• Title/Summary/Keyword: Underground lot ventilation

Search Result 22, Processing Time 0.033 seconds

A Study on Estimation of Ventilation Performance in the Underground Parking Lot (지하 주차장의 환기성능평가에 관한 연구)

  • Hwang, Min-Kyu;Kim, Seong-Sik;Kim, Kang-Soo
    • Journal of the Korean Solar Energy Society
    • /
    • v.27 no.3
    • /
    • pp.71-77
    • /
    • 2007
  • In past, parking lot was placed on the ground and for the reason air quality was not in problem. But recently parking lot has been placed under the ground and the air quality becomes problem. So in this study, the ventilation performance on the underground parking lot was estimated by using CFD software and alternative system was suggested. Three case studies are handled in this study. 1st case is just an underground parking lot. 2nd case is about an underground parking lot where has 4 fan rooms on each floor and 3rd case is about an underground parking lot where has 4 fan rooms and 30 guidance fans on each floor.

Energy and Air Quality Benefits of DCV with Wireless Sensor Network in Underground Parking Lots

  • Cho, Hong-Jae;Jeong, Jae-Weon
    • International Journal of High-Rise Buildings
    • /
    • v.3 no.2
    • /
    • pp.155-165
    • /
    • 2014
  • This study measured and compared the variation of ventilation rate and fan energy consumption according to various control strategies after installing wireless sensor-based pilot ventilation system in order to verify the applicability of demand-controlled ventilation (DCV) strategy that was efficient ventilation control strategy for underground parking lot. The underground parking lot pilot ventilation system controlled the ventilation rate by directly or indirectly tracking the traffic load in real-time after sensing data, using vehicle detection sensors and carbon monoxide (CO) and carbon dioxide ($CO_2$) sensor. The ventilation system has operated for 9 hours per a day. It responded real-time data every 10 minutes, providing ventilation rate in conformance with the input traffic load or contaminant level at that time. A ventilation rate of pilot ventilation system can be controlled at 8 levels. The reason is that a ventilation unit consists of 8 high-speed nozzle jet fans. This study proposed vehicle detection sensor based demand-controlled ventilation (VDS-DCV) strategy that would accurately trace direct traffic load and CO sensor based demand-controlled ventilation (CO-DCV) strategy that would indirectly estimate traffic load through the concentration of contaminants. In order to apply DCV strategy based on real-time traffic load, the minimum required ventilation rate per a single vehicle was applied. It was derived through the design ventilation rate and total parking capacity in the underground parking lot. This is because current ventilation standard established per unit floor area or unit volume of the space made it difficult to apply DCV strategy according to the real-time variation of traffic load. According to the results in this study, two DCV strategies in the underground parking lot are considered to be a good alternative approach that satisfies both energy saving and healthy indoor environment in comparison with the conventional control strategies.

A Strategies to Improve the Natural Ventilation Performance at Underground Parking Lot in Multi-Residential Buildings (공동주택 지하주차장의 자연환기성능 향상방안에 관한 연구)

  • Seo, Jung-Min;Lee, Joong-Hoon;Song, Jong-Eui;Jung, Jung-Hwa;Song, Doo-Sam
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.23 no.2
    • /
    • pp.153-163
    • /
    • 2011
  • Energy efficiency and indoor air quality have become main issue to develop healthy and sustainable building in these days. As an effort to reduce the energy consumption in multi-residential building, many attempts as like passive design strategies and renewable energy as well as active control method are tried. However, underground parking lot in multi-residential building seldom adopt the sustainable strategies and only mechanical system is installed as usual. Moreover, the mechanical system installed in underground parking lot is rarely operated due to the electric demand for operation after completion. In this study, as an energy efficient measure, natural ventilation system using stack effect as a driving force for underground parking lot will be proposed and the performance of the suggested system will be analyzed by simulation method.

