• Title/Summary/Keyword: flicker mitigation

Search Result 17, Processing Time 0.038 seconds

Analysis of Flicker Mitigation Effects using IEC Digital Flickermeter based on Matlab/Simulink Simulation (Matlab/Simulink 기반의 IEC 플리커미터를 이용한 플리커 저감효과 모의에 대한 연구)

  • Jung, Jae-Ahn;Cho, Soo-Hwan;Kwon, Sae-Hyuk;Jang, Gil-Soo;Kang, Moon-Ho
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.58 no.2
    • /
    • pp.232-238
    • /
    • 2009
  • Flicker, also known as voltage fluctuation, is a newest problem of power quality issues, because it is caused by nonlinear loads such as electrical arc furnace and large-scale induction motor, which are country-widely used as the heavy industries of a country develop. An international standard, International Electrotechnical Commission (IEC) 61000-4-15, was published in 1997 and revised in 2003. With increasing concerns about flicker, its mitigation methods have been also studied. General countermeasures for flicker are divided into three categories: a) enhancing the capacity of supplying system, b) Series elements including series reactor and series capacitor and c) power electronic devices including static VAR compensator (SVC) and static synchronous compensator (STATCOM). This paper introduces how to mitigate the voltage flicker at the point of common coupling (PCC) and presents how to simulate and compare the flicker alleviating effects by each mitigation method, using IEC flickermeter based on the Matlab/Simulink program.

Flicker Mitigation in a Wind Farm by Controlling a Permanent Magnet Synchronous Generator (영구자석형 동기발전기를 이용한 풍력단지의 플리커 저감)

  • Hoan, Pham Van;Kim, Dae-Hyun;Ahn, Jin-Hong;Kim, Eel-Hwan;Oh, Seong-Bo;Kim, Ho-Chan;Kim, Se-Ho
    • Journal of Institute of Control, Robotics and Systems
    • /
    • v.15 no.12
    • /
    • pp.1163-1168
    • /
    • 2009
  • The power quality of wind energy becomes more and more important in connecting wind-farms to the grid, especially weak grid. This paper presents the simulation of a wind farm of a permanent magnet synchronous generator (PMSG) and a doubly fed induction generator (DFIG). Flicker mitigation is performed by using PMSG as a static synchronous compensator (STATCOM) to regulate the voltage at the point of common coupling (PCC). A benefit of the measure is that integrating two function of to control the active power flow and to reduce the voltage flicker in a wind farm. Simulation results show that controlling PMSG is an effective and economic measure in reducing the flicker during continuous operation of grid connected wind turbines regardless of short circuit capacity ratio, turbulence intensity and grid impedance angle.

Parallel Coding Scheme for Flicker Mitigation in MIMO-VLC (다중입출력 가시광통신에서 플리커 현상을 완화하기 위한 병렬 코딩 기법)

  • Jeong, Jin-uk;Lee, Kye-san;Seo, Hyo-duck;Han, Doo-hee;Lee, Kyu-jin
    • The Journal of The Korea Institute of Intelligent Transport Systems
    • /
    • v.15 no.3
    • /
    • pp.146-154
    • /
    • 2016
  • Visible light communication using LED is a technique for transmitting digital data using the light of the LED. Recently, high-speed data rate plays an important role. Therefore, many scholars have researched the MIMO-VLC which is able to increase data rate using a lot of LED transmitters. However, it has problems such as light interference and flicker when transmitting different bit. Many researcher have focused on reduce interference. However it is not considered about flicker problem. Flicker is defined unstable brightness. It occurred the tired of human eyes, lowers eyesight and also decreases concentration. In order to solve this flicker problem in MIMO-VLC, we propose the PFM(Parallel Flicker Mitigation) code. PFM code using combinatorial theory can maintain constant brightness the whole bit duration. Therefore, it is possible to assure the brightness by confirm simulation results.

