• Title/Summary/Keyword: gurad lamp

Search Result 1, Processing Time 0.014 seconds

Development of Remote Supervision System for Guam Lamps by Way of Leakage Current(Igr) Detection Method (보안등 전거설비의 Igr 누설전류 검출 및 원격감시장치 개발)

  • Choi, Myeong-Il;Kim, Young-Seok;Kim, Chong-Min;Bang, Sun-Bae
    • Journal of the Korean Society of Safety
    • /
    • v.25 no.6
    • /
    • pp.75-80
    • /
    • 2010
  • The present study presented the implementation of a remote control/supervision system for guard lamps used in public illumination with little endeavor by far for safe management, which makes possible to supervise the state and to control the functions remotely including electric safety elements. Especially, the developed system adopts the measurement algorithm for detecting resistive leakage current(Igr) flowing based on the phase difference checkable for sensing at a monitor, being allowable for monitoring at MMI and transmitter for data transmittance. To verify reliability about the algorithm to accurately detect Igr leakage current, the laboratory-based functional test was performed.