• Title/Summary/Keyword: Room corner tester

Search Result 6, Processing Time 0.017 seconds

Investigation of the Relationship Between Wall Thermal Conductivity and Inner Room Temperature in Compartment Fires (구획화재에서 벽면의 열전도 계수와 내부 온도의 상관관계 분석)

  • You, Woo Jun;Ko, Gwon-Hyun
    • Fire Science and Engineering
    • /
    • v.32 no.2
    • /
    • pp.17-23
    • /
    • 2018
  • In this study, the relations of the wall thermal conductivity and surface temperature in a compartment fire are investigated using Buckingham Pi theorem. The dimensionless parameters of the previous study are analyzed in order to correlate the dimensionless groups of the heat release rate, the thermal conductivity, the volume of compartment and the convective heat transfer coefficient. In addition the reduced scale of compartment, which has 1/6 size of ISO 9705 Room Corner Tester, is manufactured and the oxygen concentration and the maximum temperature in the space are measured for the gasoline pool fire ($10cm{\times}10cm$, $15cm{\times}15cm$ and $20cm{\times}20cm$). Finally, the criterion of the wall temperature increase are suggested in accordance with the thermal conductivity and the convective heat transfer coefficient. In addition, the dimensionless empirical equation using Buckingham Pi theorem considering the heat release rate are presented suggested. The results of this study will be useful especially for the fire phenomenon investigation of the wall thermal conductivity coefficient and shape in the compartment space.

A Study on the Effect of Inflammable Materials on the Control Characteristics of Thermal and Smoke Fluid of Water Curtain System (가연성 물질에 따른 워터커튼 시스템의 열 및 연기유동 제어특성에 관한 연구)

  • You, Woo-Jun;Nam, Jun-Seok;Kim, Dong-Joon;Lee, Jeong-Kyoon;Ryou, Hong-Sun
    • Fire Science and Engineering
    • /
    • v.26 no.2
    • /
    • pp.53-58
    • /
    • 2012
  • In this study fire control characteristics for inflammable materials of water curtain system are experimentally analyzed. Heat release rate for pinewood and gasoline was calculated using Room Corner Tester (RCT) and fire test apparatus for water curtain system is manufactured. Nozzles (180 degree of injection angle, 8.2 mm of orifice diameter) are installed at the nearby ceiling of place at 5 m distance from fire originate and temperature profile as well as transmission are obtained from the fire experiment of pinewood and gasoline in the water curtain system. Based on the results, parameters of engineering importance for fire control characteristics of water curtain system such as generation of high temperature smoke and thermal phenomena of fluid flow by injection nozzle are identified.

An Experimental Study on the Warehouse Mock-up Fire Test (창고 모델 실물화재 특성에 대한 실험적 연구)

  • Kweon, Oh-Sang;Yoo, Yong-Ho;Kim, Heung-Youl
    • Fire Science and Engineering
    • /
    • v.24 no.4
    • /
    • pp.47-54
    • /
    • 2010
  • This study is analyze the damage of warehouse fire accident be made through the fire characteristic database of combustibles and real scale fire test of warehouse mock-up. Combustibles fire tests are carried out for database using RCT (Room Corner Tester) to predict fire growth the goods. A mockup ($3m{\times}3m{\times}2.4m$) of clothes warehouse was built and real scale fire test by LSC (Large Scale Calorimeter) base on the fire characteristic DB. The mock-up of clothes warehouse is made of two type sandwich panels (Glass wool, EPS foam sandwich panel). As a mock-up test result, test 1 (Glass wool sandwich panel) and test 2 (EPS foam sandwich panel) indicating fire growth such as 5 MW, 11 MW of maximum HRR (Heat Release Rate).