Analysis of the Distribution STATCOM for Improving the power factor and Mitigation of Voltage Flicker in Real System (전압플리커 저감과 역률 보상 기능을 갖는 배전용 STATCOM의 실계통연계 운전결과 분석)

  • Oh, Kwan-Il;Jeon, Young-Soo;Park, Sang-Tae;Choo, Jin-Boo
    • Proceedings of the KIEE Conference
    • /
    • 2000.07a
    • /
    • pp.245-248
    • /
    • 2000
  • This paper presents the test and operation results of the domestic demonstration of the reactive power compensation device called STATCOM (STATic COMpensator). The object of the paper is to describe the reliability of the unit based on the extensive operation databases. By controlling reactive power, the technology offers utilities the opportunity for increased efficiency and their capabilities will permit transmission planners make the best use of their existing transmission resources STATCOM is a custom power device in a way and can be used in a similar way for the dynamic compensation of power transmission systems, mitigation of voltage flicker and improving the power factor. It is shown that the STATCOM has clear advantages in areas such as: mitigation of voltage flicker and improving power factor.

  • PDF

Flicker Suppression Scheme for Variable-Speed Wind Turbine Systems

  • Van, Tan Luong;Nguyen, Thanh Hai;Lee, Dong-Choon
    • Journal of Power Electronics
    • /
    • v.12 no.2
    • /
    • pp.333-343
    • /
    • 2012
  • This paper proposes a strategy of flicker mitigation for doubly-fed induction generator (DFIG) wind turbine systems. In the weak grid system where the grid impedance ratio is low, the reactive power compensation only cannot suppress the flicker sufficiently due to the limited power capacity of the converters or the DFIG. For the full suppression of flickers, the active power smoothening using the energy storage system (ESS) needs to be utilized together with the reactive power compensation. The effectiveness of the proposed method is verified by PSCAD/EMTDC simulation results for a 2[MW] DFIG wind turbine system and by experimental results for a 3[kW] wind turbine simulator.

Comparative Simulation of flicker Mitigating Efficiencies of Various Compensating Devices using Matlab/Simulink (Matlab/Simulink를 이용한 무효전력 보상장치의 플리커 저감 효과 연구)

  • Jung, Jae-Ahn;Cho, Soo-Hwan;Jang, Gil-Soo;Kang, Moon-Ho
    • Proceedings of the KIEE Conference
    • /
    • 2008.07a
    • /
    • pp.83-84
    • /
    • 2008
  • Voltage fluctuation, also known as flicker, is a power quality problem caused by nonlinear loads like electric arc furnace. Since it is interpreted as a variation of the supplied electrical energy, it causes the residential customers to feel much annoyed visually through the lamps. Due to the statistical nature of IEC (International Electrotechnical Commission) short-term flicker severity index, Pst, it is not feasible to pre-evaluate the flicker level using the transient power system simulators such as Sim Power System in Matlab/Simulink. So this paper presents not only how to design the Matlab/Simulink IEC flickermeter to yield the Pst value, which considering electric distribution environments of South Korea, but also how to mitigate the voltage flicker at the Point of Common Coupling (PCC). In order to achieve this, the flicker mitigation efficiencies of various compensating devices, such as Static Var Compensator (SVC), STATCOM will be applied and compared. The simulated result demonstrates which compensating equipment is the most efficient method to mitigate the flicker phenomenon.

  • PDF

A Study on the Fliker Effect of SVC in Electric Arc Furnace Loads (전기로 부하에서 SVC의 플리커 효과에 관한 연구)

  • Kim, Kyung-Chul;Jin, Seong-Eun;Lee, Il-Moo
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.20 no.8
    • /
    • pp.48-53
    • /
    • 2006
  • An electric arc furnace being used in the steel industry is a time-varying non-linear load causing voltage fluctuations to the power system. Flicker can be defined as the effect produced on the human visual perception by a changing emission of light lamps subjected to magnitude fluctuations of their supply voltage. The level of flicker depends on the amplitude, frequency and duration of the voltage fluctuations. In this paper, the voltage fluctuation problem in an 154[kV] system due to the electric arc furnace loads is investigated and the analysis results of the static var compensator application for the voltage flicker mitigation are presented and evaluated by the IEC 61000-3-7.

