Analysis of the first order eigenvalue sensitivity affected by generator model

발전기 모델링 정도에 의한 고유치 감도계수에 미치는 영향해석

  • Cho, Eon-Jung (School of Electronic & Information Eng. Kunsan National Univ.) ;
  • Lee, Kun-Jae (School of Electronic & Information Eng. Kunsan National Univ.) ;
  • Kim, Deok-Young (School of Electronic & Information Eng. Kunsan National Univ.)
  • 조언중 (군산대학교 전자정보공학부) ;
  • 이군재 (군산대학교 전자정보공학부) ;
  • 김덕영 (군산대학교 전자정보공학부)
  • Published : 2003.07.21

Abstract

In small signal stability analysis of power systems, eigenvalue analysis is the most useful method and the detailed modeling of generator gives an important effect to the eigenvalues. Generator full model is used for precise dynamic analysis of generators and controllers while two-axis model is used for multimachine systems because of the reduced order of the state matrix. Also, the eigenvalue sensitivity coefficients are used for optimization of controller parameters to improve system stability. This paper compare the first order eigenvalue sensitivity coefficients of controllers in case of generator full model with those of two-axis model. As a result of an example the estimated eigenvalues using sensitivity coefficients in case of generator full model is very close to those of state matrix within 1% error ratios.

Keywords