A Study on Carbon Monoxide and Other Gases During the Fire Test (A-class:1st Rating & B-class:1st Rating) (한국 A급, B급 1단위 화재 시험시 발생하는 일산화탄소 등의 정량적 연구)

  • Jeong, Incheon;Chung, Yeong-Jin
    • Fire Science and Engineering
    • /
    • v.27 no.5
    • /
    • pp.44-56
    • /
    • 2013
  • This research is to identify how much toxic combustion gases are produced from Korea standardized real fire test (Class A&B) by using Room Corner Tester (RCT) and how much those gases are possibly dangerous to testing personnel by estimating the level of carboxyhemoglobin (% COHb). It is confirmed that testing personnel can be affected as more than 40% COHb from Class A 9th and 10th rating in respiration minute volume (RMV) 2 and from Class A 5th to Class A 10th rating in RMV 3 during the time for initial three minutes. Also, in the case of Class B real fire tests, although it is considered rather safe for the initial 1 minute, testing personnel can be affected as more than 20% COHb from Class B 16th to 20th rating in RMV 3 during total test time. Currently, the Korea standard is only focusing on the protection measures against the heat, but the it is neglecting the protection measures against toxic combustion gases. Therefore, according to this study, it is strongly recommended that testing personnel should wear a self-contained breathing apparatus, or the equivalence depending on the real fire test rating.

The Study of a Correlation between Heat Release and Smoke Production by Using Oxygen Consumption Calorimeter Up to 10 MW Facility (10MW급 까지의 산소소모율법 칼로리미터를 활용한 열방출률과 연기발생률의 상관성에 관한 연구)

  • Ryu, Sang-Hoon;Yoo, Yong-Ho;Rie, Dong-Ho
    • Fire Science and Engineering
    • /
    • v.24 no.3
    • /
    • pp.58-65
    • /
    • 2010
  • The fire accidents having recently occurred are getting more and more larger and causing lots of damage in terms of property loss and casualties increase, so there is in need of technical fire safety development like comprehensive prevention solution in order to effectively prevent. Especially, the needing of new paradigm for advanced fire safe technology is gathering strength in high-rise modern building construction. Therefore, we want to find out on this paper what is a correlation between heat release rate measurement and smoke release volume by three parts of oxygen consumption calorimeter in bench scale calorimeter (cone calorimeter/ISO 5660/Avg.500Kw), Medium scale calorimeter (Room corner tester, Single burning Item/ISO 9750, EN 13823/Avg.3MW), and large scale calorimeter (Industry calorimeter/Avg. 10MW). Thus, Smoke detective of new paradigm devised by making use of a correlation between heat release and smoke production is to help reduce loss property and casualties. Ultimately, based on this theory, a new concept of fire alarm and evacuation system will be developed and expected to apply to a skyscraper.

The Study on Fire Characteristics of Furniture (가구류에 대한 화재 특성 연구)

  • Kweon, Oh-Sang;Yoo, Yong-Ho;Kim, Heung-Youl;Lim, Young-Soo
    • Proceedings of the Korea Institute of Fire Science and Engineering Conference
    • /
    • 2009.04a
    • /
    • pp.379-384
    • /
    • 2009
  • 본 연구에서는 다세대 주택에서 발생되는 화재에서 가연물질이 되는 가구류에 대한 화재 특성을 파악하기 위해 단위 가연물에 대한 열방출율(HRR, Heat Release Rate), 연기발생량, 유독가스 발생량 등에 대한 기본 DB를 확보하고자 하였다. 실험에 사용된 단위가연 물에는 침대(매트리스 포함), 장롱, 화장대, 책상, 책장, 소파(3+1인용), TV, 싱크대(찬장포함), 냉장고, 이불(옷가지)등 총 12여종이며, 국제 시험 규격인 ISO 9705 시험법인 중규모 시험 장치(Room Corner Tester)와 10MW 급의 실규모화재실험장치(Large Scale Calorimeter)에서 실험을 진행하였다. 실험결과 냉장고에서 가장 높은 최대 열방출율 약 3051 kW, 장롱에서의 일산화탄소 방출량은 최대 약 3894.2 ppm, 이산화탄소의 방출량은 최대 약 1.8% 로 가장 높게 측정되었다. 이러한 중규모 시험 장치를 통한 단위 품목의 화재특성 DB 작성은 단위구획에서의 화재 확산 예측에 가장 중요한 요소가 될 수 있을 것이다.

  • PDF