• Title/Summary/Keyword: Triple modular redundant controller

Search Result 3, Processing Time 0.026 seconds

Development of the Triple Modular Redundant Excitation System with Simulator for 500MW Synchronous Generator (500MW 동기발전기용 시뮬레이터 탑재형 디지털 삼중화 여자시스템 개발)

  • Ryu, Hoseon;Cha, Hanju
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.63 no.1
    • /
    • pp.70-75
    • /
    • 2014
  • TMR(triple modular redundant) digital excitation system with simulator is developed for tuning optimal control parameters during commissioning test and coping with system faults rapidly. A new system which mocks up virtual generator, turbine, grid can simulate as if excitation system is connected to a real generator system by setting four switches. The maintenance crew using the simulator is able to test perfectly the phase controller rectifiers, field breaker, sequence relays as well as TMR controller of the excitation system. Commissioning and performance results about the excitation system with simulator is discussed. The trial product was installed and operated at a 500MW thermal power plant after the commissioning test.

A Study of PWM Inverter for Field Control on Large Synchronous Generator (대형 동기 발전기 계자제어를 위한 PWM 인버터에 관한 연구)

  • Ryu, Ho-Seon;Lee, Joo-Hyun;Lim, Ick-Hun
    • Proceedings of the KIEE Conference
    • /
    • 2006.07b
    • /
    • pp.958-959
    • /
    • 2006
  • For the life extension of Jeju thermal power plant, digital PWM excitation system was replaced by KEPRI. This system consist of TMR(Triple Modular Redundant) controller, dual PWM power inverter for field current control and MMI etc. The Performance test during the commissioning verified the reliability of digital PWM excitation system and recently, this system has been operated successfully.

  • PDF

Voting System Bus Protocol for a Highly-Reliable PLC with Redundant Modules (다중화 구조 고신뢰성 제어기기를 위한 보팅 시스템버스 프로토콜)

  • Jeong, Woohyuk;Park, Jaehyun
    • Journal of Institute of Control, Robotics and Systems
    • /
    • v.20 no.6
    • /
    • pp.689-694
    • /
    • 2014
  • An SPLC (Safety Programmable Logic Controller) must be designed to meet the highest safety standards, IEEE 1E, and should guarantee a level of fault-tolerance and high-reliability that ensures complete error-free operation. In order to satisfy these criteria, I/O modules, communication modules, processor modules and bus modules of the SPLC have been configured in triple or dual modular redundancy. The redundant modules receive the same data to determine the final data by the voting logic. Currently, the processor of each rx module performs the voting by deciding on the final data. It is the intent of this paper to prove the improvement on the current system, and develop a voting system for multiple data on a system bus level. The new system bus protocol is implemented based on a TCN-MVB that is a deterministic network consisting of a master-slave structure. The test result shows that the suggested system is better than the present system in view of its high utilization and improved performance of data exchange and voting.