반도전 재료를 이용한 Resistivity grading 방식의 XLPE절연 전력케이블용 시험단말에 관한 연구

A study on the application of testing termination for XLPE Power Cable by Resistivity Grading Method Using Semi-conductive material

  • 이창영 (LG 전선 (주) 전력연구소) ;
  • 신두성 (LG 전선 (주) 전력연구소) ;
  • ;
  • 김동욱 (LG 전선 (주) 전력연구소) ;
  • 박완기 (LG 전선 (주) 전력연구소)
  • Lee, C.Y. (LG Cable Ltd. Electric Power Research&Technology Center) ;
  • Shin, D.S. (LG Cable Ltd. Electric Power Research&Technology Center) ;
  • Dudkin, Sergey M. (LG Cable Ltd. Electric Power Research&Technology Center) ;
  • Kim, D.W. (LG Cable Ltd. Electric Power Research&Technology Center) ;
  • Park, W.K. (LG Cable Ltd. Electric Power Research&Technology Center)
  • 발행 : 1999.11.20

초록

The purpose of termination for high voltage tests of XLPE power cable is to prevent flashover during the breakdown test of specimen as well as to withstand the specified voltage between its conductor and screen without failure. For easier treatment and simpler construction of testing termination, resistivity grading method using semi-conductive material was employed. Based on the fundamental theory, its failure characteristics by changing the resistivity of semi-conductive material on the insulation surface was investigated. With two layers construction by difference resistivity on their surfaces, much improved result than that of one resistivity was obtained through the experiment for MV cable.

키워드