Abstract

This paper researched leakage current characteristics of EHW insulators(36,000lbs) to artificially contaminated clay and kaolin through construction of long-periods testing facility. Insulators were contaminated and classified into the ESDD level(B, C and D) under IEC Pub. 60507 standards method. As a result of tests, leakage current of the heavily contaminated D level to clay was approximately 2,260 $[\muA]$, which is contaminated to kaolin was approximately 3,200 $[\muA]$, during initial rainfall. However after raining, leakage current of naturally washed contamination insulators was lower at approximately 300 $[\muA]$. As regular temperature $20^{\circ}C$, leakage current increased greatly in case humidity density was over $72\%$. But, leakage current was not influenced by temperature variation in case of regular $\%$ humidity.

Keywords