 MW for frequency regulation by 2017), thus, various operational tests would first have to be conducted. The high-speed characteristic of ESS can negatively impact the power system in case the 500 MW ESS is not properly operated. At this stage we need to verify how effectively the 500 MW ESS can regulate frequency. In this paper, the effect of using ESS for frequency regulation on the power system of Korea was studied. Simulations were conducted to determine the effect of using a 524 MW ESS for frequency regulation. Models of the power grid and the ESS were developed to verify the performance of the operation system and its control system. When a high capacity power plant is tripped, a 24 MW ESS supplies power automatically and 4 units of 125MW ESS supply power manually. This study only focuses on transient state analysis. It was verified that 500 MW ESS can regulate system frequency faster and more effectively than conventional power plants. Also, it was verified that time-delayed high speed operations of multiple ESS facilities do not negatively impact power system operations. It is recommended that further testing be conducted for a fleet of multiple ESSs with different capacities distributed over multiple substations (e.g. 16, 24, 28, and 48 MW ESS distributed across 20 substations) because each ESS measures frequency individually. The operation of one ESS facility will differ from the other ESSs within the fleet, and may negatively impact the performance of the others. The following are also recommended: (a) studies wherein all ESSs should be operated in automatic mode; (b) studies on the improvement of individual ESS control; and (c) studies on the reapportionment of all ESS energies within the fleet.

Study for the Relations between Electric Multiple Unit and Energy Storage System (에너지저장시스템과 도시철도 차량의 상관관계에 관한 연구)

  • Lee, Heui-Seon;Baek, Seoung-Gil;Kwon, Kyoung-Min;Kim, Gil-Dong
    • Proceedings of the KSR Conference
    • /
    • 2011.10a
    • /
    • pp.2998-3006
    • /
    • 2011
  • This paper is about the relations between the electric multiple unit and ESS(Energy Storage system, here after) applying bi-direction Buck-Boost Converter. ESS may be possible to suppress the line voltage drops and the power loading fluctuations and to save the regeneration power lapses. This paper confirm for simulation that ESS reusing regenerative power generated during braking in train. Also, presents the influence of regenerative power variation of train and catenary acceptability for energy saving obtained by applying the ESS to Daejeon Metro line 1.

  • PDF

Endometrial Stromal Sarcoma Presented as an Incidental Lung Mass with Multiple Pulmonary Nodules

  • Kang, Dong Oh;Choi, Sue In;Oh, Jee Youn;Sim, Jae Kyeom;Choi, Jong Hyun;Choo, Ji Yung;Hwang, Jin Wook;Lee, Seung Heon;Lee, Ju-Han;Lee, Ki Yeol;Shin, Chol;Kim, Je Hyeong
    • Tuberculosis and Respiratory Diseases
    • /
    • v.76 no.3
    • /
    • pp.131-135
    • /
    • 2014
  • Low-grade endometrial stromal sarcoma (ESS) is an uncommon gynecologic malignancy of mesodermal origin. Pulmonary metastasis of low-grade ESS can occur years and decades after the treatment of the primary disease. Low-grade ESS is frequently mistaken as benign uterine neoplasm like uterine leiomyoma, which can potentially lead to a misdiagnosis. We present a case of a 42-year-old woman with low-grade ESS, that initially presented as an incidental lung mass with multiple pulmonary nodules, seven years after an uterine myomectomy. A $6.9{\times}5.8cm-sized$ intrapelvic mass suspected of uterine origin was discovered while searching for potential extrathoracic primary origin. A pelviscopy and simultaneous thoracoscopic lung biopsy were conducted for pathologic diagnosis. Finally, the diagnosis was confirmed as low-grade ESS with lung metastasis based on the histopathologic examination with immunohistochemical stain, which was showed positive for CD10 and hormone receptor markers (estrogen and progesterone receptors) in both pelvic and lung specimens.

MG Operation Technique based on DC-Grid Stability using ESS (ESS를 활용한 DC-Grid 안정성 기반 MG 운영 기법)

  • Jong-Cheol Kim;Chun-Sung Kim;Yong-Un Park;Seong-Mi Park;Sung-Jun Park
    • Journal of the Korean Society of Industry Convergence
    • /
    • v.26 no.6_3
    • /
    • pp.1269-1278
    • /
    • 2023
  • This paper presents an operational technique that can secure the stability of DC-Grid centering on MG operated based on ESS in multiple MG where three DC-based microgrid(MG) are interconnected. MG1(PV 600kWp, ESS 1.5MWh) has an 830Vdc grid voltage, MG2(PV 300kWp, ESS 1.1MWh) and MG3(PV 100kWp, ESS 500kWh) are DC-based MG with a 750Vdc grid voltage, and MG1 and MG2, 3 are linked by separate DC/DC converters (BTB). In order to keep different grid voltages stable, the power transmission capacity between MG1 and two MG(MG2, MG3) connected with an independent BTB converter was adjusted to secure the overall stability of the system, and this was verified by confirming that the surplus capacity of ESS was maintained in actual operation.

