• 제목/요약/키워드: Radiant heating panel

검색결과 26건 처리시간 0.017초

복사난방패널의 설계 및 운전을 위한 열적 특성 분석 (An analysis of the thermal characteristics for optimal design and operation of the radiant heating panels)

  • 이태원
    • 설비공학논문집
    • /
    • 제9권2호
    • /
    • pp.180-188
    • /
    • 1997
  • The theoretical analysis and experiment with simulator were performed to obtain the temperature distributions in radiant heating panel and heat supply from hot water to heating space for the purpose of the development of comfortable living space from a point of view of the improvement of air quality and the enhancement of system efficiency. The relations of various parameters, such as pipe pitch, room temperature as well as flow rate and temperature of hot water and so on, with the rate of heat supplied, mean temperature and maximum temperature difference at panel surface were discussed. The effects of these parameters were also verified on the thermal performance of heating panel using the relations which could be used for the optimal design and operation of the radiant heating panel.

  • PDF

복사 난방 패널의 과도 열전달 해석 (Unsteady Heat Transfer Analysis of Radiant Heating Panel)

  • 이태원;김호영
    • 설비공학논문집
    • /
    • 제4권3호
    • /
    • pp.191-203
    • /
    • 1992
  • To analyze the unsteady heat transfer phenomena in radiant heating panel, a mathematical model was considered. Numerical analysis for solving the governing equations was conducted by using the finite difference method with boundary-fitted meshes. Transient temperature distributions and thermal responses in heating panel were obtained for various design parameters such as pipe pitches, pipe diameters and pipe depths. Experimental results were also obtained to verify the results of calculation.

  • PDF

이중 윅 타입 히트파이프를 이용한 바닥복사패널의 난방특성 연구 (A Study on the Heating Characteristics of Radiant Floor Panel Using Heat Pipes with the Double Wick)

  • 김용기;이태원
    • 설비공학논문집
    • /
    • 제24권2호
    • /
    • pp.183-189
    • /
    • 2012
  • Most of the domestic residential buildings have used the traditional radiant heating system, circulating hot water through the cross-linked polyethylene(PE-X) pipe buried in the floor panel of the heating space. New type of the heating panel was recently developed using heat pipes with double wicks. Some experiments were carried out in this study to verify the thermal characteristics of this heating system at the unit heating space which surrounded by outer space whose temperature of air be maintained scheduled value with time. Through the various experiments with several parameters, such as flow rate, inlet and outlet temperatures of hot water and the heating duration and so on, we found that the floor heating system with heat pipes was able to reduce the pumping power for hot water circulation by 4~31% compared with the conventional panel heating system using PE-X pipe. These results could be used for optimal design and efficient operation of the heating system as well as improvement of thermal comfort.

복사 난방 패널의 공급유량 및 설계변수가 성능에 미치는 영향 (The Effects of Operating and Design Conditions on the Performance of Radiant Heating Panel)

  • 이태원;김호영
    • 설비공학논문집
    • /
    • 제3권4호
    • /
    • pp.276-285
    • /
    • 1991
  • The transient heat transfer characteristics in the radiant heating panel were predicted by numerical analysis. Thermal behaviors of panel, such as temperature distributions in panel and convective and radiative heat fluxes in panel surface with respect to time were obtained. Heating hours per day, rate of energy supplied and maximum temperature differences at panel surface were also compared for several important parameters. The performance and thermal comfort of heating panel were studied and compared for various operating and design conditions such as pipe pitch, pipe location, pipe diameter and flow rate of hot water for the purpose of producing useful data, which can be used for the test and decision of efficient operating condition of the conventional heating systems or the optimal design of the new panel heating systems.

  • PDF

방열핀이 난방용 패널의 열적거동 및 성능에 미치는 영향 (The Effects of Heat Diffusion Fin on the Thermal Behavior and Performance of Radiant Heatomg Panel)

  • 이태원
    • 대한기계학회논문집
    • /
    • 제18권9호
    • /
    • pp.2486-2493
    • /
    • 1994
  • Transient heat transfer characteristics in th radiant heating panel with heat diffusion fin were predicted by numerical analysis. Thermal behaviors of panel, such as temperature distributions in panel and convective and radiative heat fluxes in panel surface with advance of time, were obtained for several important parameters. The performance and thermal comfort of heating panel were studied and compared for various design conditions, such as pipe pitch, area ratio and thermal conductivity of optimal design of the new heating panels with heat diffusion fin. It was concluded that the efficient area ratio of heat diffusion fin is about 0.5, and the greater the thermal conductivity of fin is, the better the performance of panel is.

적외선 가열로에서 가열되는 유리 패널의 온도분포 해석 (Analysis of Temperature Distribution of the Glass Panel in the Infrared Heating Chamber)

  • 이공훈;김욱중;하수석;강새별;이준식
    • 대한기계학회:학술대회논문집
    • /
    • 대한기계학회 2003년도 추계학술대회
    • /
    • pp.278-283
    • /
    • 2003
  • Analysis has been carried out to investigate the temperature variation and the uniformity of the temperature distribution of the glass panel by infrared radiant heating. Halogen lamps are used to heat the panel and located near the top and bottom of the rectangular chamber. The thermal energy is transfered only by radiation and the radiation exchange occurs only on the solid surfaces and is considered by using the view factor. The results show that the uniformity of the temperature distribution of the panel is improved but the time for heating increases as the wall reflectivity is large. The temperature difference reaches a maximum in the early stage of the heating process and then decreases until it reaches the uniform steady-state value.