The Effect of Ventilation and Concentration of Indoor Air Quality at Indoor Parking Lots (실내주차장의 실내공기질 농도특성 및 환기에 의한 저감효과)

  • Park, Jeong-Ho
    • Journal of Korean Society of Occupational and Environmental Hygiene
    • /
    • v.20 no.4
    • /
    • pp.241-247
    • /
    • 2010
  • Recently, indoor air quality (IAQ) has been one of the major concerns of people. Indoor parking lots are subject to be exposed to high concentrations of air pollutants emitted from vehicles. This study was performed to investigate indoor air quality (IAQ) at indoor parking lots. Sampling sites were selected 5 indoor parking lots. Target indoor air quality parameters include a number of criteria pollutants such PM$_{10}$, CO, CO$_2$, and HCHO. In addition, a variation of IAQ according to ventilation system operating was measured at C site (underground parking lot). In general, all pollutants were maintained below indoor air quality maintenance standards. The indoor air quality at indoor parking lots was affected by the availability of the ventilation facility and their operation frequency. At the underground parking lot (C site) with ventilation system, TVOC concentration according to ventilation system operating were found to be lower operating (488.2 ${\mu}g/m^3$) than non-operating (1,401.2 ${\mu}g/m^3$).

Numerical Simulation on Ventilation Characteristics of an Underground Bus Parking Lot (버스전용 지하주차장의 환기 특성에 관한 수치해석적 연구)

  • Seung, Sam-Sun;Lee, Seung-Chul
    • Journal of the Korea Academia-Industrial cooperation Society
    • /
    • v.8 no.2
    • /
    • pp.179-184
    • /
    • 2007
  • In this paper, the ventilation characteristics of an underground parking lot with 17 buses has been investigated for two cases by computational fluid dynamics. It has been found that the average concentration of CO and $NO_x$ gas in the parking lot were 1.3 and 0.3 ppm respectively, when four buses operated. When the fifteen vehicles stopped in the parking lot, the average concentration of CO and $NO_x$ gas was 2.9 and 0.8 ppm respectively. The average concentration of two pollutants$(CO,\;NO_x)$ are lower than the standard values. Therefore the facilities and its location is proper to ventilation.

  • PDF

A Study on Ventilation Performance driven by Wind Force in Underground Parking Lots of Apartment - Influence of Opening Size and Surrounding Building - (공동주택 지하주차장의 풍력환기 성능에 관한 연구 - 환기구 면적 및 주변건물의 영향 -)

  • Roh, Ji Woong
    • KIEAE Journal
    • /
    • v.12 no.1
    • /
    • pp.29-34
    • /
    • 2012
  • As a series of studies about natural ventilation driven by wind in basement parking lots of apartment, the influence of opening size and surrounding buildings on ventilation rate was analyzed. Natural ventilation in underground parking lots almost rely on wind than temperature difference. To investigate natural ventilation driven by wind, wind tunnel tests by using scale model and tracer gas method were conducted. $CO_2$-gas concentration was measured, natural ventilation rates were calculated. The experimental results showed that the natural ventilation rate is more reliable to wind direction and surrounding building than opening size and distance between buildings. It was verified that surrounding buildings play a principal role in increasing air flow rate by accelerating wind speed, and growing turbulence intensity. And it showed that ventilation performance is able to be increased by oblique wind to entrance ramp than head on wind in underground parking lots with surrounding buildings.

Numerical Evaluation of CO Gas Distribution in Underground Parking Lot (지하주차장 내부 일산화탄소 가스 분포의 전산 해석적 평가)

  • Kim Jae Won;Ham Kyoung-A
    • Journal of computational fluids engineering
    • /
    • v.7 no.2
    • /
    • pp.33-42
    • /
    • 2002
  • Numerical estimation for concentration of mono-carbon oxygen (CO) gas inside an underground parking lot with auxiliary jet fans for enhancement of ventilation is carried out by using a commercial program. Main interest lies on the diagnosis of the present ventilation system including position and selection of auxiliarly fans in addition to main suppliers and exhausts. Details of both flows and concentration of CO gas that is most important component among car exhaust gases are illustrated in this investigation and those are presented for engineering construction of an underground parking pool. Prediction data of computational work is also validated by real measurements of concentration of CO gas.