Importance Assessment of Multiple Microgrids Network Based on Modified PageRank Algorithm

  • Yeonwoo LEE
    • Korean Journal of Artificial Intelligence
    • /
    • v.11 no.2
    • /
    • pp.1-6
    • /
    • 2023
  • This paper presents a comprehensive scheme for assessing the importance of multiple microgrids (MGs) network that includes distributed energy resources (DERs), renewable energy systems (RESs), and energy storage system (ESS) facilities. Due to the uncertainty of severe weather, large-scale cascading failures are inevitable in energy networks. making the assessment of the structural vulnerability of the energy network an attractive research theme. This attention has led to the identification of the importance of measuring energy nodes. In multiple MG networks, the energy nodes are regarded as one MG. This paper presents a modified PageRank algorithm to assess the importance of MGs that include multiple DERs and ESS. With the importance rank order list of the multiple MG networks, the core MG (or node) of power production and consumption can be identified. Identifying such an MG is useful in preventing cascading failures by distributing the concentration on the core node, while increasing the effective link connection of the energy flow and energy trade. This scheme can be applied to identify the most profitable MG in the energy trade market so that the deployment operation of the MG connection can be decided to increase the effectiveness of energy usages. By identifying the important MG nodes in the network, it can help improve the resilience and robustness of the power grid system against large-scale cascading failures and other unexpected events. The proposed algorithm can point out which MG node is important in the MGs power grid network and thus, it could prevent the cascading failure by distributing the important MG node's role to other MG nodes.

A Study on the Modeling Method of Performance Evaluation System for MW Scaled Energy Storage System Using the PSCAD/EMTDC (PSCAD/EMTDC를 이용한 MW급 ESS용 성능평가설비 모델링 방안에 관한 연구)

  • Kang, Min-Kwan;Choi, Sung-Sik;Park, Jae-Beom;Nam, Yang-Hyeon;Kim, Eung-Sang;Rho, Dae-Seok
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.66 no.6
    • /
    • pp.885-891
    • /
    • 2017
  • The energy storage system(ESS) is a core component for exchanging the power system structure of the unidirectional power flow into a bidirectional structure. Its important role has been increasing because it has multiple functions such as output stabilization of new renewable energy, demand management, frequency regulation, etc. However, the performance evaluation technology of ESS in korea is lower than one of advanced countries and the recognition of standardization is also lack compared to advanced countries. Furthermore, in order to more accurately and reliably validate the performance of the ESS in advanced countries, it has been required to perform not only performance testing by H/W devices but also performance verification by S/W tool. Therefore, in order to verify the performance testing of ESS by S/W tool, this paper proposes the modeling method of performance testing devices for MW scaled ESS by using the PSCAD/EMTDC S/W, based on real testing devices in domestic institute. From the simulation results of proposed modeling method, it is confirmed that the proposed modeling method is a useful tool for performance validation of ESS.

Interference Mitigation Scheme using Edge Side-lobe Suppressors for OFDMA uplink Systems (직교 주파수 분할 다중 접속 방식 상향 링크에서 측부엽 억제 신호를 이용한 간섭 완화 기법)

  • 유화선;정성순;한상철;홍대식;강창언
    • The Journal of Korean Institute of Communications and Information Sciences
    • /
    • v.28 no.12C
    • /
    • pp.1217-1224
    • /
    • 2003
  • In this paper, we propose an edge side-lobe suppressor (ESS) for the uplink of OFDMA systems, which mitigates the interference introduced by different frequency offsets between a desired user and the other users. We evaluate the proposed ESS scheme by measuring average signal to interference ratio (SIR) and average bit error rate (BER). The simulation results confirm that the proposed ESS scheme improves system performance by approximately 5∼10 dB SIR as compared to conventional OFDMA systems. Because the additional operations for the proposed scheme can be performed by a real-valued look-up table, the implementation of the ESS hardly requires increasing transmitter and receiver complexity.

Multi-Layer Onlay Graft Using Hydroxyapatite Cement Placement without Cerebrospinal Fluid Diversion for Endoscopic Skull Base Reconstruction

  • Kim, Young-Hoon;Kang, Ho;Dho, Yun-Sik;Hwang, Kihwan;Joo, Jin-Deok;Kim, Yong Hwy
    • Journal of Korean Neurosurgical Society
    • /
    • v.64 no.4
    • /
    • pp.619-630
    • /
    • 2021
  • Objective : The skull base reconstruction step, which prevents cerebrospinal fluid (CSF) leakage, is one of the most challenging steps in endoscopic skull base surgery (ESS). The purpose of this study was to assess the outcomes and complications of a reconstruction technique for immediate CSF leakage repair using multiple onlay grafts following ESS. Methods : A total of 230 consecutive patients who underwent skull base reconstruction using multiple onlay grafts with fibrin sealant patch (FSP), hydroxyapatite cement (HAC), and pedicled nasoseptal flap (PNF) for high-flow CSF leakage following ESS at three institutions were enrolled. We retrospectively reviewed the medical and radiological records to analyze the preoperative features and postoperative results. Results : The diagnoses included craniopharyngioma (46.8%), meningioma (34.0%), pituitary adenoma (5.3%), chordoma (1.6%), Rathke's cleft cyst (1.1%) and others (n=21, 11.2%). The trans-planum/tuberculum approach (94.3%) was the most commonly adapted surgical method, followed by the trans-sellar and transclival approaches. The third ventricle was opened in 78 patients (41.5%). Lumbar CSF drainage was not performed postoperatively in any of the patients. Postoperative CSF leakage occurred in four patients (1.7%) due to technical mistakes and were repaired with the same technique. However, postoperative meningitis occurred in 13.5% (n=31) of the patients, but no microorganisms were identified. The median latency to the diagnosis of meningitis was 8 days (range, 2-38). CSF leakage was the unique risk factor for postoperative meningitis (p<0.001). Conclusion : The use of multiple onlay grafts with FSP, HAC, and PNF is a reliable reconstruction technique that provides immediate and complete CSF leakage repair and mucosal grafting on the skull base without the need to harvest autologous tissue or perform postoperative CSF diversion. However, postoperative meningitis should be monitored carefully.