A Study on the Reclosing Overvoltage in 345 [kV] Transmission Line

345kV 계통 재투입과 전압 해석

  • Published : 1990.11.17

Abstract

The purpose of the circuit breaker on power system is to disconnect the faulty part from the system and to maintain the integrity of the system. With switching overvoltages are generated. When the system voltages become higher, switching overvoltage is important factor in insulation co-ordination. Since the no-load reclosing overvoltage with inductive source is severe, this paper deals with the reclosing overvoltage and the effect of closing resistor. This reclosing overvoltage of 27-bus model system with and without closing resistor is analyzed by using EMTP (Electro-Magnetic Transients Program) for both deterministic and Stochastic model.