• 제목/요약/키워드: Oil impregnated insulation paper

검색결과 9건 처리시간 0.03초

Comparative Study of DC Breakdown and Space Charge Characteristics of Insulation Paper Impregnated with Natural Ester and Mineral Oil

  • Hao, Jian;Zou, Run-Hao;Liao, Rui-Jin;Yang, Li-Jun;Liao, Qiang;Zhu, Meng-Zhao
    • Journal of Electrical Engineering and Technology
    • /
    • 제13권4호
    • /
    • pp.1682-1691
    • /
    • 2018
  • Natural ester is a suitable substitute for mineral oil and has been widely used in AC transformer in many countries. In order to further application of natural ester in direct current (DC) equipment, it is needed to investigate its long term insulation property under DC condition. In this paper, a thermal ageing experiment was conducted for both mineral oil-paper and natural ester-paper insulation. The DC breakdown and space charge characteristics of insulation paper impregnated with natural ester and mineral oil was compared. Results show that the resistivity of the paper immersed in natural ester and mineral oil both increase as the ageing goes on. While insulation paper impregnated with natural ester has higher resistivity and DC breakdown voltage than the paper impregnated with mineral oil. The DC breakdown voltage for the oil impregnated insulation paper being DC pre-stressing is higher than that without pre-stressing. The average DC breakdown field strength difference between the test with pre-stressing and without pre-stressing clearly shows that there is an apparent enhancement effect for the homo-charge injection on the DC breakdown.

Influence of Electrical Aging on Space Charge Dynamics of Oil-Impregnated Paper Insulation under AC-DC Combined Voltages

  • Wang, Yan;Li, Jian;Wu, Sicheng;Sun, Peng
    • Journal of Electrical Engineering and Technology
    • /
    • 제8권6호
    • /
    • pp.1512-1519
    • /
    • 2013
  • Oil-impregnated paper is a major type of insulation used in oil-filled converter transformers for both traditional and new energy systems. This paper presents and analyzes the results of the experiment conducted on the electrical aging of oil-impregnated paper under AC-DC combined voltages using the pulsed electro-acoustic (PEA) technique. The formation and dynamics of space charge affected the performance of insulation material. The electrical aged oil-paper insulation was obtained through electrical aged experiments under the voltages. Based on the PEA technique, measurements were carried out when the oil-paper insulation system was subjected to different stressing and aging times. The space charge dynamics in the bulk of the oil-paper insulation system with different aging times were measured and analyzed. Characteristic parameters such as the total charge injection amount, the total charges of fast moving and slow moving, and the distortion factor of electric field were calculated and discussed. Results show that the longer electrical aging time, the more charges trapped in the bulk of aging sample. It leads to larger distortion factor of electric field in the bulk of aging samples and accelerate degradation of oil-paper insulation under AC-DC combined voltages.

Space Charge Behavior of Oil-Impregnated Paper Insulation Aging at AC-DC Combined Voltages

  • Li, Jian;Wang, Yan;Bao, Lianwei
    • Journal of Electrical Engineering and Technology
    • /
    • 제9권2호
    • /
    • pp.635-642
    • /
    • 2014
  • The space charge behaviors of oil-paper insulation affect the stability and security of oil-filled converter transformers of traditional and new energies. This paper presents the results of the electrical aging of oil-impregnated paper under AC-DC combined voltages by the pulsed electro-acoustic technique. Data mining and feature extractions were performed on the influence of electrical aging on charge dynamics based on the experiment results in the first stage. Characteristic parameters such as total charge injection and apparent charge mobility were calculated. The influences of electrical aging on the trap energy distribution of an oil-paper insulation system were analyzed and discussed. Longer electrical aging time would increase the depth and energy density of charge trap, which decelerates the apparent charge mobility and increases the probability of hot electron formation. This mechanism would accelerate damage to the cellulose and the formation of discharge channels, enhance the acceleration of the electric field distortion, and shorten insulation lifetime under AC-DC combined voltages.

Two Factors Failure Model of Oil-Paper Insulation Aging under Electrical and Thermal Multistress

  • Li, Jian;Wang, Yan;Bao, Lianwei
    • Journal of Electrical Engineering and Technology
    • /
    • 제9권3호
    • /
    • pp.957-963
    • /
    • 2014
  • Converter transformers play important roles in high-voltage direct current transmission systems. This paper presents experimental and analysis results of the combined electrical and thermal aging of oil-impregnated paper at pulsating DC voltages. Breakdown voltages and time-to-breakdown of oil-paper specimens were measured by using short-time and constant-stress tests. The breakdown characteristics of combined electrical and thermal aging on insulation system were discussed. According to the relationship between failure time and aging temperature, the two-parameter Weibull model was improved. On the basis of the competing risk algorithm and the improved Weibull model, the two factors failure model was calculated. And the influence of temperature in the insulation system has been analyzed. This model performs better than the two-parameter Weibull model when both time and temperature are considered as variables in estimating the lifetime of oil-paper insulation.

