• Title/Summary/Keyword: Untransposed transmission lines

Search Result 7, Processing Time 0.028 seconds

A New fault Location Algorithm for 765㎸ Untransposed Parallel Transmission Lines (765㎸ 비연가 송전선로에서 고장점 표정 알고리즘)

  • 안용진;강상희
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.53 no.3
    • /
    • pp.168-174
    • /
    • 2004
  • This paper describes a new fault location algorithm based on the voltage equation at the relaying point using 6-phase current for untransposed 765㎸ parallel transmission lines. The proposed method uses the voltage and current collected at only the local end. By means of 3-phase circuit analysis theory to compensate the mutual coupling effects between parallel lines, the fault location is derived. The fault distance is determined by solving the 2nd distance equation based on KVL(Kirchhoff's Voltage Law). Extensive simulation results using EMTP(Electromagnatic Transients Program) have verified that the error of the fault location achieved is up to 4.56(%) in untransposed parallel transmission lines.

A New Distance Relaying Algorithm Immune to Mutual Coupling Effect and Reactance Effect for 765kV Untransposed Parallel Transmission Lines (상호결합효과와 리액턴스효과를 제거한 765kV 비연가 송전선로 보호용 거리계전 알고리즘)

  • Ahn Yong-Jin;Kang Sang-Hee
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.54 no.1
    • /
    • pp.25-30
    • /
    • 2005
  • An accurate digital distance relaying algorithm which is immune to mutual coupling effect and reactance effect of the fault resistance and the load current for the line faults in 765kV untransposed transmission lines is proposed. The algorithm can estimate adaptively the impedance to a fault point independent of the fault resistance. To compensate the magnitude and phase of the apparent impedance, this algorithm uses the angle of an impedance deviation vector. The impedance correction algorithm for phase-to-ground fault and phase-to-phase short fault use a voltage equation at fault point to compensate the fault current at fault point. A series of tests using EMTP output data in a 765kV untransposed transmission lines have proved the accuracy and effectiveness of the proposed algorithm.

A Study on the Transient Characteristics in 765kV Untransposed Transmission Systems (765kV 비연가 송전계통 과도 특성에 관한 고찰)

  • 안용진;강상희
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.53 no.7
    • /
    • pp.397-404
    • /
    • 2004
  • This paper describes a study of transient characteristics in 765kV untransposed transmission lines. As the 765(kV) system can carry bulk power, some severe fault on the system nay cause large system disturbance. The large shunt capacitance and small resistance of 765kv transmission line make various difficulties for its protection. These problems including current difference between sending and receiving terminals on normal power flow, low order harmonic current component in fault current and current transformer saturation due to the long DC time constant of the circuit etc. must be investigated and solved. The analysis of transient characteristics at sending terminal has been carried out for the single phase to ground fault and 3-phase short fault, etc. The load current, charging current in normal condition and line flows, fault current, THD(Total Harmonic Distortion) of harmonics, time constants have been analysed for the 765kV untransposed transmission line systems.

Estimation of Fault Location on Transmission Lines using Current Phasor (전류 페이저를 이용한 송전선로 고장점 추정 알고리즘)

  • Yeo, Sang-Min;Kim, Chul-Hwan
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.58 no.11
    • /
    • pp.2095-2100
    • /
    • 2009
  • Since most of the Extra High Voltage (EHV) transmission lines are untransposed and multi-circuits, errors are occurred inevitably because of the unbalanced impedances of the lines and so on. Therefore, a distance relaying algorithm applicable to the untransposed multi-circuits transmission lines needs to be developed. The proposed algorithm of fault location estimation in the paper uses the fundamental phasor to reduce the effects of the harmonics. This algorithm also analyzes the second-order difference of the phasor to calculate the traveling times of waves generated by faults. The traveling time of the waves generated by faults is derived from the second-order difference of the phasor. Finally, the distance from the relaying point to the faults is estimated using the traveling times. To analyze the performance of the algorithm, a power system with the EHV untransposed double-circuit transmission lines are modeled and simulated under various fault conditions such as several fault types, fault locations, fault inception angles and fault resistances. The results of the simulations show that the proposed algorithm has the capability to estimate the fault locations quickly and accurately.

A New Distance Relaying Algorithm for Phase-to-Ground Fault in 765kV Untransposed Transmission Lines (765kV 비연가 송전선로에서 단상지락고장 시어 거리개전 알고리즘)

  • AHN YONG JIN;KANG SANG HEE
    • Proceedings of the KIEE Conference
    • /
    • summer
    • /
    • pp.452-454
    • /
    • 2004
  • An accurate digital distance relaying algorithm which is immune to reactance effect of the fault resistance and the load current for phase-to-ground fault in 765kV untransposed transmission lines is proposed. The algorithm can estimate adaptively the impedance to a fault point independent of the fault resistance. To compensate the magnitude and phase of the apparent impedance, this algorithm uses the angle of an impedance deviation vector. The impedance correction algorithm for Phase-to-ground fault uses a voltage equation at fault point to compensate the fault current at fault point. A series of tests using EMTP output data in a 765kV untransposed transmission lines have proved the accuracy and effectiveness of the proposed algorithm.

  • PDF

A New Distance Relaying Algorithm for Phase-to-Phase Short Fault in 765kV Untransposed Transmission Lines (765kV 비연가 송전선로에서 상간단락고장 시어 거리계전 알고리즘)

  • AHN YONG JIN;KANG SANG HEE
    • Proceedings of the KIEE Conference
    • /
    • summer
    • /
    • pp.455-457
    • /
    • 2004
  • An accurate digital distance relaying algorithm which is immune to reactance effect of the fault resistance and the load current for phase-to-phase short fault in 765kV untransposed transmission lines is proposed. The algorithm can estimate adaptively the impedance to a fault point independent of the fault resistance. To compensate the magnitude and phase of the apparent impedance, this algorithm uses the angle of an impedance deviation vector. The impedance correction algorithm for phase-to-phase short fault uses a voltage equation at fault point to compensate the fault current at fault point. A series of tests using EMTP output data in a 765kv untransposed transmission lines have proved the accuracy and effectiveness of the proposed algorithm.

  • PDF

Algorithm for Fault Location Estimation on Transmission Lines using Second-order Difference of a Positive Sequence Current Phasor

  • Yeo, Sang-Min;Jang, Won-Hyeok;Kim, Chul-Hwan
    • Journal of Electrical Engineering and Technology
    • /
    • v.8 no.3
    • /
    • pp.499-506
    • /
    • 2013
  • The accurate estimation of a fault location is desired in distance protection schemes for transmission lines in order to selectively deactivate a faulted line. However, a typical method to estimate a fault location by calculating impedances with voltages and currents at relaying points may have errors due to various factors such as the mutual impedances of lines, fault impedances, or effects of parallel circuits. The proposed algorithm in this paper begins by extracting the fundamental phasor of the positive sequence currents from the three phase currents. The second-order difference of the phasor is then calculated based on the fundamental phasor of positive sequence currents. The traveling times of the waves generated by a fault are derived from the second-order difference of the phasor. Finally, the distance from the relaying point to the fault is estimated using the traveling times. To analyze the performance of the algorithm, a power system with EHV(Extra High Voltage) untransposed double-circuit transmission lines is modeled and simulated under various fault conditions, such as several fault types, fault locations, and fault inception angles. The results of the simulations show that the proposed algorithm has the capability to estimate the fault locations with high speed and accuracy.