345kV 및 154kV 송전철탑의 뇌사고율 예측계산

The Calculation of Lightning Flashover rate of 345kV/154kV Transmission Tower

  • 발행 : 2001.07.18

초록

This paper described the calculation results of lightning flashover rate on the 345kV and 154kV transmission system of KEPCO. The back-flashover rate and shielding failure rate was calculated by FLASH(lightning flashover rate calculation program from IEEE) and KEPRI's own program which is based on the EGM(Electro Geometrical Model) method. The estimated lightning flashover late of 345kV transmission system of double circuit was 1.0 flash per 100km-year, and the lightning flashover rate of 154kV transmission line was 2.0 flash Per 100km-year approximately.

키워드