Comparison of Individual and Common Grounding Method for Potential Rise

전위상승에 대한 독립접지방식과 공통접지방식의 비교

  • Gil, Hyoung-Jun (Electrical Safety Research Institute, subsidiary of KESCO) ;
  • Kim, Dong-Ook (Electrical Safety Research Institute, subsidiary of KESCO) ;
  • Kim, Dong-Woo (Electrical Safety Research Institute, subsidiary of KESCO) ;
  • Lee, Ki-Yeon (Electrical Safety Research Institute, subsidiary of KESCO) ;
  • Choi, Chung-Seog (Electrical Safety Research Institute, subsidiary of KESCO)
  • 길형준 (한국전기안전공사 전기안전연구원) ;
  • 김동욱 (한국전기안전공사 전기안전연구원) ;
  • 김동우 (한국전기안전공사 전기안전연구원) ;
  • 이기연 (한국전기안전공사 전기안전연구원) ;
  • 최충석 (한국전기안전공사 전기안전연구원)
  • Published : 2006.05.26

Abstract

This paper deals with a comparison of individual and common grounding method for potential rise. When a test current flowed through grounding electrode, potential rise was measured and analyzed for grounding method using a electrolytic tank in real time. The grounding electrodes were designed and fabricated with ground rods on a scale of one-eightieth. Potential rises of individual grounding method were higher than those of common grounding method. The distributions of surface potential are dependent on the distance from grounding electrode.

Keywords