• Title/Summary/Keyword: On-line monitoring system

Search Result 761, Processing Time 0.037 seconds

On-line Monitoring and Diagnostics for Distribution Panel System (배전반 시스템의 온라인 감시 및 진단)

  • Choi, Yong-Sung;Lee, Kyung-Sup
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2008.04c
    • /
    • pp.106-110
    • /
    • 2008
  • Continuous on-line temperature monitoring allows corrective measures to be taken to prevent upcoming failure. Continuous temperature monitoring and event recording provides information on the energized equipment's response to normal and emergency conditions. On-line temperature monitoring helps to coordinate equipment specifications and ratings, determine the real limits of the monitored equipment and optimize facility operations. Using wireless technique eliminates any need for special cables and wires with lower installation costs if compared to other types of online condition monitoring equipment. In addition, wireless temperature monitoring works well under difficult conditions in strategically important locations. Wireless technology for on-line condition monitoring of energized equipment is applicable both as standalone system and with an interface with power quality monitoring system.

  • PDF

The Development of Industry Operation Control System using Intelligent Web Monitoring for the Heat Treatment Process (열처리공정의 지능형 웹 모니터링 산업용 공정제어 시스템 개발)

  • Oh, J.H.;Bae, H.J.;Choi, G.S.;Ahn, D.S.
    • Journal of Power System Engineering
    • /
    • v.9 no.4
    • /
    • pp.181-186
    • /
    • 2005
  • Because of advanced control technology, Shop floor control system of various kinds of equipment and machinery need a web based remote monitoring to control process efficiently. This paper presents the development of Operation Control System. Operation Control System(OCS) is based on intelligent web monitoring, so that OCS is improved the working condition for the line of heat treatment process and the product's quality. The developed OCS is consisted of Atmega128(MCU) based on embedded system, running the data logging of the line of heat treatment process. Web monitoring system is based on CS8900 ethernet controller and TCP/IP for remote monitoring responsibility between a server and clients and controlling the progress of entire system. The developed OCS is implemented on the line of heat treatment process and shows the improvement of environment condition, product's quality and efficiency of process line.

  • PDF

An Improvement of Optical Fiber Composite Power Cable On-Line Monitoring System for Underground Distribution Network (지중 배전계통 적용을 위한 광복합 케이블 실시간 감시시스템 개선)

  • Cho, Jin-Tae;Kim, Ju-Yong;Lee, Hak-Ju;Park, Jung-Sung
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.26 no.7
    • /
    • pp.77-83
    • /
    • 2012
  • Since power system is switching to smart grid, on-line monitoring technology has become necessary for underground distribution power cable. Therefore, the application of DTS(Distributed Temperature Sensing) technology using OFCPC(Optical Fiber Composite Power Cable) capable of monitoring underground distribution power cables has been developed. These can bring about reductions in faults and increases in operating capacity of underground distribution system. To date, the test-bed of optical fiber composite power cable on-line monitoring system has been constructed. Then, matters to be improved have been drawn through verification experiments. This paper presents the improvement and experiment results of the optical fiber composite power cable on-line monitoring system to apply to underground distribution lines in the field.

On-line Insulation Diagnostic by PD Monitoring Field Practical of UHF Technique for On-line PD Monitoring (UHF 기술을 이용한 온라인 부분방전 모니터링)

  • Oh, Yong;Choi, Yong-Sung;Hwang, Jong-Sun;Lee, Kyung-Sup
    • The Transactions of the Korean Institute of Electrical Engineers P
    • /
    • v.57 no.2
    • /
    • pp.176-180
    • /
    • 2008
  • A field-oriented UHF system for on-line PD monitoring of transformers is designed, which has been installed inside the oil tank of transformer in a substation by two ways: on-line installing mode through the oil-valve and pre-installing mode through the man hole/hand hole cover. This system has successfully captured long intermittent discharge signals that hadn't been detected through conventional techniques, and solved the problem successfully. The results demonstrate that UHF technique has great advantages for on-line PD monitoring of transformers. By adopting the peak detection technique, it becomes easy and effective for the transplantation of the phase-resolved pattern recognition technique from conventional method to UHF method, and then to realize continuous on-line monitoring, source characterization and trending analysis.

A case study on the failure diagnosis of plant machinery system by implementing on-line wear monitoring (실시간 마모량 측정을 통한 대형 기계윤활시스템의 파손발생 진단사례)

  • 윤의성;장래혁;공호성;한흥구;권오관;송재수;김재덕;엄형섭
    • Proceedings of the Korean Society of Tribologists and Lubrication Engineers Conference
    • /
    • 1998.04a
    • /
    • pp.321-327
    • /
    • 1998
  • This paper presented a case study on the application of on-line wear monitoring technique to a high duty air-turbo-compressor system. Main objects monitored were a gear unit and metal bearings, both shown frequent troubles due to the severe operation conditions at heavy dynamic load. The air-turbo-compressor system needs secure condition monitoring because it is one of the main utilities in steel making industry. Temperature and vibration characteristics have been mainly on-line monitored in this system for a predictive maintenance; however, it has been shown that they are not fairly good enough to give an early warning prior to the machine failure. In this work, an on-line Opto Magnetic Detector(OMD) was implemented for an on-line wear monitoring, which quantitatively measured the contamination level of both ferrous and non-ferrous wear particles by detecting the change in optical density of used oil. Results showed that the application of on-line OMD system was satisfactory in diagnosis of the machine system.

