과부하 및 경년 변압기 절연유 열화 특성 분석 연구

Analysis of Aging Characteristics in Oil Immerged Pole Transformer

  • 발행 : 2002.05.17

초록

In order to evaluate the aging of mineral oil immersed distribution transformers, it gathered some insulation oil in over loaded and long time(exceed their service life, 13yrs.) aged transformers in the field, we measured moisture content, acid number, dielectric strength of the oil as defined in KS C 2101 standard. And also, it had been measured dielectric constant, specific resistant, $tan{\delta}$ on aged transformer oil at from $10^{\circ}C$ to $130^{\circ}C$. These results are compared with a new mineral oil. From this study, it can be considered that the analysis of mineral oil may be suitable for evaluation of life expectancy in distribution transformers

키워드