AC loss Measurement of Superconducting Power Cable

초전도 전력케이블의 교류손실 측정

  • 황시돌 (한국전력공사 전력연구원) ;
  • 현옥배 (한국전력공사 전력연구원) ;
  • 손송호 (한국전력공사 전력연구원) ;
  • 최형식 (한국전력공사 전력연구원)
  • Published : 2005.07.18

Abstract

As a research activity of the project of "Verification Test of Superconducting Power Cable", we measured the AC loss of a short length superconducting power cable. The rating and the length of the cable were 22.9kV, 1,250A and 2.2m. The voltage taps for measuring the AC loss were attached to both ends of the conductor of the superconducting cable. Through the voltage taps and a lock-in amplifier we measured the in-phase component of the voltage($V_x$) with the load current(I). The AC loss was measured by multiplying the in-phase component of the voltage($V_x$) by the load current(I). The value of the AC loss of the superconducting power cable was 1.18W/m/phase/kA at 77.3K, 1atm.