Analysis of the Distribution STATCOM Operating Results for Improving Distribution System Power Quality (전력품질 향상을 위한 배전용 STATCOM 운전결과 분석)

  • 오관일;전영수;박상태;추진부
    • The Transactions of the Korean Institute of Power Electronics
    • /
    • v.5 no.4
    • /
    • pp.377-385
    • /
    • 2000
  • This paper presents the test and operation results of the domestic demonstration of the reactive power compensation device called STATCOM (STATic COMpensator). The object of the paper is to describe the reliability of the unit based on the extensive operation databases. The custom power is similar in nature to the concept of FACTS(Flexibel AC Transmission System). By controlling reactive power, the technology offers utilities the opportunity for increased efficiency and their capabilities will permit transmission planners make the best use of their existing transmission resources. STATCOM is a custom power device in a way and can be used in a similar way for the dynamic compensation of power transmission systems, providing reactive power compensation, voltage regulation and mitigation of voltage flicker. It is shown that the STATCOM has clear advantages in areas such as; providing reactive power compensation and improving power factor.

  • PDF

Experimental Study on Flicker Mitigation in VLC using Pseudo Manchester Coding (VLC에서 Pseudo Manchester Coding을 사용한 Flicker 최소화에 관한 실험 연구)

  • Ifthekhar, Md. Shareef;Le, Nam-Tuan;Jang, Yeong Min
    • Journal of Satellite, Information and Communications
    • /
    • v.9 no.3
    • /
    • pp.116-120
    • /
    • 2014
  • Visible Light Communication is one of the promising technologies for wireless communication due to the possibility to use existing LED lightening infrastructure to transmit data. LED has the ability to turn on and off very fast enough that our human eyes can't recognize so it can be used to transmit data via visible light along with illumination. But it faces flicker problem due to the brightness discrepancies between '1' and '0' bit patterns inside a data frame. Various run length limited (RLL) coding scheme like Manchester code, 4B6B, 8B10B or VPPM can be used to solve flickering problem. So we propose pseudo Manchester codding which can transmit data without modifying LED modulator and demodulator circuit as well as solve flickering problem.

Electric Arc Furnace Voltage Flicker Mitigation by Applying a Predictive Method with Closed Loop Control of the TCR/FC Compensator

  • Kiyoumarsi, Arash;Ataei, Mohhamad;Hooshmand, Rahmat-Allah;Kolagar, Arash Dehestani
    • Journal of Electrical Engineering and Technology
    • /
    • v.5 no.1
    • /
    • pp.116-128
    • /
    • 2010
  • Modeling of the three phase electric arc furnace and its voltage flicker mitigation are the purposes of this paper. For modeling of the electric arc furnace, at first, the arc is modeled by using current-voltage characteristic of a real arc. Then, the arc random characteristic has been taken into account by modulating the ac voltage via a band limited white noise. The electric arc furnace compensation with static VAr compensator, Thyristor Controlled Reactor combined with a Fixed Capacitor bank (TCR/FC), is discussed for closed loop control of the compensator. Instantaneous flicker sensation curves, before and after accomplishing compensation, are measured based on IEC standard. A new method for controlling TCR/FC compensator is proposed. This method is based on applying a predictive approach with closed loop control of the TCR/FC. In this method, by using the previous samples of the load reactive power, the future values of the load reactive power are predicted in order to consider the time delay in the compensator control. Also, in closed loop control, two different approaches are considered. The former is based on voltage regulation at the point of common coupling (PCC) and the later is based on enhancement of power factor at PCC. Finally, in order to show the effectiveness of the proposed methodology, the simulation results are provided.