반사파를 이용한 지중케이블의 고장점 탐지연구

Fault Location of Underground Cables Using Travelling Wave

  • 발행 : 2000.07.17

초록

In this paper, we made an experiment on fault location of underground cables with travelling wave. The 5C2V coaxial cables of 100, 200m length, connected with discharge gap, are used for simplifying model cable lines of power cable. And 100KHz -2MHz CT and HV probe are installed at one side of the ends. We made travelling pulse in discharge gab and then pulse travelled along the cable to the both ends. Therefore, it is detected in CT and HV probe. Measuring the time difference of the pulse start and arrival, we were able to obtain the distance of pulse travelling. Consequently, our experimental results show the possibility to detect fault location of underground cables with travelling wave.

키워드