Constant power. high power factor drive of DFIG for wind power generation in the wide wind speed

넓은 풍속에서의 풍력발전용 권선형 유도발전기의 정출력.고역률 운전

  • 이우석 (부산정보대학 전기전자계열) ;
  • 김광태 (부산정보대학 전기전자계열) ;
  • 정순용 (부산정보대학 전기전자계열) ;
  • 손제봉 (부산정보대학 전기전자계열) ;
  • 배종문 (부산정보대학 전기전자계열)
  • Published : 2000.07.17

Abstract

Wide operating range and speed control is needed for wind power generating and a Doubly Fed Induction Generator(DFIG) has good adaptivity for that purpose. This paper deals with power and power factor control using the Grid connected DFIG in the wide speed regions, by controlling frequency and voltage fed to the rotor. Power flow of the DFIG and steady-state algebraic equations of the equivalent circuit are analyzed. For a normal operating region, in which the generator ratings were not exceeded, the rotor current was either less than or equal to the rated value. Accordingly, the optimal power factor can be selected relative to the permissible rated current at the rotor coil which controls the magnitude of the injected rotor voltage to the rotor according to a given rotor frequency.

Keywords