Implementation of Feedback Control System in Profibus-DP

Profibus-DP에서의 Feedback 제어시스템 구축

  • 강송 (부산대학교 기계공학부) ;
  • 이경창 (부산대학교 기계공학부) ;
  • 이석 (부산대학교 기계공학부)
  • Published : 2000.10.01

Abstract

As many sensors and actuators are used in various automated systems, the application of network system to real-time distributed control is gaining acceptance in many industries. In order to take advantages of the network technique. however, network implementation should be carefully designed to satisfy real-time constraints and to consider network delays. This paper presents the implementation of feedback control system in Profibus-DP. Profibus-DP is a type of fieldbus protocols that are specifically designed to interconnect simple devices with fast I/O data exchange. As feedback control in profibus-DP is implemented, Network delays is found with influence of system performance. We analyze network delays in Profibus-DP into 3 reasons - dead time in Profibus interface, protocol delay, delay by asynchronization. In order to compensate the network delays, we introduce control algorithms with time delay concept. The results show that network delay can be compensated.

Keywords