  • PDF

강판 마감형 조립식 벽패널 복사냉난방시스템의 냉난방 방열 특성 평가 (Evaluation of Heating and Cooling Thermal Output Characteristics of Prefabricated Steel Wall Panel System for Radiant Heating and Cooling)

  • 임재한;구보경;김성임;송승영
    • 한국태양에너지학회 논문집
    • /
    • 제33권2호
    • /
    • pp.70-77
    • /
    • 2013
  • Recently the radiant panel heating and cooling system has been regarded as an alternative of low temperature heating and high temperature cooling by applying the renewable energy sources to the heating and cooling of buildings. Especially this system can be used as HVAC system alternatives in super high-rise buildings for energy saving and thermal comfort. Also it can be possible to reduce the plenum space because the minimum ventilation air will be supplied into the space. This study focused on the evaluation the basic characteristics of thermal output in prefabricated steel wall panel system for radiant heating and cooling. In order to evaluate the thermal output according to both various supply water temperatures and supply water flow rates, three-dimensional dynamic heat transfer analysis was performed. As results, for the heating mode, thermal output increased by 26% with the supply temperature increasing by $5^{\circ}C$. The surface temperature of panels range within $1{\sim}3^{\circ}C$. For the cooling mode, thermal output decreased by 18.2% with the supply temperature increasing by $2^{\circ}C$. The surface temperature of panels range within $0.5{\sim}1^{\circ}C$ and it was shown the even temperature distribution.

불균등 복사공간의 쾌적온도범위 설정에 관한 연구 (A Study on the Establishment of the Optimal Temperature Limits for Man's Thermal Comfort in an Asymmetric Radiant Space)

  • 손장열;공성훈;윤용진
    • 대한설비공학회지:설비저널
    • /
    • 제14권3호
    • /
    • pp.187-199
    • /
    • 1985
  • The low-temperatured radiant heating System like a panel heating system is recognized as nice means to make comfortable indoor environment. Perhaps, 'Ondol' would be a typical example of the Panel heating system. Nevertheless. Occupants in a radiantly heated Space which has an asymmetric radiant field may feel thermally discomfort due to the asymmetric radiation. The aim of this Study is to suggest the fundamental technical data for establishing Standards of thermally comfortable environment when designing a radiant heating System. Thermal distribution of indoor environment and the skin temperature of the occupants were measured at experimental room in KIER (Korea Institute of Energy and Resources). Whole/Regional thermal and comfort Sensation votes of the occupants were taken simultaneously in order to investigate the relationships between thermal environmental factor and the occupants' responses. The effect of an asymmetric radiation on thermal environment and the occupants' responses was analyzed by using a v.r.t.(vector radiant temperature). By this means, the thermally neutral limits for the ambient air temperature and the floor surface temperature by the occupants' responses were Obtained. And the recommended temperature limits of the indoor surface were derived from the experimental work and the theory of radiant and will provide thermal neutrality for man without any discomfort on the part of the body.

  • PDF

복사난방패널 방열량실험의 제어오차요인 분석 (Analysis of Control Error Factors of a Thermal Output Experiment for Radiant Heating Panels)

  • 신대욱
    • 토지주택연구
    • /
    • 제9권4호
    • /
    • pp.33-42
    • /
    • 2018
  • As a radiant heating panel gets more popularity, the need to study on evaluation method of thermal output of the panel also becomes increasing. Generally, the chamber using method is applied to evaluate the thermal output through an experiment. However, the chamber using method cannot be used due to the limitations on space and cost. EN1264 addresses the test equipment to evaluate the thermal output by using simpler experimental setup, and introduces application method in detail. However, there is not enough description of control methods to meet the experiment condition, and it is difficult to meet this when practical experiment. Therefore, this paper analysed the control error factors of when the thermal output experiment is performed. When EN1264 method is applied to evaluate the thermal output of the radiant floor heating panel, the error factor which is caused by the characteristic of test equipment cannot be removed by the control methods of chamber using method. In addition, the error factor can be occurred at the element which is located out of the control system. These possible error factors are defined as the characteristic error factors.

2차원(次元) 온돌 상난방(床煖房)시스템의 연도내 열유동(熱流動) 및 열전달(熱傳達) 수치해석(數値解析) (Numerical Analysis of Heat Flow and Heat Transfer in Flue Channel of Two-Dimensional Ondol Panel Heating System)

  • 김영득;민만기;이상혁;김원갑
    • 설비공학논문집
    • /
    • 제6권4호
    • /
    • pp.337-343
    • /
    • 1994
  • Numerical analysis was applied to a simplified two-dimensional Ondol heating model which consists of heating space on the top of it along with radiant and convective heating floor panel, flue channel in the midway and rectangular underground soil region at the bottom. These three components constitute a system thermally coupled at the top and bottom interfaces of the flue channel. Investigated in the present paper are effects with variations of the Reynolds numbers of 100, 200, and 300, Grashof numbers of $0.1{\times}10^6$ and $0.3{\times}10^6$ and aspect ratios of 15 and 20 on the heat transfer and fluid flow characteristics of two-dimensional Ondol heating model by computer simulation.

  • PDF