A Distance Protection Algorithm for a Transmission Line to Interconnect a Wind Farm to a Utility System

풍력발전단지 연계 전용선로 보호용 거리계전 알고리즘

  • 권영진 (명지대학교 차세대전력기술연구센터) ;
  • 강상희 (명지대학교 차세대전력기술연구센터) ;
  • 최동민 (명지대학교 차세대전력기술연구센터) ;
  • 장성일 (명지대학교 차세대전력기술연구센터)
  • Published : 2005.07.18

Abstract

This paper presents a distance protection algorithm a lied to the linked line for interconnecting wind farm with the utility. The capacity of wind farm is lower than utility system and its fault current level is very low. When a high resistance fault occurs in the linked line, it is difficult to detect accurate fault distance because of reactance effect. By using the characteristic of equivalent source impedance of induction generator which is compensated by capacitor bank and characteristic of the capacity of wind farm, this paper proposes improved distance protection algorithm applied to the linked line. A series of PSCAD/EMTDC simulation results have shown effectiveness of the proposed algorithm.