  • PDF

On-line PD Monitoring Using UHF Technique (UHF 가술을 이용한 온라인 PD 모니터링)

  • Choi, Yong-Sung;Lee, Kyung-Sup
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2008.04c
    • /
    • pp.115-118
    • /
    • 2008
  • A field-oriented UHF system for on-line PD monitoring of transformers. is designed, which has been installed inside the oil tank of a transformer by two ways: on-line installing mode through the oil-valve and pre-installing mode through the man hole/hand hole cover. This system has successfully captured long intermittent discharge signals that hadn't been detected through conventional techniques, and solved the problem successfully. The results demonstrate that UHF technique has great advantages for on-line PD monitoring of transformers. By adopting the peak detection technique, it becomes easy and effective for the transplantation of the phase-resolved pattern recognition technique from conventional method to UHF method, and then to realize continuous on-line monitoring, source characterization and trending analysis.

  • PDF

On-line Monitoring of Tribology Parameters and Fault Diagnosis for Disc Brake System

  • Yang Zhao-Jian;Kim Seock-Sam
    • Proceedings of the Korean Society of Tribologists and Lubrication Engineers Conference
    • /
    • 2003.11a
    • /
    • pp.224-228
    • /
    • 2003
  • The basic Principles and methods of the on-line monitoring of tribology parameters (friction coefficient and wear allowance) and fault diagnosis for the hoist disc brake system were introduced, the method were based on the spring force and oil pressure of the brake system and the hoist kinematics parameters. The experiment on the monitoring and diagnosis of hoist brake system were carried out. The research results showed: the monitoring and diagnosis methods are feasible.

  • PDF

On-line Monitoring of Glucose and Starch by a Flow Injection Analysis Technique (흐름주입분석 기술에 의한 글루코우스와 전분의 온라인 모니터링)

  • 김준홍;박돈희;이종일
    • KSBB Journal
    • /
    • v.16 no.5
    • /
    • pp.459-465
    • /
    • 2001
  • The on-line monitoring technique for the concentrations fo glucose and starch by FIA(Flow Injection Analysis)system was studied. Glucose oxidase(GOD) and amyloglucosidase(AMG) were immboilized on VA-Fpoxy carrier and integrated into the FLA system. The pH, buffer flow rate and temperature were optimized and the effects of salts and metabolites dissolved in the sample on the activity of immobilized enzyme were investigated. GOD-FIA and AMG/GOD-FIA were applied for the on-line monitoring of the glucose and starch in a simulated bioprocess. The on-line measurements of glucose concentrations by GOD-FIA agreed with off-line data well and the AMG/GOD-FIA with single cartidge system took and advantage over the FIA system with two separated cartridges for the on-line monitoring of starch concentrations.

  • PDF

Development and Application of Distributed Multilayer On-line Monitoring System for High Voltage Vacuum Circuit Breaker

  • Mei, Fei;Mei, Jun;Zheng, Jianyong;Wang, Yiping
    • Journal of Electrical Engineering and Technology
    • /
    • v.8 no.4
    • /
    • pp.813-823
    • /
    • 2013
  • On-line monitoring system is important for high voltage vacuum circuit breakers (HVCBs) in operation condition assessment and fault diagnosis. A distributed multilayer system with client/server architecture is developed on rated voltage 10kV HVCB with spring operating mechanism. It can collect data when HVCB switches, calculate the necessary parameters, show the operation conditions and provide abundant information for fault diagnosis. Ensemble empirical mode decomposition (EEMD) is used to detect the singular point which is regarded as the contact moment. This method has been applied to on-line monitoring system successfully and its satisfactory effect has been proved through experiments. SVM and FCM are both effective methods for fault diagnosis. A combinative algorithm is designed to judge the faults of HVCB's operating mechanism. The system's precision and stability are confirmed by field tests.

On-Line Diagnostics and Monitoring of Distribution Panel Using IR-Sensor (광온도센서를 이용한 분전반의 온라인 진단 및 감시)

  • Yun, Ju-Ho;Choi, Yong-Sung;Hwang, Jong-Sun;Lee, Kyung-Sup
    • Proceedings of the KIEE Conference
    • /
    • 2008.07a
    • /
    • pp.2110-2111
    • /
    • 2008
  • Continuous on-line temperature monitoring allows corrective measures to be taken to prevent upcoming failure. Continuous temperature monitoring and event recording provides information on the energized equipment's response to normal and emergency conditions. On-line temperature monitoring helps to coordinate equipment specifications and ratings, determine the real limits of the monitored equipment and optimize facility operations. Using wireless technique eliminates any need for special cables and wires with lower installation costs if compared to other types of online condition monitoring equipment. In addition, wireless temperature monitoring works well under difficult conditions in strategically important locations. Wireless technology for on-line condition monitoring of energized equipment is applicable both as standalone system and with an interface with power quality monitoring system.

  • PDF