회복전압측정 방법을 통한 식물유와 광유에 따른 절연지의 수분 흡습 특성 (A moisture absorption characteristics of insulation papers on the vegetable oil impregnated paper and the mineral oil impregnated paper)

  • 정진혜;한상옥;이세현;박강식
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2008년도 제39회 하계학술대회
    • /
    • pp.2034-2035
    • /
    • 2008
  • 본 논문은 RVM(Return Voltage measurement)을 이용하여 식물유와 광유에 따른 절연지의 수분 흡습성에 관한 특성을 비교하였다. 시험 절연재료로써 절연유는 각각 식물유(Bio Trans 1000,Cargill사)와 광유(제1종 2호, 동남석유(주))를 사용하였고, 절연지는 셀룰로오스계 크래프트 절연지를 사용하였다. 각 조건에서 IEEE/ANSI Standard C59.91-1981의 기대수명 곡선에서 $55^{\circ}C$ 절연을 기준으로하여 가속 열열화 시험을 수행한 후, $15^{\circ}C$씩 온도를 변화시켜 RVM 측정을 하였다.

  • PDF

Effects of the Insulation Quality on the Frequency Response of Power Transformers

  • Abeywickrama Nilanga;Ekanayake Chandima;Serdyuk Yuriy V.;Gubanski Stanislaw M.
    • Journal of Electrical Engineering and Technology
    • /
    • 제1권4호
    • /
    • pp.534-542
    • /
    • 2006
  • This paper presents results of frequency domain spectroscopy (FDS) measurements on oil-impregnated pressboard insulation, their analyses and use of the data for modeling high frequency response (FRA) of transformers. The dielectric responses were measured in a broad frequency range, i.e. from 0.1 mHz to 1 MHz, on model samples containing different amount of moisture. The responses were parameterized with terms representing dc conductivity, low frequency dispersion and Cole-Cole polarization mechanisms and they were thereafter used to model the FRA response of a three-phase transformer.

OF 케이블 절연유의 환경친화적 자재 적용 (Biodegredible material application of insulation oil of OF CABLE)

  • 김종원;이기수;하재청;최봉남;이승열
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2000년도 하계학술대회 논문집 C
    • /
    • pp.2023-2025
    • /
    • 2000
  • Globally, movements for an environmental preservation have been further extended in all the areas of industries. In the manufacturing area. environment-friendly properties for all the manufactured products are increasingly required by many national standards. For EHV oil-filled cables. Hard Alkylbenzen has been applied as an impregnated insulating oil. But as it flows into the soil during failures, such as oil leakage, the oil is not dissolved by microbes and then causes an environmental pollution. Recently some countries are increasingly requiring Soft Alkylbenzen which is dissolved by microbes. This paper describes the electrical and environmental properties of Soft Alkylbenzen. applied for a 230kV oil-filled cables at a Singapore's project.

  • PDF

HVDC 500kV PPLP MI 케이블시스템 개발 (Development of HVDC 500kV PPLP MI cable systems in Korea)

  • 이수봉;조동식;김성윤;이태호;이수길;전승익
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2015년도 제46회 하계학술대회
    • /
    • pp.1202-1203
    • /
    • 2015
  • This paper describes the development of HVDC ${\pm}500kV$ polypropylene laminated paper (PPLP) mass-impregnated (MI) type cable system for HVDC transmission lines. As you know, mass-impregnated type cable generally has only insulating layer with the Kraft paper impregnated with a high-viscosity insulating compound. But polypropylene laminated paper is made of a layer of extruded polypropylene (PP) film sandwiched between two layers of Kraft paper. Thanks to PP film and its combination with Kraft paper, PPLP has higher AC, Impulse (Imp.) and DC breakdown (BD) strengths as well as lower dielectric loss than conventional Kraft paper insulation. In addition, Kraft MI cable has a limitation for the maximum conductor temperature as $55^{\circ}C$ But this PPLP MI cable has higher maximum conductor temperature than that of Kraft MI cable due to advantage of oil drainage characteristics. It is the most economic type of cable for HVDC transmission. Also HVDC ${\pm}500kV$ PPLP MI cable system was developed including land joints and outdoor-terminations. In order to prove the mechanical and electrical performances, the type test was carried out according to CIGRE recommendations. A full scale cable system has been tested successfully. And additional load cycle and polarity reversal tests on the cable system showed a higher performance compared with a similar mass impregnated paper cable.

  • PDF

180kV HVDC 해저케이블 기계적/전기적 특성 평가 (Mechanical and Electrical Performance of 180kV HVDC Submarine Cable System)

  • 김남열;이태호;지봉기;이상진;김정년;전승익;윤희석;정수길;강채홍;안용호
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2007년도 제38회 하계학술대회
    • /
    • pp.616-618
    • /
    • 2007
  • This paper describes the mechanical and electrical test on HVDC submarine cable, Flexible Repair Joint and termination for 180kV. This HVDC submarine cable was manufactured using LS cable's unique skill and would be applied the HVDC submarine cable system in korea. The performance test consist of mechanical test and electrical test. The tensile bending test and tensile test was done as the mechanical test and Electrical test is DC voltage and Impulse test. The tensile bending test carried out 6 times(double of specified times) for maximum reliability. The DC test voltage is $\pm$400kV/1hr. We estimate the lower limit of DC breakdown voltage is 600kV. The impulse test voltage is $\pm$800kV/10shots. The type of developed cables is the MI type. Its insulation consist of paper tapes impregnated with a high viscosity oil. The development of new HVDC cable is available for HVDC underground or submarine power transmission. The developed HVDC cable, FRJ and termination have passed the mechanical and electrical test successfully and showed excellent performance.

  • PDF