Noise and vibration reductions in exhaust duct system of cogeneration power plants

열병합발전소 배기 덕트 시스템의 소음 진동 저감

  • 김원현 (현대중공업 선박해양연구소 동역학연구실) ;
  • 주원호 (현대중공업 선박해양연구소 동역학연구실) ;
  • 배종국 (현대중공업 선박해양연구소 동역학연구실)
  • Published : 2004.11.01

Abstract

Noise and vibration was encountered in exhaust duct system which is connected with a gas turbine and a heat recovery steam generator(HRSG) of a cogeneration power plants. Especially, these problems occurred when water was added to the fuel injection to reduce NOx contents of the exhaust gas. Through the cavity mode analysis and measurements, It was concluded that these problems occurred due to the acoustic resonance between the duct cavity mode and the excitation force induced by turbulent gas flow during water injection. To reduce the noise and vibration, optimal baffle plate to change the cavity mode was installed inside of duct and noise levels of about 8 dB(A) are reduced in duct system. The effects of baffle plate and guide vane to the HRSG or inlet duct vibration were also evaluated and it was verified that there is no relation to the resonance phenomena. So, vibration of inlet duct was easily reduced by the reinforcement of structures.

Keywords