• Title/Summary/Keyword: Partial discharge inception voltage

Search Result 54, Processing Time 0.031 seconds

A Study on Degradation Properties of Silicone Cable due to Partial Discharge (부분 방전에 의한 실리콘 케이블의 열화 특성에 관한 연구)

  • Lee, Sung Ill
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.28 no.1
    • /
    • pp.34-39
    • /
    • 2015
  • In this study, the characteristics of partial discharge was measured for the four core silicone cable (0.6/1.0 kV, $1.0SQ{\times}4C$) with insulated part of 15 cm and conductor of 1cm. The following results have been confirmed as a result of this study. When the first line of cable is connected to the positive electrode and the second, third line of cable is connected to the negative electrode, it found that the inception voltage and extinction voltage decreased with increasing the line of negative electrode, and the partial discharge charge quantity(Q) increases, while the number of discharge occurrence has decreased. The inception voltage and extinction voltage of partial discharge has decreased with increasing the degradation rate in the 33%, 67%, 100%. Also, it confirmed that the partial discharge charge quantity(Q) and the number of discharge occurrence has decreased.

Insulation Performance Estimation of Main Relays by Partial Discharges (부분방전에 의한 주계전기의 절연성능 평가)

  • Kil, Gyung-Suk;Kim, Il-Kwon;Park, Dae-Won;Song, Jae-Yong;Lee, Gang-Won;Cho, Eun-Je
    • Journal of the Korean Society for Railway
    • /
    • v.10 no.4
    • /
    • pp.388-392
    • /
    • 2007
  • A new dielectric test on main relays of electric traction vehicles, the partial discharge(PD) test, is proposed. The PD test will not affect the insulation performance of specimen during the test and provide much more detailed information on insulation, the types of defects, and so on. Insulation performance of relays is estimated by discharge inception voltage(DIV), discharge extinction voltage (DEV), and apparent charge as a function of test voltage and time. Three main relays of different manufacturing date were estimated by applying AC voltage with three patterns in ranges of $0{\sim}1,200[V]$. From the results, we could estimate insulation state and which types of defects exist in them.

The Analysis of Discharge Distribution due to the Inner Void of Extra High Voltage Cable

  • Kim Tag-Yong;Hong Jin-Woong
    • KIEE International Transactions on Electrophysics and Applications
    • /
    • v.5C no.4
    • /
    • pp.155-160
    • /
    • 2005
  • This paper addresses the discharge characteristics of cross-linked polyethylene according to void by the Weibull function. It analyzes discharge number and amount of discharge using Weibull distribution to identify the inter-relationship between partial discharge and defect. We detected a 10 second discharge. The applied voltage increased by 1 [kV] at discharge inception voltage. As a result, in a no-void specimen, the shape parameter was consistent according to the increase of voltage, whereas, in a void specimen, it increased according to the increase of voltage. As the result, the shape parameter expressed a fixed value at no-void specimen. However, in void specimen, according to increasing voltage shape parameter rapidly increases.

A Study on Partial Discharge Degradation Properties of PVC Cable due to NaCl (NaCl에 의한 PVC 케이블의 부분방전 열화 특성에 관한 연구)

  • Lee, Sung Ill
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.28 no.10
    • /
    • pp.636-641
    • /
    • 2015
  • In this study, the partial discharge degradation properties for 2-core PVC cable($2cores{\times}1.5mm^2$ cross section, length of 10 cm, 20 cm, 30 cm) following immersion with the salt water that the 2%, 4%, 8% of NaCl is dissolved in 100 g of distilled water for 48 and 96 hours has been measured. The results of this study are as follows. When the degradation time in salt water of 2% NaCl is 48 hours, it found that the number of partial discharge increased as about 40 pps, 50 pps, 90 pps with increasing the length of cable to 10 cm, 20 cm, 30 cm. In case the concentration and degradation time is same, the inception and extinction voltage decreased with increasing the length of cable. When the degradation time in salt water is 96 hours and the length of cable is 20 cm, it found that the number of partial discharge decreased as 3,000 pps, 500 pps, 100 pps with increasing the concentration of NaCl to 2%, 4%, 8%.

Dependence of the Partial Discharge Characteristics of Ultra-high Voltage Cable Insulators on the Measuring Temperature

  • Shin, Jong-Yeol;Park, Hee-Doo;Lee, Hyuk-Jin;Lee, Kang-Won;Kim, Won-Jong;Hong, Jin-Woong
    • Transactions on Electrical and Electronic Materials
    • /
    • v.9 no.5
    • /
    • pp.186-192
    • /
    • 2008
  • Cross linked polyethylene (XLPE) insulators are used as insulation in ultra-high voltage electric power cables. This study investigated the electrical properties of XLPE at different temperatures. The electrical properties of the changing tree phenomenon was examined as a function of temperature applied to the electrical conductors by measuring the partial discharge at $25^{\circ}C$ to $80^{\circ}C$ and applied voltages to the electrodes ranging from 1 kV to 40 kV. The activity of the partial discharge was examined at various temperatures using the K-means distribution. The results revealed the specimen at $80^{\circ}C$ to have the lowest inception voltage and breakdown voltage. In addition, the core of clusters was moved $0^{\circ}$ and $180^{\circ}$ at the positive region and $180^{\circ}$ and $360^{\circ}$ in the negative region in the K-means. The distribution of clusters was concentrated on the inception condition and spread out widely at the breakdown voltage.