A NUMERICAL SIMULATION OF HYDROGEN DIFFUSION FOR THE HYDROGEN LEAKAGE FROM FCV IN UNDERGROUND PARKING LOT (지하주차장 내 수소연료 자동차의 수소 누설로 인한 수소 확산에 대한 수치해석 연구)

  • Choi, J.;Hur, N.;Lee, E.D.;Lee, K.B.
    • 한국전산유체공학회:학술대회논문집
    • /
    • 2011.05a
    • /
    • pp.477-482
    • /
    • 2011
  • In the present study, the diffusion process of hydrogen leaking from a FCV (Fuel Cell Vehicle) in an underground parking lot was analyzed by numerical simulations in order to assess the risk of a leakage accident. The temporal and spatial changes of the hydrogen concentration as well as the flammable region in the parking lot were predicted numerically. The effects of the leakage flow rate and an additional ventilation fan were investigated to evaluate the ventilation performance in the parking lot to relieve the accumulation of the leaked hydrogen gas. The present numerical analysis can provide useful information such as the distribution of the leaked hydrogen concentration for safety of various hydrogen applications.

  • PDF

Professional Engineer Yard: A study on Preventing Floor Surface Condensation in Consideration of Thermal Characteristic of Underground Parking lot in an apartment (기술사마당: 공동주택 지하주차장의 열적특성을 고려한 바닥 표면결로방지 방안에 관한 연구)

  • Seo, Yong-Won
    • Journal of the Korean Professional Engineers Association
    • /
    • v.44 no.4
    • /
    • pp.44-49
    • /
    • 2011
  • For the pleasant dwelling place, the most of apartments are designed with the increased green area ratio in ground space and the underground parking lot. However, the condensation in underground space has occasionally occurred due to the insufficient ventilation and insulation treatment. Despite reinforcement of the insulation treatment and mechanical ventilation for the preventing method of condensation. It seems difficult to expect preventing effects for the condensation without consideration of the thermal characteristic of structures. Furthermore, no fundamental measure has been established because maintenance work for these defects incurs a lot of costs and these defects could be occurred again. This study suggests a new method for preventing floor surface condensation through analyzing the reasons of condensation which occurred in the underground floor.

  • PDF

A Study on the Plans of Apartments Underground Parking lots to Prevent Women's Criminal fear Psychology - Focused on apartment design competitions of Suwon A region - (여성의 범죄불안심리를 고려한 공동주택의 지하주차장 계획 연구 - 수원A지구 공동주택 현상설계를 중심으로 -)

  • Li, Jin-Ji;Kim, Nam-Hyo
    • Korean Institute of Interior Design Journal
    • /
    • v.18 no.6
    • /
    • pp.104-114
    • /
    • 2009
  • The purpose of study was understanding necessity of environment design for underground parking lot in residential design plan and grasping design plans of 'Activity Support' that considerate women, exclude women's unsecured feeling at underground parking lot. The inquiry analyzed 6 design plan in design competition that considerate women according to precede studies, a theory of CPTED, a design guide for wayfinding, and survey. A ramp, circulation, entrance, lighting, ventilation, and space design plan are proceed on this study The result are as below. First, a rectilinear figure ramp suits entrance plan on the circulation, but if it is not possible, cross-using of rectilinear and curvilinear figure ramp plan is desirable. Second, on the circulation plan, vehicles circulation plan and equality parking distribution plan got accomplished generally, and help senses of direction because it is planed network systemize. On a large scale underground parking lot, simplify parking circulation to convenience entrance and exit for weak in sense of direction. Third, the shape and material that‘s environmentally conscious will be in use to the entrance plan. As the first stage to the underground, artwork that women prefer can modulate the rejection of underground space. Forth, natural lighting system and ventilation can make the environment-friendly space, decrease the women’s rejection to the underground, it can also keep a natural watch on the space. Fifth, on the space design plan, it can use bright and comfortable design of wall and ground to decrease the women‘s rejection, also it is useful to the sense of direction. LED indirect lighting plan that 58.7% of women prefers on survey reflects women’s state of desire that bright and atmosphere. In addition, proper use of plans that subsidiary facilities, rest area with Sunken, and nature-friendly material can minimize differences of underground and ground parking lot.