고분자 애자의 시멘트 분진에 의한 특성 변화 연구

Properties of composite insulators stuck by cement powder

  • Lee, Sang-Jin (Electric Power Research & Technology Center, LG Cable Ltd.) ;
  • Kim, Dong-Wook (Electric Power Research & Technology Center, LG Cable Ltd.) ;
  • Choi, Myung-Kyu (Electric Power Research & Technology Center, LG Cable Ltd.)
  • 발행 : 2000.07.17

초록

When insulators are operated near cement factories, some amount of cement powder may be stuck on the surface of insulators and decreases their electrical performances. Three kinds of insulators, such as, silicone EPDM and porcelain insulators, are tested in this paper. Testing Voltage of 25kV is applied to the samples, and surface leakage current is measured for 6 months after cement solvent of 10 vol% was stuck on the surface of each insulator in the laboratory. Insulation layers are cut from 3 and 6 month-aged insulators and tested for ac breakdown, impulse breakdown, contact angle. After aging, electrical properties are unchanged in silicone and EPDM insulators but show some changes in porcelain insulators.

키워드