Partial Discharge Phenomenon with $SF_6$ Gas Pressures in Insulation consisting of Insulation Paper and $SF_6$ Gas (SF_6 가스와 절연지의 절연계에서 가스압력에 따른 부분방전현상)

  • 선종호;김광화;박정후;조정수
    • The Transactions of the Korean Institute of Electrical Engineers C
    • /
    • v.50 no.2
    • /
    • pp.65-71
    • /
    • 2001
  • This paper describes partial discharge phenomenon with SF6gas pressures in insulation consisting of insulation paper and SF6 gas. We made the specimens with SF6 gas gaps which exist between aramid papers and electrodes and calculated the electric field intensity in the these gaps. We measured the partial discharge inception voltages and the AC breakdown voltages with the test method of IEC 60060-2 and did the partial discharge degradation experiments with a constant voltage. According to gas pressures, the breakdown voltages in SF6gas gaps were calculated by Paschen's law. And these results showed the ability applying partial discharge inception voltages evaluation to Paschen's law and the relationship between the PD quantities occurring insulation breakdown and PD occurring area.

  • PDF

Insulation Characteristics of High Temperature Superconducting Cable (고온 초전도 레이블의 절연 특성)

  • Kim, H.J.;Kim, J.H.;Sim, K.D.;Kim, H.J.;Cho, J.W.;Seong, K.C.;Kwag, D.S.;Kim, S.H.
    • Proceedings of the KIEE Conference
    • /
    • 2004.11a
    • /
    • pp.244-247
    • /
    • 2004
  • The electrical insulating design is important to realize a HTS power cable because the cable is operated under the high voltage environment. For the insulation design of a HTS power cable, it is necessary to investigate the AC, impulse breakdown and partial discharge(PD) inception stress of liquid nitrogen/LPP composite insulation system. Based on these results, the electrical insulation of a HTS power cable is designed and Mini-model cables are manufactured. The manufactured Mini-model cables are evaluated that AC, impulse withstand voltage, breakdown and partial discharge inception stress and analyzed characteristics insulation of HTS cable bending condition according to this paper. From these tests, the AC, impulse withstand voltage test and partial discharge inception stress is satisfied "standard technical specification of KEPCO" in Korea and the breakdown voltage was 120kV.

  • PDF

Breakdown Voltage and PD Characteristics of $SF_6/CF_4$ Mixtures in Nonuniform Field (불평등 전계에서 $SF_6/CF_4$ 혼합가스의 절연내력과 PD특성)

  • Hwang, Cheong-Ho;Sung, Heo-Gyung;Huh, Chang-Su
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.57 no.4
    • /
    • pp.635-640
    • /
    • 2008
  • New gas mixtures are now finding applications such as interrupting media for high-voltage circuit breakers. These mixtures consist of a high content of carbon tetrafluoride($CF_4$) added to sulfur hexafluoride($SF_6$). Nowdays $SF_6$ has been established for the use in gas insulated substations due to its high insulation withstand level and good arc quenching capability. At this paper Breakdown characteristics were investigated for $SF_6/CF_4$ mixtures when AC voltage and standard lightning impulse voltage(LI) was applied in a needle-plane electrodes. And partial discharge(PD) experiments were carried out in the test chamber which was made in needle-plane electrode. And ${\Phi}$-Q-N distribution of partial discharge signals was analyzed. The total pressure of the $SF_6/CF_4$ mixtures was varied within the range of 0.1-0.5 Mpa in the test chamber. The breakdown voltage in needle-plane electrode displayed N shape characteristics for increasing the content of $SF_6$ at positive impulse voltage and the PD inception voltage was increased slightly when pressure of $SF_6/CF_4$ Mixtures was increased. Maximum PD inception voltage is showed in 80% SF6/20%$CF_4$.

Lift-Off Voltage and Partial Discharge Characteristics of Free Metallic Particles in GIS (GIS 내 금속입자의 부상전압과 부분방전특성 연구)

  • Yun, Jin-Yeol;Han, Sang-Ok
    • The Transactions of the Korean Institute of Electrical Engineers C
    • /
    • v.48 no.2
    • /
    • pp.127-132
    • /
    • 1999
  • Both motion of free metallic particles from which most GIS internal failures are caused and partial discharges from the particles were examined using EHV GIS test chamber. Effects from particle length and gas pressure which are main factors to lead to breakdown failure were investigated theoretically and experimentally. Magnitude of both lift-off voltage and partial discharge inception voltage were measured respectively and, through these measurements, this paper showed the possibility of predicting breakdown fault and of taking action to prevent the fault in advance. The measurement of partial discharge when the particles began to move could be adopted to decide minimum sensitivity in developing predictive diagnostic equipments. Both the amount of apparent discharge and real discharge in GIS were examined theoretically and experimentally, then experimental results were analyzed on the basis of the theory.

  • PDF

Insulation Characteristics of PET Films for $SF_6$ EHV VT Winding ($SF_6$ EHV VT 권선 절연지의 절연특성)

  • 김정달;박재윤;정장근;김종석;하현진;이용길
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.14 no.5
    • /
    • pp.391-396
    • /
    • 2001
  • The purpose of this study is to investigate the effect of hole or crack on the Insulation characteristics of a PET films for EHV(Extra High Voltage) VT winding. The hole or the crack in the PET films was made and the insulation characteristics of them were measured. Ad an experimental result, it was shown hat he PDIV(Partial Discharge Inception Voltage) and the BDV(Breakdown Voltage) of the PET films with hole or crack were lower than those without them, and were markedly dependent on their position and temperature. Therefore, the hole and the crack affected to insulation characteristics of PET films for SF$_{6}$EHV(Extra High Voltage) VT Winding.g.

  • PDF