Proceedings of the KIEE Conference (대한전기학회:학술대회논문집)
- 1996.11a
- /
- Pages.267-269
- /
- 1996
Effect of the Inner Side Dielectric Coating of the Tank on the Particle Movement for Improving of GIS Insulation Reliability
GIS 절연 신뢰성 향상을 위한 탱크 내면 코팅이 파티클 거동에 미치는 영향
- Lee, Bang-Wook (Dept. of Electrical Eng. HanYang University) ;
- Koo, Ja-Yoon (Dept. of Electrical Eng. HanYang University) ;
- Kim, Min-Kyu (High Voltage Team, KERI) ;
- Kim, Ik-Soo (High Voltage Team, KERI)
- Published : 1996.11.16
Abstract
In this work, the influence of wire type conducting particles on the insulation reliability of GIS has been systematically investigated when outer electrode was dielectric coated by epoxy resin. For this purpose, coaxial cylinder-type electrode was adopted in 362 kV chamber and various size of Cu conducting particle was used and different gas pressure was applied. To prove the coating effect on the gas insulation, different thickness of epoxy coated outer electrode have been considered and the lift-off voltage and flashover voltage have been analyzed. The results show that the dielectric coated electrode has an remarkable influence on the reducing particle behavior in GIS system and enhancing the GIS insulation reliability.
Keywords