Development of Hold on Swing a Jumper Support String for Overhead Transmission Line

송전선로 점퍼선 횡진방지용 지지애자장치 개발

  • Published : 2005.07.18

Abstract

A Jumper wire is currently used to connect each fixed power line on both sides of dead end tower for overhead transmission line, but in case of a jumper wire swing under circumstances of typhoon, etc. and the air clearance is deficient then a flashover fault may Happen. Now the angle tower has the jumper support string to prevent a swing of jumper wire and to secure the air clearance between jumper wire and tower main body, but the flashover fault by swing of jumper wire was happened yl times across all over the country, because of the typhoon 'Rusa' in year 2002 and 'Maemi' in year 2003. This paper presents the design and development of 'Counter Weight' which enables to keep the swing angle of jumper wire under 40 degree in design condition to prevent a flashover fault by swing of jumper wire by a high wind pressure load in case of typhoon and have completed a mechanical and electrical characteristic test.

Keywords